3.2.2 Remote control (Option parts)
(1) Wired remote control
Model RC-EX3A
Dimensions (Viewed from front)
Fixing holes
固定穴
37
23
37
23
120
● Do not install the remote control at following places.
(1) It could cause break-down or deformation of remote control.
・Where it is exposed to direct sunlight
・Where the ambient temperature becomes 0 °C or below, or 40 °C or above
・Where the surface is not flat
・Where the strength of installation area is insufficient
(2) Moisture may be attached to internal parts of the remote control, resulting in a display failure.
・Place with high humidity where condensation occurs on the remote control
・Where the remote control gets wet
(3) Accurate room temperature may not be detected using the temperature sensor of the remote
control.
・Where the average room temperature cannot be detected
・Place near the equipment to generate heat
・Place affected by outside air in opening/closing the door
・Place exposed to direct sunlight or wind from air-conditioner
・Where the difference between wall and room temperature is large
(4) When you are using the automatic grille up and down panel in the IU, you may not be able to
confirm the up and down motion.
・Where the IU cannot be visually confirmed
● When installing the unit at a hospital, telecommunication facility, etc., take
measures to
suppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power
generator, high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could
disrupt medical activities, video broadcasting or cause noise interference.
23
23
120
Installation space
Wiring
配線
30mm
30mm
19
19
42
-
-
'20 • KX-T-373
30mm
30mm
30mm
30mm
R/C temperature sensor
Secure minimum spaces for disassembling the case.
Upper left and Upper right sides
......30mm or more
Bottom side...120mm or more
If using L-shaped screwdriver, 50mm or more is
available.
R/C cable:0.3mm
When the cable length is longer than 100m,
the max size for wires used in the R/C case
2
is 0.5mm
. Connect them to wires of larger
size near the outside of R/C. When wires are
connected, take measures to prevent water,
etc. from entering inside.
≦ 200 m
0.5mm
≦ 300m
0.75mm
≦ 400m
1.25mm
≦ 600m
2.0mm
Adapted RoHS directive