Siemens SIMATIC S7-1500/ET 200MP Manual page 18

Digital input module di 16x24vdc ba
Hide thumbs Also See for SIMATIC S7-1500/ET 200MP:
Table of Contents

Advertisement

Diagnostics alarms
5.1 Status and error displays
Meaning of the LED displays
The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1
RUN/ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
Flashes
Flashes
LED CHx
Table 5- 2
CHx status display
LED CHx
Off
On
18
Meaning
Voltage missing or too low at backplane bus.
Module is starting up.
Module is ready.
Hardware defective.
Meaning
0 = Status of the input signal.
1 = Status of the input signal.
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
---
---
Digital input module DI 16x24VDC BA (6ES7521-1BH10-0AA0)
Manual, 09/2014, A5E32363114-AB
Remedy