Vaillant aroTHERM plus VWL 105/6 A 230V S2 Operating Instructions Manual page 90

Hide thumbs Also See for aroTHERM plus VWL 105/6 A 230V S2:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

Technical data – Heating circuit
Heating water temperature, minimum/maximum
Basic length of the heating water pipe, max-
imum, between the outdoor unit and indoor
unit
Operating pressure, minimum
Operating pressure, maximum
Volume flow, minimum
Volume flow, maximum
Water volume, in the outdoor unit
Water volume, in the heating circuit, minimum,
thawing mode, activated/deactivated back-up
heater
Remaining feed pressure, hydraulic
Technical data – Refrigerant circuit
Refrigerant, type
Refrigerant, fill quantity
Refrigerant, Global Warming Potential (GWP)
Refrigerant, CO
equivalent
2
Permissible operating pressure, maximum
Compressor, type
Compressor, oil type
Compressor, control
Technical data – Power, heating mode
Heating output, A2/W35
Coefficient of performance, COP, EN 14511,
A2/W35
Power consumption, effective, A2/W35
Power consumption, A2/W35
Heat output, minimum/maximum, A7/W35
Heat output, nominal, A7/W35
Coefficient of performance, COP, EN 14511,
A7/W35
Power consumption, effective, A7/W35
Power consumption, A7/W35
Heating output, A7/W45
Coefficient of performance, COP, EN 14511,
A7/W45
Power consumption, effective, A7/W45
Power consumption, A7/W45
Heating output, A7/W55
Coefficient of performance, COP, EN 14511,
A7/W55
Power consumption, effective, A7/W55
90
VWL 105/6 A
VWL 105/6 A S2
230V S2
20 ... 75 ℃
20 ... 75 ℃
20 m
20 m
0.05 MPa
0.05 MPa
(0.50 bar)
(0.50 bar)
0.30 MPa
0.30 MPa
(3.00 bar)
(3.00 bar)
995 l/h
995 l/h
2,065 l/h
2,065 l/h
2.5 l
2.5 l
45 l / 150 l
45 l / 150 l
55.0 kPa
55.0 kPa
(550.0 mbar)
(550.0 mbar)
VWL 105/6 A
VWL 105/6 A S2
230V S2
R290
R290
1.30 kg
1.30 kg
3
0.0039 t
0.0039 t
3.15 MPa
3.15 MPa
(31.50 bar)
(31.50 bar)
Scroll compressor
Scroll compressor
Specific
Specific
polyalkylene glycol
polyalkylene glycol
(PAG)
(PAG)
Electronic
Electronic
VWL 105/6 A
VWL 105/6 A S2
230V S2
5.80 kW
5.80 kW
4.60
4.60
1.26 kW
1.26 kW
6.20 A
2.80 A
5.40 ... 12.50 kW
5.40 ... 12.50 kW
8.10 kW
8.10 kW
5.30
5.30
1.53 kW
1.53 kW
7.40 A
3.00 A
8.10 kW
8.10 kW
4.10
4.10
1.98 kW
1.98 kW
9.40 A
3.60 A
9.10 kW
9.10 kW
3.10
3.10
2.94 kW
2.94 kW
Installation and maintenance instructions 0020326637_00
VWL 125/6 A
230V S2
20 ... 75 ℃
20 m
0.05 MPa
(0.50 bar)
0.30 MPa
(3.00 bar)
995 l/h
2,065 l/h
2.5 l
45 l / 150 l
55.0 kPa
(550.0 mbar)
VWL 125/6 A
230V S2
R290
1.30 kg
3
3
0.0039 t
3.15 MPa
(31.50 bar)
Scroll compressor
Specific
polyalkylene glycol
(PAG)
Electronic
VWL 125/6 A
230V S2
5.90 kW
4.60
1.28 kW
6.20 A
5.40 ... 14.00 kW
8.50 kW
5.40
1.57 kW
7.60 A
8.10 kW
4.10
1.98 kW
9.40 A
9.10 kW
3.10
2.94 kW
VWL 125/6 A S2
20 ... 75 ℃
20 m
0.05 MPa
(0.50 bar)
0.30 MPa
(3.00 bar)
995 l/h
2,065 l/h
2.5 l
45 l / 150 l
55.0 kPa
(550.0 mbar)
VWL 125/6 A S2
R290
1.30 kg
3
0.0039 t
3.15 MPa
(31.50 bar)
Scroll compressor
Specific
polyalkylene glycol
(PAG)
Electronic
VWL 125/6 A S2
5.90 kW
4.60
1.28 kW
2.90 A
5.40 ... 14.00 kW
8.50 kW
5.40
1.57 kW
3.10 A
8.10 kW
4.10
1.98 kW
3.60 A
9.10 kW
3.10
2.94 kW