TemperZone IMDL 40Y Installation & Maintenance

TemperZone IMDL 40Y Installation & Maintenance

Ducted fan coil units

Advertisement

Quick Links

IMDL 40Y
(c/w EC motor)
Ducted
Fan Coil Units
Fig. 1
Dimensions (mm)
FILTER ACCESS
EITHER END,
OR LIFT OUT
K
B
OVERALL
J
100
C
OVERALL
Note:
1. Allow adequate clearance for the filter (if fitted) to be removed.
2. IMDL 130 has two half length filters, 2 motors and 3 fans.
3. Left handed models have drain exit nearer supply air side.
MODEL
A
B
IMDL 40Y
685
715 255
IMDL 60Y
940
715 255
IMDL 90Y
1195 750 265 1050 255 1012 179 1026 265
IMDL 130Y
1595 750 265 1450 255 1412 179 1427 265
NOTE
The manufacturer reserves the right to change specifications at any time
without notice or obligation. Certified dimensions available on request.
Fig. 2 Optional Supply Air Spigots
100
SPIGOTS TO SUIT
FLEXIBLE DUCTING
D
(HEIGHT = E)
H
SUPPLY AIR
SPIGOT
F x G
A
OVERALL
C
D
E
F
G
550
245
512
170
795
245
762
170
Right Handed model shown
Not to Scale
ELECTRICAL
BOX
DRAIN
19 OD
S/A SPIGOT
WATER
CONN'S
OUT
IN
WATER CONN'S
BSP MALE
H
J
K
COLD HOT
526
225
470
20
13
775
225
470
20
13
510
25
13
510
25
13
MODEL
SPIGOTS
IMDL 40
200 dia (x2)
IMDL 60
250 dia (x2)
IMDL 90
250 dia (x3)
IMDL 130 250 dia (x4)
Installation &
Maintenance
GENERAL
The IMDL-Y ducted fan coil units must be
installed in accordance with all national and
local safety codes.
Optional
1. Supply air spigots adaptors (refer Fig.2).
2. Flexible hoses:
- 13 BSP (1/2") part no. 060-000-270
- 20 BSP (3/4") part no. 060-000-271
- 25 BSP (1") part no. 060-000-272.
3. Electric heater elements (factory fitted).
INSTALLATION
Positioning & Mounting
Provide 500 mm minimum clearance to the
electrical box end of the unit.
Allow adequate clearance for the filter to be
withdrawn to its full length from either end of
the unit. Alternatively the filter may be lifted
out of its track.
Left handed models have drain exit on
supply air side of the drain tray.
Install the unit suspended on threaded rods
or bolts and locking nuts (not supplied).
Alternatively mount each unit on vibration
isolators on a suitable platform.
The unit must be installed level. Use the
adjustable support bracket (see figure 3)
to lower the drain pipe outlet and provide a
slope in the drain tray.
WATER SUPPLY & RETURN
The IMDL unit's IN and OUT water
connections are male pipe threaded
(refer Fig. 1). Warning: overtightening of
connections to the main water supply may
damage the unit.
It is recommended you use two temperzone
600 mm flexible high pressure water
hoses. These have female pipe threaded
connections at each end. Maximum water
pressure for each hose is 1720 kPa (250
psi). The IMDL unit alone, excluding hoses,
will withstand 4480 kPa (650 psi).
Poor quality water supply must be pre-
filtered and it is essential that adequate
water treatment is maintained, particularly
where open cooling towers are used.
Condensate Drain
The drain should have a slope of at least
1 in 50 and must not be piped to a level
above the unit drain tray. Fit a vent pipe
within 500 mm of the unit (see Fig.3).
Check the drain by pouring water into the
drain tray and ensuring that it clears.

Advertisement

loading

Summary of Contents for TemperZone IMDL 40Y

  • Page 1 715 255 damage the unit. IMDL 90Y 1195 750 265 1050 255 1012 179 1026 265 It is recommended you use two temperzone IMDL 130Y 1595 750 265 1450 255 1412 179 1427 265 600 mm flexible high pressure water hoses.
  • Page 2 ELECTRICAL WIRING ELECTRIC HEAT (Option) Fig. 3 Condensate Drain Electrical work must be carried out by a Units installed with electric heat elements qualified electrician in accordance with local include both auto (90°C) and manual supply authority regulations and the wiring (120°C) high temp.
  • Page 3 Power Relay Earth Stud MODIFICATION DATE APVD Model IMDL40Y-SPE Fan full load current (FLA) Initial release. 13-12-21 ECN 5016 S.S. ©temperzone Ltd 2021 Title: Drawing No: Rev: IMDL 40Y-SPE S.S. 13/12/21 Drawn: Date: Client Wiring 291-003-481 Electrical Wiring Schematic Apprvd:...
  • Page 4 Electric Heat current 6.5A Electric Heat kW Initial release. ECN 5016 S.D.H. 13/12/21 ©temperzone Ltd 2021 Title: Drawing No: Rev: S.D.H. IMDL 40Y-SPE EH c/w SSR Drawn: Date: 13/12/21 Client Wiring 291-003-480 Electrical Wiring Schematic Apprvd: SHEET 1 OF 1...