Panasonic CS-Z25YKEA Service Manual page 104

Hide thumbs Also See for CS-Z25YKEA:
Table of Contents

Advertisement

D) During Duty Rota on = ON, CN-CNT B is malfun oned
Main unit (A)
No wifi se ng
CN-CNT
change signal
CN-RMT A
WRC A
E) During Duty Rota on = ON, both CN-CNT A and B are malfun oned
Main unit (A)
Wifi
se ng
CN-CNT A
change signal
CN-RMT A
WRC A
Note:
1) WRC = Wired Remote Control
2) The above cases assume that users do not change Duty Rota on se ng at any me.
3) A er both CN-CNTs are recovered from Case C, D, E, return to Case B.
4) If only CN-CNT A or CN-CNT B is recovered from Case E, return to Case D or Case C respec vely.
5) For running unit B in Case C and unit A in Case D, running opera on will follow se ng set when duty
rota on is started. To change se ng through WRC (CN-RMT signal) or Wi-Fi, users need to turn off Duty
rota on mode first in WRC. A er turned off, Duty rota on mode cannot be turned on again if the
malfunc oned CN-CNT is not repaired.
6) If WRC B is not connected to Sub unit (B), se ng change through WRC (CN-RMT signal) is not possible for
unit B.
Sub unit (B)
CN-RMT B
CN-CNT B
WRC B
Sub unit (B)
CN-RMT B
CN-CNT B
WRC B
Wifi
se ng
change signal
1.
CN-CNT Signal to A: ON, B: OFF (Malfunc oned)
2.
Se ng change through WRC (CN-RMT signal) Flag for
A: Disabled, B: Enabled a er 3min no CN-CNT B signal
3.
Se ng change through WLAN Flag for
A: Disabled, B: Enabled a er 3min no CN-CNT B signal
4.
Indoor opera on for
A: ON, B: OFF a er 3min no CN-CNT B signal un l recovery
5.
Rota on interval: A er 1min no CN-CNT A signal, set to
zero un l recovery
6.
Duty rota on flag for
A: ON, B: OFF a er 3min no CN-CNT B signal un l recovery
Wifi
se ng
change signal
1.
CN-CNT Signal to A and B: OFF (Malfunc oned)
2.
Se ng change through WRC (CN-RMT signal) Flag for
A and B: Enabled a er 3min no CN-CNT A&B signal
3.
Se ng change through WLAN Flag for
A and B: Enabled a er 3min no CN-CNT A&B signal
4.
Indoor opera on for
A and B: OFF a er 3min no CN-CNT A&B signal
5.
Rota on interval: A er 1min no CN-CNT A/B signal, set to
zero un l CN-CNT A/B recovers
6.
Duty rota on flag for
A: OFF a er 3mins no CN-CNT A signal un l recovery
B: OFF a er 3mins no CN-CNT B signal un l recovery