Rpa Parallel System Connection; Power Wiring Of Parallel Units - GE SG 750 UL S2 Series Installation Manual

Table of Contents

Advertisement

3.10

RPA PARALLEL SYSTEM CONNECTION

WARNING !
This operation must be performed by QUALIFIED SERVICE PERSONNEL ONLY before
the initial start-up.
ENSURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.

3.10.1 Power wiring of parallel units

To guarantee good Load sharing between the units of a Parallel System, we recommend that the cable
length from the input distribution board (5) to the output distribution board (9) is equal for each unit (a+b
= c+d = e+f = g+h = i+l = m+n). Tolerance: +/- 10%.
The RPA Cable Saver option introduces a bypass inductor in every UPS module, minimizing the influence
of external conductor length on bypass current sharing.
The RPA Cable Saver option extends the cable length tolerance to +/-50% for runs not exceeding 160
feet (49m).
The AC input power of the Bypass must be the same for all units of the parallel system - no phase shift
allowed between units.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or
fuses be inserted between the unit's output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch be installed in
order to totally isolate a unit if needed.
Verify that power wiring and control wiring are run in separate conduits or cable trays.
UPS input cables must be run in separate conduits from the output cables.
Fig. 3.10.1-1 Power wiring of RPA Parallel System
Modifications reserved
OPM_SGS_ISG_M75_M75_2US_V010.doc
1
= Rectifier
2
= Inverter
3
= Automatic Bypass
4
= Q1 Output UPS switch
5
= Input Utility Distribution
6
= Unit Output Load
7
= External Battery fuse or MCB
8
= External Battery
Common bus bar and Output
9
=
Load Distribution
= UPS Number 1
2
= UPS Number 2
3
= UPS Number 3
4
= UPS Number 4
5
= UPS Number 5
6
= UPS Number 6
Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2