INSTALLING THE HYDRO KIT

Placing the Hydro Kit Controller

Placing the Hydro Kit Controller
Hydro Kits include a factory-supplied controller (with integral temperature sensor), but also can be used with remote temperature sensors
and third-party thermostats (optional; sold separately). If the Hydro Kit's water flow will be controlled by monitoring the conditioned space
temperature, proper Hydro Kit operation depends on the location of the controller (sensor, thermostat). A good location will be to protect
the controller (sensor, thermostat) away from direct sunlight, high
humidity, water vapor, and where it could be directly exposed to cold
air. Controller (sensor, thermostat) must be installed four (4) to five
(5) feet above the floor where its display can be read easily (if regu-
lations of the American Disability Act [ADA] do not require a lower
mounting height), in an area with good air circulation, and where it
can detect an average room temperature.
Do not install the controller (sensor, thermostat) where it can be
impacted by the following:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Radiant heat from sun or appliances
• Concealed pipes and chimneys
• Uncontrolled areas such as an outside wall behind the remote
controller
1. Pull cable between the controller handy box (if used) and the
Hydro Kit.
2. Store a minimal amount of cable in the handy box.
3. If the cable between the controller (sensor, thermostat) and the Hydro Kit is too long,
cable, tie-wrap it, and leave it next to the Hydro Kit location.
Do not route power wiring and communications cables in the same conduit. Routing power wiring and communications cables together
will cause communication errors and unit malfunction.
• Maintain at least the minimum distance required between the communications cable and power wiring. The minimum required space be-
tween the two depends on the voltage of the power wiring. See the Wiring section in this manual for more information
Do not cut any quick-connect plugs off or adjust the length of the cable.
• Keep the communications cable away from high voltage wires and electromagnetic field (EMF) producing equipment. It will result in com-
munication errors and unit malfunction.
26
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
YES
TEMP
Remote Controlle r
NO
Remote Controlle r
4 to 5 feet
above the floor
TEM
P
roller
ot e
Cont
Rem
NO
do not cut. Coil any spare communications
TEMP
TEM
P
ot e
Cont
roller
Rem
NO

Advertisement