REMOTE DISPLAY PANE INSTALLATION AND OPERATION INSTRUCTIONS
APPROVALS
Nonhazardous Locations
KIT CONTENTS
Item Qty
Description
A
1
Display panel with mounting screws
B
1
Single duplex outlet cover plate with mounting screws
WARNING:
This unit should be installed, opened, and repaired by qualified
personnel only.
To avoid shock hazard, do not open the front cover with power
connected to the controller or any controlled equipment.
THERMAL BUILDING SOLUTIONS
ECW-GF-DP
Always open any circuit breakers and remove power from any high
voltage electrical circuits installed in close proximity to or sharing
an enclosure with the ECW-GF-DP prior to removing the enclosure
cover plate.
EN-RaychemECWGFDP-IM-H58410      03/15
DESCRIPTION
The Raychem ECW-GF-DP is a remote display panel only for the
Raychem ECW-GF electronic controller. The ECW-GF-DP allows
remote monitoring of the heating cable system operation. The
display has LED indicators which signal communication loss to the
controller, high/low temperature alarm, and temperature sensor
failure. The display also has buttons to test and reset the ground-
fault sensor. The display may be located up to 328 feet (100 m)
from the ECW-GF controller.
The ECW-GF-DP remote display panel must be installed in
conjunction with the ECW-GF controller. Refer to the ECW-GF
installation instructions (H58339) for further details.
For technical support, call Pentair Thermal Management at
(800) 545-6258.
TOOLS REQUIRED
• Large slotted screwdriver
• Small slotted screwdriver
ADDITIONAL MATERIALS REQUIRED
• Duplex junction box
• 1/2 inch conduit
• Communication cable: 8 conductor 22 AWG shielded
Alpha Cat. No. 1298C or equivalent
A
B
Read all instructions carefully before installation. Save this
Installation and Operation Instruction for future reference.
• Needle nose pliers
• Wire strippers
1 / 4

Advertisement

loading

Summary of Contents for Pentair Raychem ECW-GF-DP

  • Page 1 ECW-GF-DP REMOTE DISPLAY PANE INSTALLATION AND OPERATION INSTRUCTIONS DESCRIPTION The Raychem ECW-GF-DP is a remote display panel only for the Raychem ECW-GF electronic controller. The ECW-GF-DP allows remote monitoring of the heating cable system operation. The display has LED indicators which signal communication loss to the controller, high/low temperature alarm, and temperature sensor failure.
  • Page 2 System Illustration The ECW-GF-DP remote display panel is only compatible with the ECW-GF controller. ECW-GF Conduit ECW-GF-DP Power Ambient thermister Heating cable • Install the ECW-GF-DP in an indoor dry location in a standard duplex junction box, up to 328 ft (100 m) from the ECW-GF. 328 ft (100 m) max.
  • Page 3 • Prepare communication cable by • Connect the communication cable to stripping 1/4 in of insulation from the ECW-GF controller. each wire. • Terminate cable shield in the SH • Install wires according to Steps 4 position on the J5 (Thermistor) ECW-GF and 5.
  • Page 4 Fax: +1.650.474.7711 thermal.info@pentair.com Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2011-2015 Pentair. PN P000001089 THERMAL BUILDING SOLUTIONS EN-RaychemECWGFDP-IM-H58410      03/15...