Viking Oxeo PR LCP Operator's Manual

Inert gas extinguishing system
Table of Contents

Advertisement

Quick Links

Operator's Manual
Oxeo Inert Gas Extinguishing System

Advertisement

Table of Contents
loading

Summary of Contents for Viking Oxeo PR LCP

  • Page 1 Operator’s Manual Oxeo Inert Gas Extinguishing System...
  • Page 2 This document is a translation of the original German document with modifications specific to the usage in North and South America. The Viking Corporation 210 N. Industrial Park Dr. Hastings, MI 49058 Phone: 269-945-9501 Fax: 269-818-1680 www.vikinggroupinc.com...
  • Page 3: Table Of Contents

    4.3 Manifold 200 bar and 300 bar, DN50........4.4 Check valve KRV-2 ..............4.5 Extinguishing cylinder with quick release valve QRV ..4.6 Hose for extinguishing agent ..........Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 4 8.1 Warnings regarding the cleaning of the system..... 8.2 Cleaning the system..............9 Servicing and Repair ............10 Malfunctions............... 10.1 Warnings regarding troubleshooting ......10.2 Fault indicators ................. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 5 12.1 Operating conditions.............. 12.2 Emissions ..................13 Appendix A - Weekly Inspections....... 14 Safety Data Sheet - IG-01 (Argon)....... 15 Safety Data Sheet - IG-100 (Nitrogen)....... Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 6 Table of Contents Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 7: General

    This manual is intended for the operator of the fire extinguishing system. 1.1 Information About this Manual This manual describes the operation of Oxeo inert gas extinguishing systems “Oxeo PR LCP” with a pressure reducer (also referred to hereinafter as “system”). Information about fire detection and electrical control is not part of this manual.
  • Page 8: About This Document

    Wiring methods for the electrical release devices are to be in accordance with the provided installation instructions for the UL Listed fire detection and extinguishing control panel. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 9: Requirements For Detection Elements And Control Panels

    UL listed or FM Approved fire detection system/electric control device that is compatible with the release device. Likewise, all fire detection devices must also be UL-listed or FM-accredited and com- patible with the fire detection system/electric control device. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 10: Copyright

    Copyright violators shall also receive a written warning and be liable to pay costs. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 11: Safety

    WARNING The signal word describes a danger with a high risk level. If the danger is not avoided, it will result in death or serious injury. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 12: Warnings In Instructions

    CAUTION Clamping danger on the cover Carefully close the cover. 2. Tighten screw. 2.3 Intended use This system is designed exclusively for the intended use described here. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 13 • Do not use the protection zone for any purpose other than the one intended by the Authorized Distributor. • Do not hang objects from pipe lines. • Do not block the extinguishing nozzles or the ventilation devices. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 14: Safe Operation

    Any changes, extensions or modifications not approved by the manufacturer are the sole responsibility and liability of the person making the modification and exclude any responsibility of the manufacturer. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 15: General Dangers

    • Shut down the power supply immediately and consult the Authorized Distributor in the event of damage to the wire insulation. • Keep moisture away from live components. This may lead to short circuits. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 16 • Leave the extinguishing zone without delay and within the pre-discharge timer when an alarm is given. • Stay out of the direct flow area of a discharge nozzle. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 17 • Exit the extinguishing zone without delay and within the pre-discharge timer when an alarm is given. • Do not place any sensitive objects (e.g. hard drives) directly into the discharge zone of the discharge nozzles. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 18: Qualification Of Personnel

    • All work should be carried out only by persons qualified to do so. Before starting any work, the following persons must be designated who have the knowledge required to operate the system: Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 19 The person in charge of the system has been appointed by the owner as the person who is respon- sible for the correct and proper completion of the work and inspections performed on the system. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 20: System-Specific Design Specifications

    Hearing protection serves to protect hearing from high sound levels (noise). Industrial hard hat Industrial hard hats protect the head against falling objects, hanging loads and bumping against stationary objects. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 21: Operator's Obligations

    The system is used in commercial applications. The operator of the system is therefore subject to legal obligations for occupational safety. In addition to the safety instructions in this manual, the Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 22 (e.g.what to do in the case of fire, how to respond in the event of acci- dental triggering). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 23: Safety And Protective Devices

    Pressure relief dampers Pressure relief dampers are installed in the exterior walls of buildings to dissipate the pressure increase or drop that occurs when the system is activated. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 24 The locking nuts are connected to the valves by means of loss protection devices. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 25: Signage

