Fujitsu ETERNUS AX Series Manual page 12

Hide thumbs Also See for ETERNUS AX Series:
Table of Contents

Advertisement

1.
ETERNUS AX/HX Installation
Installation Specifications
Maximum power
consumption (*2)
Maximum heat
generation (*2)
Maximum amount of
exhaust air
Environmental
conditions
Noise emission (*6)
*1:
A 2U power distribution unit is composed of two 1U power distribution units.
*2:
These values are for each shelf when 24 drives are installed.
*3:
The value in the parentheses for the controller shelf and drive shelves includes the mass of the rack rail kit.
*4:
These values are for the maximum load when all the available options are installed in an ETERNUS AX/HX.
*5:
The operating test was performed in environments compatible with the Operating Condition Class A2 of the EU eco-
design directive (ErP Directive 2009/125/EC).
Item
Controller
2.5" type
AC100 – 120V
shelf
AC200 – 240V
Drive
DS224C
AC100 – 120V
shelf
2.5" type
AC200 – 240V
NS224
AC100 – 120V
AC200 – 240V
Maximum configuration
AC100 – 120V
(*4)
AC200 – 240V
Controller
2.5" type
AC100 – 120V
shelf
AC200 – 240V
Drive
DS224C
AC100 – 120V
shelf
2.5" type
AC200 – 240V
NS224
AC100 – 120V
AC200 – 240V
Maximum configuration
AC100 – 120V
(*4)
AC200 – 240V
Controller shelf
Drive
2.5" type / 3.5" type
shelf
60-drive type
Tempera-
Operating (*5)
ture
Not operating
During shipment
Temperature gradient
Humidity
Operating (*5)
Not operating
During shipment
Humidity gradient
Maximum wet bulb temperature
Altitude above sea level
Airborne dust
Gas concentration tolerance level
Oil vapor
Seawater (salt corrosion)
Sound pressure level
Sound power level
12
ETERNUS AX4100
1,580 W (1,630 VA)
1,528 W (1,560 VA)
390 W (398 VA)
383 W (392 VA)
848 W (848 VA)
810 W (810 VA)
9,380 W (9,590 VA)
9,188 W (9,400 VA)
5,688 kJ/h
5,501 kJ/h
1,404 kJ/h
1,379 kJ/h
3,053 kJ/h
2,916 kJ/h
33,768 kJ/h
33,077 kJ/h
-
-
-
10 – 35 °C
-40 – 70 °C
-40 – 70 °C
15 °C/Hr or less
8 – 80 %RH
10 – 95 %RH
10 – 95 %RH
30 %/day or less
29 °C
0 – 3,048 m
3
0.15 mg/m
or less
Cl
: 6.8 ppb or less, H
S: 7.1 ppb or less,
2
2
SO
: 37 ppb or less, NH
: 423.5 ppb or less,
2
3
NO
: 52.3 ppb or less, O
: 5 ppb or less,
2
3
HCl: 6.6 ppb or less, HF: 3.6 ppb or less
3
0.2 mg/m
or less
If the ETERNUS AX/HX is installed on the ocean or
premises within 0.5 km from the coast, necessary
measures must be taken to prevent salt corrosion.
67.2 dBA
8.5 B
Site Planning Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eternus hx series