HOR. SIDEWALL & RECESSED HOR. SIDEWALL SPRINKLERS
UNIVERSAL MODEL A/Q-71
QUICK RESPONSE, 3 mm BULB TYPE, 5.6 K-FACTOR, 1/2" NPT**
GENERAL DESCRIPTION
The 5.6 K-Factor Quick Response Uni-
versal Model A/Q-71 Horizontal Side-
wall and Recessed Horizontal Side-
wall Sprinklers (Ref. Figure A) are
automatic sprinklers of the "quick re-
sponse" frangible bulb type. They are
"standard spray sprinklers" intended
for use in fire sprinkler systems de-
signed in accordance with the stand-
ard installation rules recognized by the
applicable Listing or Approval agency
(e.g., UL Listing is based on NFPA 13
requirements).
Horizontal sidewall sprinklers are gen-
erally used in lieu of pendent and up-
right sprinklers because of building
construction or installation economy
considerations. They are designed for
installation along a wall or side of a
beam and just beneath a smooth ceil-
ing. Installed with their centerline of
waterway horizontal, these sprinklers
produce a quarter-spherical water dis-
charge pattern that is predominately
directed downward and outward from
the deflector; however, a portion of the
spray is also directed towards the back
wall.
The Model A/Q-71 Sprinklers feature a
unique "Deflector Hat" which provides
a low profile for improved aesthetics.
The recessed versions of the Model
A/Q-71 Sprinkler are obtained by util-
izing the Model A/Q-71 Sprinkler in
combination with either the Model
F700 or F705 Recessed Escutcheon
(Ref. Figures A and B). The F700 and
F705 Recessed Escutcheons have a
separable two-piece design which al-
lows installation of the sprinklers and
pressure testing of the fire protection
system, prior to wall construction
and/or application of a finish coat to
the wall. They also permit refinishing
of a wall surface without having to first
shut down the fire protection system
and remove the sprinklers.
The vertical adjustment provided by
the F700 or F705 substantially re-
duces the accuracy to which the length
of fixed pipe nipples to the sprinklers
must be cut. Also, the Closure has a
1/2 inch (12,7 mm) wide flange which
provides ample clearance for covering
the mounting hole.
Printed in U.S.A. 3-01
Customer Service/Sales: Tel: (877) 436-8926 / Fax: (877) 866-9250
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
1-13/16"
(46,0 mm)
OF SPRINKLER
1 - Frame
2 - Button
3 - Gasketed
Spring
Plate
4 - Bulb
5 - Compression
Screw
6 - Deflector
*
Temperature rating is indicated on deflector or adjacent to orifice seat on frame.
**
Pipe thread connections per ISO 7/1 can be provided on special request.
5.6 K-FACTOR QUICK RESPONSE
MODEL A/Q-71 HORIZONTAL SIDEWALL (SIN G7378) SPRINKLERS
Lead coatings are utilized to extend
the life of copper alloy sprinklers be-
yond that which would otherwise be
obtained when exposed to corrosive
atmospheres. Although lead coated
sprinklers have passed the standard
DEFLECTOR
5
HAT
6
4
*
WRENCH
9/16"
FLATS
(14,3 mm)
7/16"
(11,1 mm)
NOMINAL
CENTERLINE
MAKE-IN
WATERWAY
1-1/2"
(38,1 mm)
2-3/16"
(55,6 mm)
MODEL
F700 or F705
RECESSED
ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FIGURE A
corrosion tests of the applicable ap-
proval agencies, the testing is not rep-
resentative of all possible corrosive at-
mospheres.
recommended that the end user be
consulted with respect to the suitability
2
3
1
1/2"
**
NPT
ESCUTCHEON
PLATE SEATING
SURFACE
Consequently,
it
is
TD534

Advertisement

loading

Summary of Contents for GEM A/Q-71

  • Page 1 FIGURE A shut down the fire protection system 5.6 K-FACTOR QUICK RESPONSE and remove the sprinklers. MODEL A/Q-71 HORIZONTAL SIDEWALL (SIN G7378) SPRINKLERS The vertical adjustment provided by the F700 or F705 substantially re- duces the accuracy to which the length...
  • Page 2: Approvals And Standards

    Laboratory listings and approvals for F700 or F705 will void all sprinkler psi (bar). the 5.6 K-Factor Model A/Q-71 Hori- warranties, as well as possibly void The Frame of the Model A Sprinkler zontal Sidewall Sprinklers and Re- the sprinkler’s Approvals and/or...
  • Page 3: Installation

    FIGURE B ble should be present. The diameter of MODEL A/Q-71 RECESSED HORIZONTAL SIDEWALL SPRINKLER the air bubble is approximately 1/16 WITH TWO-PIECE MODEL F700 AND F705 RECESSED ESCUTCHEON inch (1,6 mm) for the 135°F/57°C to...
  • Page 4: Care And Maintenance

    F700 or4 F705 Clo- tion Association (e.g., NFPA 25), in wall Sprinklers must be installed in sure over the Model A/Q-71 Sprinkler addition to the standards of any other accordance with the following instruc- and push the Closure over the Mount- authorities having jurisdiction.
  • Page 5 National Fire Protection Associa- PRODUCT SYMBOL NUMBER SELECTION tion, and/or the standards of any other 5.6 K-FACTOR MODEL A/Q-71 HORIZONTAL SIDEWALL SPRINKLERS Authorities Having Jurisdiction. Mate- WITH 1/2 INCH NPT CONNECTIONS rials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products’...