    210 N. INDUSTRIAL PARK DR. 210 N. INDUSTRIAL PARK DR. HASTINGS, MI 49058, USA HASTINGS, MI 49058, USA NITROGEN ITROGEN IG-100 IG-100 PN 24587 PN 24588 FIGURE 2-1: System labeling Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 26 Inhaling high concentrations of these gases is hazardous to a person's health. Protect the containers from tipping over and falling down as well as from heating, impact, and shock. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 27 2. Designation: pilot cylinder 3. Pilot gas: Nitrogen 4. Filling pressure at 59 °F (15 °C) [bar] 5. Filling quantity [kg] 6. Part number of the pilot cylinder Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 28 4. Weight of extinguishing agent charge 5. Overall weight of the extinguishing agent container 6. Part numbers of the manuals: • Installation and maintenance • Operating 7. Fill station Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 29: Environmental Protection

    • If there is no danger posed to your own health, rescue people from the danger zone. • Immediately leave the extinguishing zone. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 30 After the system is triggered Certain rules of behavior apply for how to act after the system has been activated - these are explained in a separate section. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 31: Transport And Storage

    • Allow only the Authorized Distributor or service personnel authorized by the Authorized Distribu- tor to transport the components of the system. • Avoid unauthorized transport and location changes - including transporting and moving the extinguishing agent containers. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 32: Storing Extinguishing Agent Containers

    • Replace any damaged signs or labels immediately (or have them replaced). There might be notices on storage on the packaging items that go beyond the requirements stipulated here. Observe them accordingly. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 33: Design And Function

    The extinguishing agent then flows through the pressure reducer and reaches the discharge nozzles through the downstream pipe- Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 34 Optionally, a mechanical manual release device for manually activating the system can be fitted on the electric release device. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 35 In contrast to single container systems, the extinguishing agent initially flows from the hose through check valves into a manifold if a multi container system is actuated. From there, the extin- Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 36: Oxeo Unistrut Racking Arrangements

    Manifolds are intended for a one-, two-, or three- row set-up for extinguishing agent contain- ers. Manifolds with 2 to 3 inlets are available for the one-row, two-, or three-row set-ups. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 37: Check Valve Krv-2

    For safety reasons, the container batteries must be fastened to load-bearing parts of the building (wall and/or floor). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 38 This drop in pressure causes the extinguishing agent container pressure to press the closing piston in the opened position, thereby opening the valve. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 39 There is subsequently always a residual pressure in the extinguishing agent con- tainer. 4.5.2 Release device, manual, QRV FIGURE 4-8: Release device, manual 1. Manual lever 2. Split pin 3. Release pin Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 40 The electrical signal must be applied for at least 5 seconds to ensure an acti- vation. Only the following release devices may be assembled: Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 41 There, the absence or incorrect assem- bly of the electrical release device is displayed as a fault. The monitoring is mounted on the QRV valve with a clamp. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 42 6527 psi (450 bar) 3916 psi (270 bar)- NO under pressure 921617 4351 psi (300 bar) 6527 psi (450 bar) 3916 psi (270 bar)- NC under pressure Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 43: Hose For Extinguishing Agent

    ISO 228 (375 mm) Agent hose, 23.6 W21.8 x 1/14 G3/4 934922D* 600 mm long DIN 477 ISO 228 (600 mm) *Parts are special order only Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 44: Pilot Hoses For Activation Of "Slave" Cylinder

    20” Flexible Oxeo pilot hose, kit See tech data 25132 39” Flexible Oxeo pilot hose, kit See tech data 25133 59” Flexible Oxeo pilot hose, kit See tech data 25134 Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 45: Monitored Blocking

    2” NPT inlet / 2” NPT outlet pressure reducer with a 0.118” orifice diameter. See tech data for all available pressure reducer configurations and maximum orifice sizes. The pressure reducer is moreover available in two different variants: Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 46 Pressure reducer with orifice and protective screen for hole diameters of (1 mm) (0.039 in.) to 0.114 in. (2.9 mm). FIGURE 4-15: Pressure reducer 1. Inlet side 2. Outlet side FIGURE 4-16: Pressure reducer with sieve Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 47 Orifice diameters range from 0.039” (1.0 mm) to 0.114” (2.9 mm) Orifice diameters start at 0.118” (3.0 mm) NOTE: Only base part numbers shown. For the complete ordering number, refer to the Technical Data Sheet Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 48: Manifold Safety Valve

