Maintenance
Error
message
code
HART communi‐
141
H
cation error
HART primary var‐
142
H
iable out of range
HART analog out‐
143
H
put current of
field device satu‐
rated
HART output cur‐
144
H
rent of the field
device fixed
HART error - addi‐
145
H
tional status infor‐
mation available
HART configura‐
146
H
tion changed
1
HART malfunc‐
147
H
tion in the field
device
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA
Assignment
Meaning / Cause
Analog input
HART field device is not responding
Timing error
HART field device did not understand the
command that was sent (1st status byte)
Analog input
Incorrect parameters in the HART field
device
HART field device is set to "Primary vari‐
able out of range" in simulation mode
Incorrect measuring point
Parameter assignment of primary varia‐
ble out of range
Analog input
The output current of the HART field de‐
vice is saturated:
Incorrect parameters in the HART field
device
HART field device is set to a measured
value that is too high in simulation mode
Incorrect measuring point
Analog input
The output current of the HART field de‐
vice is fixed:
Incorrect parameters in the HART field
device
HART field device is set to a measured
value that is too high in simulation mode
Incorrect measuring point
Analog input
In the HART device status (in the 2nd status
byte), the HART field device identifier for
"further status information available" has
been set
Analog input
In the HART device status (in the 2nd status
byte), the identifier for "re-parameteriza‐
tion" of the HART field device has been set
Analog input
In the HART device status (in the 2nd status
byte) the field device reports a malfunction
Displays, alarms and messages
7.5 Maintenance events
Remedy
Check the process wiring
Correct the parameter as‐
signment
Set current ≥4 mA
Increase number of config‐
ured repetitions
Check the parameter as‐
signment of the HART de‐
vice
Correct the simulation
Check whether the correct
measuring transmitter is
connected
Read out status with HART
command 48 and clear error/
cause if necessary
If no diagnostics interrupt is to
be triggered by reconfigura‐
tion, the HART diagnostics
must be disabled.
Read out status with HART
command 48 and clear er‐
ror/cause if necessary
Replace the field device
73