Appendix

Troubleshooting

The table below list the self-diagnostic routines. For some of error codes, you must contact an authorized service centre.
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No. Error Code
1
E108
Error due to duplicated communication address
Error on room temperature sensor of indoor unit (Short or
2
E121
Open)
3
E122
Error on EVA IN sensor of indoor unit (Short or Open)
4
E123
Error on EVA OUT sensor of indoor unit (Short or Open)
5
E153
6
E154
Indoor fan error
7
E198
Error on thermal fuse of indoor unit (Open)
Communication error between the indoor unit and outdoor
unit (Pre-tracking failure or when the actual number of
indoor units are different from the indoor unit quantity
8
E201
setting on the outdoor unit)
Error due to communication tracking failure after initial
power is supplied (The error occurs regardless of the
number of units.)
Communication error between indoor unit and outdoor
9
E202
unit (When there is no response from indoor units after
tracking is completed)
Communication error between the outdoor unit and main
10
E203
micom (For PF #4 to #6 controllers, error will be determined
from the time when the compressor is turned on.)
11
E221
Error on outdoor temperature sensor (Short or Open)
12
E231
Error on outdoor COND OUT sensor (Short or Open)
Error on discharge temperature sensor of compressor 1
13
E251
(Short or Open)
14
E320
Error on OLP sensor (Short or Open)
15
E403
Compressor down due to freeze protection control
16
E404
System stop due to overload protection control
17
E416
System stop due to discharge temperature
18
E422
Blockage detected on high pressure pipe
19
E425
Reverse phase or open phase
Heating operation restricted at outdoor temperature over
20
E440
Meaning
Remarks
Check on repeated indoor unit main address
Indoor unit Room Thermistor Open/Short
Indoor unit Float Switch Open/Short Drain Pump
operation Check
Check on indoor unit indoor Fan operation
Thermal Fuse Open Check of indoor unit Terminal Block
Check indoor quantity setting in outdoor
Check electrical connection and setting between indoor
unit and outdoor unit
Check electrical connection and setting between
outdoor unit MAIN PBA - INVERTER PBA
Check Outdoor sensor Open / Short
Check Cond-Out sensor Open / Short
Check Discharge sensor Open / Short
Check OLP sensor Open / Short
Check Outdoor Cond.
Check Comp. when it starts
-
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe connections, heat
exchanger) and charge refrigerant if necessary
3. Check if there's any blockage on the refrigerant cycle
(indoor unit/outdoor unit)
4. Check if additional refrigerant has been added after
pipe extension
Check whether 3 phase is reversed or opened.
1. Check the range of temperature limited for heating
operation
2.Check the outdoor temperature sensor
29
English