    In the event of an impermissibly high pressure, the safety valve ensures pressure relief. A blow-off line attached to the outlet on the safety valve leads the medium to safely discharge on the outside. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 49: Occupiable Space Protection Kit

    The occupiable space protection kit is comprised of components that give personnel within the extinguishing zone both warning and an egress time to vacate the area. The occupiable space pro- tection kit is comprised of the following. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 50 The control gas then flows through the pressure reducer into the con- nected pneumatic pilot line to the pneumatic system parts of the fire extinguishing system. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 51 A type plate is attached to each pilot cylinder. For safety reasons, all pilot cylinders must be mounted using a wall support set on stable building elements (e.g. a wall). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 52 The contact pressure gauge monitors any pressure drop in the pilot cylinder. The contact pressure gauge is screwed into the connection thread M12 x 1 on the quick release valve QRV. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 53 Adapter and pressure reducer FIGURE 4-22: Adapter and pressure reducer 1. Adapter 2. Pressure reducer An adapter is provided the valve thread to the 200/10 bar N pressure reducer. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 54 B - Operating connection “pneumatic pilot line”, outgoing to the extinguishing agent con- tainer battery/extinguishing agent container group (connection “B” is marked on the time delay unit and in the circuit symbol with [2]). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 55 During the delay time, flooding of the extinguishing zone can be prevented only by an optional stop valve downstream of the pneumatic time delay unit. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 56 100dB(A) to 125dB(A) is reached depending on the pressure. The makrofon can optionally be fitted with a silencer. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 57: Shuttle Non-Return Valve

    By pressure at input “A”, input “B” is closed, and there is a passage from input “A” to the output. By pressure at input “B”, input “A” is closed, and there is a passage from input “B” to the output. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 58: Pilot Pressure Relief Assemblies

    If other, unlisted components are used, this may result in failure due to over strain. This can cause fragments to fly around uncontrollably and cause life-threatening injuries. • Only use the 300 bar version (4351psi) of the complete set. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 59 The pilot pressure relief device enables the discharge of small leaks in pneumatic pilot lines using a relief bore. The pilot pressure relief device closes automatically at high pressures. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 60: Blocking Device, Pilot Line

    Pressure tapping must occur only downstream from the pressure reducer. The extinguishing agent pressure activates the cylinder, which opens or closes the floating contacts of the limit switch. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 61 For instance, they can also be used to alert the fire department. An additional push button allows you to trigger the electrical signal for test purposes. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 62: Vn Nozzle

    Two versions of the nozzle VN are available: • 360° for assembly in the middle of the room • 180° for assembly near walls Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 63: Dcm Nozzle

    The pilot lines made of precision steel pipe are connected to the components using solderless pipe unions with a cut ring in accordance with DINENISO8434-1 and DIN2353, standard steel ver- sion in accordance with DIN3859-1. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 64 Cut ring form A or B in accordance with DIN3861 or in accordance with DINENISO8434-1 • Steel pipes in accordance with DIN2394 (DINEN10305), test certificate in accordance with EN10204-3.1 Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 65: Installation And Commissioning

    (also of subcomponents). For more information on the installation and commissioning of Oxeo inert gas fire extinguishing systems, refer to the Oxeo Installation and Maintenance Manual. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 66 Installation and Commissioning Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 67: Operation

    Operation Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 68 Operation FIGURE 6-1: Overview 1. Extinguishing agent container 2. Container valve 3. Contact pressure gauge 4. Safety valve 5. Pressure reducer Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 69 The occupiable space protection kit is comprised of components that give personnel within the extinguishing zone both warning and an egress time to vacate the area. The occupiable space pro- tection kit is comprised of the following. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 70 For safety reasons, the container batteries must be fastened to load-bearing parts of the building (wall and/or floor). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 71 This drop in pressure causes the extinguishing agent container pressure to press the closing pis- ton in the opened position, thereby opening the valve. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 72 Membranes in the makrofon are made to vibrate as a result of pressurization with gas. This generates a sound at a constant frequency. This sound is ampli- Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 73 A pressure reducer downstream of the pilot cylinder reduces and regulates the control gas to a pressure of 152 psi (10.5 bar). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 74 In the event of an impermissibly high pressure, the safety valve ensures pressure relief. A blow-off line attached to the outlet on the safety valve leads the medium to safely discharge on the outside. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 75 Depending on the system, it is stored as a non-lique- fied gas under a pressure of 200 or 300 bar (2901 or 4351 psi). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 76: Resetting The Isolation In The Event Of Fire

