TemperZone OPA 465RKTB Installation & Maintenance

Air cooled packaged units - reverse cycle - r410a

Advertisement

Air Cooled Packaged Units - Reverse Cycle - R410A
1. GENERAL
Follow these instructions to ensure the optimum
performance, reliability and durability.
Units must be installed in accordance with all national and
regional regulations and bylaws. National Health and Safety
regulations must be followed to avoid personal injuries.
2. INSTALLATION
Refer to dimension diagrams below (Fig.1) for minimum
clearances. If multiple units are to be placed side-by-side
then allow at least 2m between coil faces.
500 MIN. CLEARANCE
OUTDOOR
AIR FLOW
ELECTRICAL
ACCESS
PANEL
OUTDOOR
AIR FLOW
500 MIN. CLEARANCE
2000 MIN. CLEARANCE
Figure 1.
2.1 Mounting
The unit should be fastened to a firm flat horizontal
base using the holes supplied in the mounting
channels. When the unit is being installed on a roof it is
recommended that the unit is installed on a substantial
structure with vibration isolating springs beneath the
unit. These springs are not supplied with the unit.
Flexible duct connections are recommended between
the supply and return ducts and the unit.
Unit is shipped with wooden blocks installed under the
compressors. Ensure these blocks are removed from
the compressor feet prior to starting the unit
(not required for operation).
OPA 465–960 RKTB (c/w UC6)
Installation & Maintenance
OPTIONAL
WEATHER
HOOD
RETURN
AIR
1000 MIN.
CLEARANCE
FOR FILTER
ACCESS
SUPPLY
AIR
FAN
ACCESS
PANEL
1000 MIN. CLEARANCE
The appropriate local permits must be acquired and
adhered to.
Local regulations on maximum boundary noise need to
be considered when positioning the unit.
Factory filter slides are fitted. Access to the filter access
door should be considered when designing return
and supply air ductwork. Access to the filters can still
be achieved by removing the return air access door,
however it is imperative that the rubber insulating
washers be refitted to the screws prior to replacing
the panel.
2.2 Condensate Drain
The condensate drain should be 'U' trapped outside the
unit. The trap should have a vertical height of at least
100 mm. The drain should have a slope of at least 1 in
50 and must not be piped to a level above the unit drain
pipe. (refer fig. 2)
100 mm
APPROX.
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
Figure 2.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
OPEN
DRAIN
003-000-029 02/17

Advertisement

Table of Contents
loading

Summary of Contents for TemperZone OPA 465RKTB

  • Page 1 OPA 465–960 RKTB (c/w UC6) Air Cooled Packaged Units - Reverse Cycle - R410A Installation & Maintenance 1. GENERAL Follow these instructions to ensure the optimum The appropriate local permits must be acquired and performance, reliability and durability. adhered to. Units must be installed in accordance with all national and Local regulations on maximum boundary noise need to regional regulations and bylaws.
  • Page 2: Refrigeration System

    4.2 Unit Controller (UC6) or in steps, in order to protect against excessively low or The temperzone Unit Controller 6 (UC6) combines the high head pressure. µPC controller board from Carel plus an interface board Refer to temperzone for operation &...
  • Page 3: Startup Procedure

    5. STARTUP PROCEDURE 5.1 Pre-Startup 3. Compressors fitted are directional. Check for correct rotation. If rotation is incorrect the compressor will 1. Leave the external temperature controller on/off switch not pump, be noisy, and will draw minimal current. in the off position and close the unit’s mains isolating To correct motor rotation, change the phasing at the switch.
  • Page 4: Sensor Alarm

    6.6 Compressor lock-out When indoor coil frost protection is activated the compressor is stopped for 15 minutes, after which it is Certain faults (as outlined in the preceding paragraphs) allowed to restart. can cause the unit to be “locked out” if they occur three consecutive times while the compressor-run If three consecutive trips occur then the unit will be request has remained active.
  • Page 5: Performance Data

    9. PERFORMANCE DATA Air Handling Note: Airflows are for a dry coil. Reduce airflow by 5% In high moisture removal conditions. In a free blow or low resistance application, beware of exceeding indoor fan motor’s full load amp limit (refer wiring diagrams). As filters are optional, the fan air flows given are for units installed without filters.
  • Page 6 10. CONTROLS 10.1 Modbus Connections The bridging wires should be screwed to terminals A and B separately and should be long enough to be used as the bridging cables between the 24 V hot terminal and compressors 1 and 2. If in the event a TZT is not used, they can stay there and not be of anyone’s concern.
  • Page 7: Communication Ports

    Note 1: Connectors to the UC6 show R+/T+ for signal A, R-/T- for signal B. 11.2 Temperzone TZT-100 thermostat connection The UC6 can connect directly to the temperzone TZT-100 thermostat using a shielded cable with two twisted pair wires suitable for RS485 serial communications. The drawing below shows connection details.
  • Page 8: Troubleshooting

    13.4 In a new building, why does it take some days operation & fault diagnostics information; before the air conditioning heat hump unit seems model search ‘UC6 - www.temperzone.biz to work properly • Many new buildings, especially a commercial 14. WARRANTY Please refer to the separate warranty document supplied with the unit, or visit www.temperzone.biz...
  • Page 9 OPA 465RKTB - 9 -...
  • Page 10 OPA 550RKTB - 10 -...
  • Page 11 OPA 705RKTB For SW2 (DIP switch) For SW2 (DIP switch) settings- Refer table settings- Refer table - 11 -...
  • Page 12 OPA 800RKTB - 12 -...
  • Page 13 OPA 850RKTB - 13 -...
  • Page 14 OPA 855RKTB - 14 -...
  • Page 15 OPA 960RKTB - 15 -...
  • Page 16 (Head Office and Manufacturing) Sydney (Australian Head Office and Manufacturing) Wellington, Christchurch Brisbane, Melbourne, Adelaide Singapore, Shanghai Distributors North Queensland, Perth, Hobart, Newcastle Singapore, Shanghai, Beijing, Jakarta, Hong Kong, Sri Lanka, Mauritius, Bangalore, Bangkok, Hanoi, Cambodia, South Pacific Islands, Bangladesh www.temperzone.biz...

Table of Contents