2.21.55 Basic stage cooling
Note
Only available when the "Extended settings" parameter under "Cooling control"
is set on "Yes".
2.21.56 Basic stage cooling — Status object cooling
Options:
This parameter enables the "Status cooling" communication object.
2.21.57 Basic stage cooling — Mode of the control value
Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
–
Normal: Value 0 means "Valve closed".
–
Inverse: Value 0 means "Valve open".
Product manual 2CKA001473B5023
Control elements and application parameter
Deactivated
Activated
Normal
Inverse
Application "Internal RTC"