    =>The extinguishing agent containers open instantaneously. 3. Leave the extinguishing zone immediately. 6.2 Activating the system Personnel: • Person in charge of the system Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 77 The pre-discharge timer is the time between the release of the main alarm and the beginning of the fire extinguishing process. It is usually set to 30-45 s. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 78 After the pre-warning time has elapsed, the system actuates and flooding commences. 6.2.2 Activating the system with the manual release device 1. Evacuate the extinguishing zone. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 79 The emergency stop device is used to briefly prevent extinguishing agent flooding for evacuation purposes. However, it is not suitable for preventing flooding permanently or stopping flooding that is already running. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 80: Actions After The System Is Activated

    3. Once all persons have been rescued, release the emergency stop device. =>Flooding takes place immediately but not before the remaining pre-warning time has elapsed. 6.3 Actions after the system is activated Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 81 3. Keep an eye on the fire sources that have been put out. 4. Do not clear the extinguishing zone for access until it has been sufficiently ventilated and there are no remnants of extinguishing agent left. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 82 3. Do not clear the extinguishing zone for access until it has been sufficiently ventilated and an oxygen concentration of at least 20.9% has been reached. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 83: Changing Over The Main/Reserve Change-Over

    • In the meantime, or as soon as possible, secure the valve outlet with a locking nut and the valve with a protective valve cap. • Wear safety gloves, safety footwear, protective goggles and hearing protection. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 84 Operation Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 06-2022 | en...
  • Page 85: Inspections

    • Prior to carrying out work during which heat and smoke are generated, observe the following: • Block the system. • Switch off the fire detectors. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 86 Are all wall breakthroughs sealed off to the adjoining zones? • Are the pressure relief devices closed? • Are the flow openings of the pressure relief devices unobstructed? Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 87 If one or several of these inspection questions cannot be answered with “Yes” or if you are uncertain as to the correct answer, please contact an Authorized Distributor immediately. Contact can be established through the manufacturer; see page 2. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 88 Inspections Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 89: Cleaning

    Cleaning 8.1 Warnings regarding the cleaning of the system Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | enP...
  • Page 90: Cleaning The System

    8.2 Cleaning the system Personnel: • Person in charge of the system Protective equipment: • Safety goggles • Safety gloves Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 91 1. Use a damp cloth to carefully remove dust and dirt deposits from all surfaces of the compo- nents. 2. Report any corrosion damage and/or coating stuck on the component surfaces to the Autho- rized Distributor. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 92 Cleaning Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 93: Servicing And Repair

    • Allow only the Authorized Distributor or service personnel authorized by the Authorized Distribu- tor to service and repair the system. • Avoid any unauthorized servicing and repair - also of subcomponents. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 94 Servicing and Repair Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 95: Malfunctions

    If faults occur frequently or cannot be remedied by following the instructions listed below, contact a company approved to install the system. Contact can be established through the manufacturer (see page 2). Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 96: Warnings Regarding Troubleshooting

    3. Notify the owner of all detected faults. The fault table provided below specifies who is authorized to correct a fault. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 97: Fault Indicators

    Line or cable connec- Identify damaged Authorized Distributor circuit in the loss moni- tion is faulty area and repair it toring is shown on the EST/FACP Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 98 The line fault “loss The line connection is Detect the faulty con- Authorized Distributor indication” is shown faulty (short circuit or nection wire break) Perform repairs Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 99 The shuttle non-return The seal fitting is dirty Replace the shuttle Authorized Distributor valve is leaky or not or the ball is stuck non-return valve functioning Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 100 Replace the limit Authorized Distributor switch switch Limit switch does not Pneumatic pilot line is Check the pneumatic Authorized Distributor switch faulty pilot line and repair if necessary Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 101: Correct The Display Of The Contact Pressure Gauge

    In this case, the indicator of the contact pressure gauge is located in the red zone even though no extinguishing agent leak exists. FIGURE 10-1: Contact pressure gauge Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 102: Putting The System Back Into Operation

    Allow only an Authorized Distributor or service personnel authorized by the Authorized Distributor to perform the work for the return to service of the system after troubleshooting. Contact can be established through the manufacturer; see page 2. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 103: Inspections

    • Allow only the Authorized Distributor or service personnel authorized by the Authorized Distribu- tor to perform the final shutdown and disassembly of the system. • Do not allow the final shutdown and disassembly to be performed without authorization. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 104: Disposal

