12 - FACTORY OPTIONS AND ACCESSORIES
■ Location
These roofcurb with integrated burner are designed to be
coupled with an 50FF/FC unit (roof-top installation). Make
sure they are not fi tted near areas where there is a risk of fi re
(fl ammable dust) or explosion, or in areas where aggressive
products are kept, e.g. trichloroethylene, perchloric acid, etc.
■ Delivery of the roofcurb with gas burner
Check the condition of the equipment upon delivery. Check
that the details on the label, the packing and the name plate
match the order. If equipment has been damaged, or there is
a shortfall in delivery, notify accordingly.
■ Burner identifi cation
The roofcurb with the burner includes a name plate featuring the
main gas characteristics as well as the roofcurb serial number.
GAS INFORMATION
COUNTRY
GAS
CATEGORY
PIN
Roofcurb with burner
CE certifi cate No.
Important: The serial number must be used in all
communication regarding the unit.
Transport and installation
Follow the recommendations given in section 7.4 which details
how to handle and fi t the adjustable roff curb, and how to fi t the
50FF/FC unit onto this roff curb.
Electrical connection of the burner
It is necessary to communicate the burner control with the electrical
cabinet of the 50FF/FC unit. The costumer must connect the cables
coming from the burner to the connection box "BOX8-QUE" that
is located inside of the 50FF/FC unit. This box is accessed via the
same panel that the supply fans.
Initial location of the cables for connection:
50FF/FC
unit
2
BOX8
1
QUE
Connection to be made by the customer:
50FF/FC
unit
2
BOX8
1
QUE
Note: see the wiring diagram included with the unit for a more
detailed information about the wiring.
CONSUMPT.
m3/h
PRESSURE
mbar
TYPE
WO
Burner
Roofcurb
model
serial No.
Roofcurb
with burner
W48-QUE
2
Burner
W49-QUE
1
control
Roofcurb
with burner
W48-QUE
2
Burner
W49-QUE
1
control
The following image shows the location of the connection box
"BOX8-QUE".
BOX8-QUE
Connection of the outlet probe
The connection of the outlet temperature probes must be
performed on-site. This probe is supplied inside the electrical
cabinet of the 50FF/FC unit.
Make the electrical connection of the probe (S3)
to the connection box "BOX8-QUE" that is located
inside of the 50FF/FC unit, using 2 x 1mm
cable.
Note: this cable is not supplied with the probe.
Please refer to the wiring diagram and the
"50FC" electronic control brochure, included
with the unit.
For the electrical connections, remove the top cover of the sensor.
Remove the cover by rotating it anticlockwise.
■ In order to guarantee the correct measurement of the outlet air
temperature this probe will be positioned at 1.5 metres as a
minimum from the outlet mouth at the bottom of the duct and
as near to the middle as possible inside this duct. The probe is
connected to the air duct using the special fastening bracket.
- Fasten the bracket to the air duct;
- Insert the rod on the bracket to the required depth;
- Tighten the screw on the bracket to fasten.
Clamp for attaching to the duct
Rotate to close
Detail of clamp dimensions (mm)
Rotate to open
42
DPDT011000
section
2
40
GND
BOX8-QUE
Screw to fix the probe
position (PT3.5x12)
3 x M3x10 self-tapping male
No. 3 holes Ø 2.75
120°
120°
Ø 17
61
43,3
=
=
S3
46
B3
57