PLACEMENT
INSTALL UNIT AWAY FROM WINDOWS.
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
Figure 1.
Outdoor Section
Zoning ordinances may govern the minimum distance the
condensing unit can be installed from the property line.
Discharge Air
Building
Structure
Mounting slab must slope slightly away from
building, not to exceed 1/4" per foot.
Figure 2. Slab Mounting
Install on a Solid, Level Mounting Pad
The outdoor section is to be installed on a solid foundation.
This foundation should extend a minimum of 2" (inches)
beyond the sides of the outdoor section. To reduce the
possibility of noise transmission, the foundation slab
should NOT be in contact with or be an integral part of the
building foundation. See Figure 2.
If conditions or local codes require the unit be attached to
pad or mounting frame, tie down bolts should be used and
secured to unit base pan.
Elevate Unit
Accumulation of water and ice in base pan may cause
equipment damage.
508296-01
Mounting Slab
Ground Level
CAUTION
Elevate unit per local climate and code requirements to
provide clearance above estimated snowfall level and
ensure adequate drainage of unit. Use snow stand in areas
where prolonged freezing temperatures are encountered.
If conditions or local codes require the unit be attached to
pad or mounting frame, tie down bolts should be used and
fastened through knockouts provided in unit base pan.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. For proper airflow,
quiet operation and maximum efficiency. Position so water,
snow, or ice from roof or eaves cannot fall directly on unit.
Refer to Table 1 for installation clearances.
Location
Service box
Top of unit*
Between units
Against wall
* Maximum soffit overhang is 36".
NOTE: At least one side should be unobstructed by a wall or
other barrier.
Note: See Table 1 for specific minimum clearance guidelines.
DO LOCATE THE UNIT:
With proper clearances on sides and top of unit
On a solid, level foundation or pad (unit must be level
to within ± 1/4 in./ft. per compressor manufacturer
specifications)
To minimize refrigerant line lengths
Issue 2231
Minimum Clearance
30"
48"
24"
Table 1. Clearances
24"
6"*
30" around
Control
Box
Figure 3.
6"
Page 3 of 25