    • Allow only the manufacturer of the extinguishing agent to dispose of the extinguishing agent. • Avoid unauthorized disposal. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 105: Technical Data

    (according to UL-Listing requirements) If locally applicable guidelines and standards define further restrictions, they take pri- ority. The system must not be exposed to outdoor weather conditions. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 106: Emissions

    (makrofon) The specified value is based on measurements in a laboratory with CO and IG-100. The actual value may differ due to local acoustic influencing factors. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 107: Appendix A - Weekly Inspections

    Are the manual releases accessible and in good condition? Are the automatic fire detectors intact? Are the extinguishing nozzle discharge zones unobstructed? Are all wall breakthroughs sealed off to the adjoining zones? Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 108 If any of these inspection questions cannot be answered with “Yes” or if you are uncertain on the answer, please contact an Authorized Distributor immediately. Contact can be established through the manufacturer; see last page of document. Operator’s Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en...
  • Page 109: Safety Data Sheet - Ig-01 (Argon)

    Safety Data Sheet - IG-01 (Argon) Oxeo PR LCP | 08-2022 | en...
  • Page 110 : IF INHALED: Remove to fresh air and keep at rest in a position comfortable for breathing. Get medical attention if breathing is affected. If breathing is difficult, supply oxygen. 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 111 : Stop leak if safe to do so. Methods for cleaning up : Exclude sources of ignition and ventilate the area. Ground equipment electrically. Use explosion-proof equipment. 6.4. Reference to other sections See Sections 8 and 13. 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 112 SECTION 9: Physical and chemical properties 9.1. Information on basic physical and chemical properties Physical state : Gas Color : Colourless Odor : Odorless Odor threshold : No data available : No data available 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 113 Carcinogenicity : Not classified Reproductive toxicity : Not classified STOT-single exposure : Not classified STOT-repeated exposure : Not classified Aspiration hazard : Not classified Viscosity, kinematic : No data available 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 114 Transportation of Dangerous Goods Not applicable Transport by sea (IMDG) Transport document description (IMDG) : UN 1006 ARGON, COMPRESSED, 2.2 UN-No. (IMDG) : 1006 Proper Shipping Name (IMDG) : ARGON, COMPRESSED 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 115 This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product. 05/17/2022 Argon IG-01 Oxeo PR LCP | 08-2022 | en...
  • Page 116 Safety Data Sheet - IG-01 (Argon) Oxeo PR LCP | 08-2022 | en...
  • Page 117: Safety Data Sheet - Ig-100 (Nitrogen)

    Safety Data Sheet - IG-100 (Nitrogen) Oxeo PR LCP | 08-2022 | en...
  • Page 118 : IF INHALED: Remove to fresh air and keep at rest in a position comfortable for breathing. Get medical attention if breathing is affected. If breathing is difficult, supply oxygen. 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 119 : Stop leak if safe to do so. Methods for cleaning up : Exclude sources of ignition and ventilate the area. Ground equipment electrically. Use explosion-proof equipment. 6.4. Reference to other sections See Sections 8 and 13. 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 120 SECTION 9: Physical and chemical properties 9.1. Information on basic physical and chemical properties Physical state : Gas Color : Colorless Odor : Odorless Odor threshold : No data available : No data available 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 121 Germ cell mutagenicity : Not classified Carcinogenicity : Not classified Reproductive toxicity : Not classified STOT-single exposure : Not classified STOT-repeated exposure : Not classified Aspiration hazard : Not classified 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 122 Transport document description (IMDG) : UN 1066 NITROGEN, COMPRESSED, 2.2 UN-No. (IMDG) : 1066 Proper Shipping Name (IMDG) : NITROGEN, COMPRESSED Class (IMDG) : 2 - Gases Limited quantities (IMDG) : 120 ml 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 123 This information is based on our current knowledge and is intended to describe the product for the purposes of health, safety and environmental requirements only. It should not therefore be construed as guaranteeing any specific property of the product. 05/17/2022 Nitrogen IG-100 Oxeo PR LCP | 08-2022 | en...
  • Page 124 Safety Data Sheet - IG-100 (Nitrogen) Oxeo PR LCP | 08-2022 | en...
  • Page 126 The Viking Corporation 210 N. Industrial Park Dr. Hastings, MI 49058 Phone: 269-945-9501 Fax: 269-818-1680 www.vikinggroupinc.com...