Siemens DMS8000 MP4.81 Operation Manual page 34

Hide thumbs Also See for DMS8000 MP4.81:
Table of Contents

Advertisement

2
Configuring intrusion control units
Configuring a CS4
34
Building Technologies
CPS Fire Safety
a In a few moments, the CS4 structure is imported, and the node is represented
in the Composer tree.
Note: The node is renamed to match the metafile name. To customise the name,
click the node text, type in a new name, and press ENTER.
Note: After the import procedure, by selecting the Import tab, a report page
displays. It contains the detailed logs of the latest import procedure, including any
added or removed objects.
Linking the CS4 to the Communication network
Link the CS4 node to the Cerloop, CDI-Net, or NK8000 network.
1. Expand the network folders until you reach the node that represents the
network that is physically connected to the CS4.
2. Select the CS4 node.
3. Drag and drop the CS4 node to the network node.
a When the link is established, a new node appears on the structure tree, and its
properties can be seen on the Node tab.
Note: The valid link position for Cerloop is always the same main node,
representing the entire loop. The valid link positions on CDI-Net/NK8000 units are
distributed along the subsystem lines.
Note: Composer helps you in recognising a valid link by showing a shortcut Link
icon
instead of the circle No-link icon
Linking CS4 to a Cerloop network
.
A6V10359489_a_en
30.09.2016