  (ii) Regardless of the setting temperature, the cooling or heating operation mode is judged according to the "Judgment
based on Room temperature/Cooling or Heating and Outdoor temperature/Cooling or Heating".
1)  I n case of "Room temperature/Cooling < Indoor return air temperature" and "Outdoor temperature/Cooling < Out-
door air temperature" ⇒ Operation mode: Cooling
2)  I n case of "Room temperature/Heating > Indoor return air temperature" and "Outdoor temperature /Heating > Out-
door air temperature" ⇒ Operation mode: Heating
3) The outdoor air temperature of the above judgment conditions is sampled at every 10 minutes.
4) In the range where the above cooling and heating zones are overlapped ⇒ Forced thermostat OFF
30
28
26
24
22
20
18
16
14
12
(2)

Operations of functional items during cooling/heating

Operation
Thermostat
Functional item
Compressor
4-way valve
Outdoor unit fan
Indoor unit fan
(3)
Drain pump
Notes (1)
: Operation
(2) ON during the drain motor delay control.
(3) Drain pump ON setting may be selected with the indoor unit function setting of the wired remote control.
(3)

Dehumidifying (DRY) operation

Return air temperature sensor [Thi-A (by the remote control when the remote control thermistor is enabled)] controls the
indoor temperature environment simultaneously.
(a)
Operation is started in the cooling mode. When the difference between the return air temperature and the setting
temperature is 2°C or less, the indoor unit fan tap is brought down by one tap. That tap is retained for 3 minutes
after changing the indoor unit fan tap.
(b) If the return air temperature exceeds the setting temperature by 3°C during dehumidifying operation, the indoor
unit fan tap is raised. That tap is retained for 3 minutes after changing the indoor unit fan tap.
(c)
If the thermostat OFF is established during the above control, the indoor unit fan tap at the thermostat ON is
retained so far as the thermostat is turned OFF.
Room temperature/Cooling
Forced thermostat OFF
Forced thermostat
OFF
Heating
12
14
16
18
20
Indoor return air temperature (℃)
Cooling
Fan
Thermostat
ON
OFF
(2)
(2)
: Stop
/ : Turned ON/OFF by the control other than the room temperature control.
168
-
Room temperature/Heating
Cooling
Forced thermostat
OFF
22
24
26
28
30
Heating
Thermostat
Thermostat
ON
OFF
/
/
/
(2)
-
'18 • SCM-T-251
Outdoor temperature/Heating
Outdoor temperature/Cooling
Dehumidifying
Hot start
(Defrost)
/
( )
( )
/
/
/
Thermostat ON:
(2)
Thermostat OFF: