Table of Contents

Advertisement

®
P
URE
Gas
Boilers
PF-50 PF-80 PF-110 PF-140 PF-200 PF-210 PF-300 PF-399
As an ENERGY STAR
®
Partner, PB Heat, LLC has determined that
this product meets the ENERGY STAR guidelines for energy efficiency.
I n s t a l l a t i o n ,
O p e r a t i o n &
M a i n t e n a n c e
M a n u a l
®
F
IRE
REV 2

Advertisement

Table of Contents
loading

Summary of Contents for PEERLESS PureFire PF-80

  • Page 1 ® ® REV 2 Boilers PF-50 PF-80 PF-110 PF-140 PF-200 PF-210 PF-300 PF-399 As an ENERGY STAR ® Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency. I n s t a l l a t i o n , O p e r a t i o n &...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS TABLE OF CONTENTS C. ZONE CIRCULATOR WIRING ... . .34 USING THIS MANUAL D. INTERNAL WIRING ....34 A.
  • Page 3: Using This Manual

    USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE DANGER Follow the installation instructions provided in this manual Indicates a condition or hazard which will cause in the order shown. The order of these instructions has severe personal injury, death or major property been set in order to provide the installer with a logical damage.
  • Page 4: Preinstallation

    PREINSTALLATION 1. PREINSTALLATION **Please read if installing in Massachusetts** A. GENERAL Massachusetts requires manufacturers of Side Wall Vented boilers to provide the following information 1. P ® boilers are supplied completely assembled from the Massachusetts code: as packaged boilers. The package should be inspected ·...
  • Page 5: Accessibility Clearances

    PREINSTALLATION 2. Figure 1.1 shows the minimum recommended C. ACCESSIBILITY CLEARANCES clearances to allow reasonable access to the boiler for Models PF-50, PF-80, PF-110 and PF-140. 1. The P ® boiler is certified for closet installations For Models PF-200, PF-210, PF-300 and PF-399, with zero clearance to combustible construction.
  • Page 6: Combustion & Ventilation Air

    PREINSTALLATION a. Combining Spaces on the Same Floor: Provide two D. COMBUSTION AND VENTILATION AIR permanent openings communicating with additional spaces that have a minimum free area of 1 in 1. The P ® boiler is designed for operation with 1000 Btu/hr (22 cm per 1000 W) of the total input combustion air piped directly to the boiler from...
  • Page 7 PREINSTALLATION 5. Outdoor Combustion Air: Outdoor combustion air is ii. Where communicating with the outdoors through to be provided through one or two permanent horizontal ducts, each opening shall have a openings. The minimum dimension of these air minimum free area of 1 in per 2000 Btu/hr (22 openings is 3 inches (76 mm).
  • Page 8: Planning The Layout

    PREINSTALLATION 6. Combination Indoor and Outdoor Combustion Air: If b. Motorized dampers shall be interlocked with the the required volume of indoor air exceeds the equipment so that they are proven in the full open available indoor air volume, outdoor air openings or position prior to ignition and during operation of ducts may be used to supplement the available indoor the main burner.
  • Page 9 PREINSTALLATION WARNING This boiler is certified as an indoor appliance. Do not install this boiler outdoors or locate where it will be exposed to freezing temperatures. WARNING Do not install this boiler where gasoline or other flammable liquids or vapors are stored or are in use. WARNING Do not install this boiler in the attic.
  • Page 10: Boiler Set-Up

    BOILER SET-UP 2. BOILER SET-UP d. Install the two additional lag bolts supplied with A. GENERAL the boiler into the wall structure approximately 23” below those used to attach the wall mounting 1. P ® boilers are intended for installation in an bracket to the wall as shown in Figure 2.1.
  • Page 11: Venting & Air Inlet Piping

    3. Cellular core piping is approved for inlet air piping only. 4. The Peerless ® ® boiler, like all high efficiency, gas-fired appliances, is likely to produce a vapor WARNING plume due to condensation.
  • Page 12 VENTING & AIR INLET PIPING 6. Air Intake Pipe Location – Sidewall Venting: 7. Sidewall Venting Configuration: a. Provide 1 foot (30 cm) clearance from the bottom a. See Figure 3.2 for an illustration of clearances for of the air intake pipe to the level of maximum location of exit terminals of direct-vent venting snow accumulation.
  • Page 13 VENTING & AIR INLET PIPING b. Figures 3.3 through 3.6 show approved sidewall venting configurations using the standard fittings supplied. c. Figure 3.4 is only approved for locations in which the outdoor temperature is above -5°F (-21°C) in accordance with ASHRAE 90A-1980 recommendations.
  • Page 14 VENTING & AIR INLET PIPING 8. Vertical Venting Configuration: a. Figure 3.8 shows the approved venting configuration for vertical venting using the standard fittings supplied. Figure 3.6: Sidewall Exhaust with Indoor Air Figure 3.8: Standard Vertical Vent Installation b. Locate the air intake pipe inlet 12" above the expected snow accumulation on the roof surface or 24"...
  • Page 15 VENTING & AIR INLET PIPING Figure 3.9: Concentric Vertical Vent Installation Figure 3.11: Venting Through a Chimney Using Sidewall Outside Air Figure 3.10: Venting Through a Chimney Using Figure 3.12: Venting with a Chimney Using Inside Air Outside Air...
  • Page 16: Exhaust Vent/Air Intake Pipe Sizing

    VENTING & AIR INLET PIPING This is well below the 200 feet maximum D. EXHAUST VENT/AIR INTAKE PIPE SIZING equivalent length. If the total is above 200 equivalent feet, alternate boiler locations or 1. Table 3.2 shows Exhaust Vent/Air Intake Sizes for exhaust penetration location should be considered.
  • Page 17: Exhaust Tapping For Vent Sample

    VENTING & AIR INLET PIPING c. A straight coupling is provided with the boiler to Retrait de la chaudière d’un système d’évacuation be used as an outside vent termination. One of commun. Au moment de retirer une chaudière existante, the two screens is to be installed to prevent birds il est important de suivre les étapes suivantes pour chaque or rodents from entering.
  • Page 18 VENTING & AIR INLET PIPING 8. After it has been determined that each appliance 10. When resizing any portion of the common venting remaining connected to the common venting system system, the common venting system should be resized properly vents when tested as outlined above, return to approach minimum size as determined using the doors, windows, exhaust fans, fireplace dampers and appropriate tables located in the chapter “Sizing of...
  • Page 19: Water Piping And Controls

    WATER PIPING AND CONTROLS 4. WATER PIPING & CONTROLS Table 4.2 provides the water volume of the heat A. GENERAL exchanger including the supply and return pipes that 1. Size water supply and return piping in accordance are attached at the factory. with system requirements rather than the boiler Table 4.2: Heat Exchanger Water Capacity connections.
  • Page 20 WATER PIPING AND CONTROLS Figure 4.1: Piping Symbol Key 4. Y-Type Strainer or Filter Ball ® Valve: PB Heat 8. Pressure Relief Valve: The boiler pressure relief valve recommends the use of a strainer device in the system to is shipped separately for field installation. prevent dirt or sediment from clogging the heat The valve is to be installed as shown in Figures 4.2 or exchanger.
  • Page 21 WATER PIPING AND CONTROLS Table 4.3: Boiler Inputs and Outputs ® Boiler Input Gross Output Model Btu/hr (kW) Btu/hr (kW) PF-50 50,000 (14.7) 46,000 (13.5) PF-80 80,000 (23.4) 74,000 (21.7) PF-110 110,000 (34.2) 102,000 (29.9) PF-140 140,000 (41.0) 131,000 (38.4) PF-200 199,000 (58.3) 183,000 (53.6)
  • Page 22 WATER PIPING AND CONTROLS d. The boiler pressure drop for various flow rates can e. Table 4.4 provides the flow rate and pressure drop be determined using Figure 4.4, the P ® information that corresponds to various system Boiler Circulator Sizing Graph. temperature rise values (ΔT).
  • Page 23: System Piping

    2. For a single boiler with one heating zone and one make-up water will dilute the system and reduce the DHW zone which utilizes an indirect water heater like ability of the solution to protect from freezing. the Peerless ® Partner ®...
  • Page 24 WATER PIPING AND CONTROLS...
  • Page 25 WATER PIPING AND CONTROLS...
  • Page 26 WATER PIPING AND CONTROLS...
  • Page 27 WATER PIPING AND CONTROLS...
  • Page 28 WATER PIPING AND CONTROLS...
  • Page 29: Special Applications

    WATER PIPING AND CONTROLS c. See Figure 4.10 for recommended system piping SPECIAL APPLICATIONS for chiller operation. 1. If the P ® boiler is used in conjunction with a 2. For boilers connected to heating coils in a forced air chilled medium system, pipe the chiller in a separate system where they may be exposed to chilled air secondary loop.
  • Page 30: Fuel Piping

    FUEL PIPING 5. FUEL PIPING Table 5.1: Required Fuel Input A. GENERAL Required Input Rate* Natural Gas ft LP Gas ft ® 1. All fuel piping to the P ® boiler is to be in /hr) /hr) Model accordance with local codes. In the absence of local PF-50 50 (1.4) 20 (0.6)
  • Page 31: Gas Supply Piping - Operation

    FUEL PIPING 3. Install a ground joint union between the sediment trap 3. To check the gas supply pressure to the gas valve: and the boiler to allow service to the appliance. a. Turn off the power at the service switch. 4.
  • Page 32: Main Gas Valve - Operation

    FUEL PIPING 2. Refer to Section 3, Venting and Air Intake for E. MAIN GAS VALVE - OPERATION information on obtaining vent samples from this boiler. 1. Figure 5.2 is an illustration of the gas valve/venturi assembly for the P ®...
  • Page 33: Condensate Drain Piping

    CONDENSATE DRAIN PIPING 6. CONDENSATE DRAIN PIPING 1. Condensate Drain Hoses: The PF-50, PF-80, PF-110, A. GENERAL and PF-140 boilers have two drain hoses attached to the heat exchanger. The first hose drains condensate 1. The disposal of all condensate into public sewage from the combustion chamber of the boiler.
  • Page 34: Condensate Drain Pipe Material

    CONDENSATE DRAIN PIPING 4. Condensate Neutralizer Container: The condensate E. CONDENSATE DRAIN PIPE INSTALLATION neutralizer container is an additional transparent container near the front of the boiler. Fill this 1. Connect a 3/4" schedule 40 PVC Tee to the outlet of container with the condensate neutralizer provided.
  • Page 35: Electrical Connections

    ELECTRICAL CONNECTIONS 7. ELECTRICAL CONNECTIONS 3. Figure 7.2 shows customer connections for the PF-50, A. GENERAL PF-80, PF-110 and PF-140 boilers. This appliance is to be wired in accordance with local a. Terminals 1-10 on the left side are for low voltage codes and regulations as defined by the Authority having customer connections to the CH thermostat, jurisdiction.
  • Page 36: Zone Circulator Wiring

    ELECTRICAL CONNECTIONS Figure 7.3: Customer Connections – PF-200, PF-210, PF-300 and PF-399 5. Note that the service switch does not disconnect D. INTERNAL WIRING power to the convenience outlet. Figure 7.5 shows the complete boiler wiring schematic for PF-50, PF-80, PF-110 and PF-140 boilers. Figure 7.6 C.
  • Page 37 ELECTRICAL CONNECTIONS...
  • Page 38 ELECTRICAL CONNECTIONS Figure 7.6: Internal Wiring Schematic for PF-200, PF-210, PF-300 & PF-399 boilers.
  • Page 39 FOR BLOWN FUSE BEFORE REPLACING. Additional 12. Blocked Vent Switch: This switch is only needed and fuses can be ordered as need from your Peerless used on PF-200/210/300/399 to detect a blockage on Boiler Distributor (Part #5650). See Figure 10.1 for the exhaust vent.
  • Page 40: Boiler Control: Internal Wiring & Operation

    BOILER CONTROL: INTERNAL WIRING & OPERATION 8. BOILER CONTROL: INTERNAL WIRING & OPERATION 1. Central Heating (CH) Modes: A. CONTROL OVERVIEW The P ® boiler control allows the installer to choose from several different central heating modes. The P ® boiler control is one of the primary safety The following table shows the central heating modes.
  • Page 41 BOILER CONTROL: INTERNAL WIRING & OPERATION 3. Special Features: The P ® control offers several special features to give the installer options in setting up the boiler. These options are shown in the following table and described in detail later in this section. Table 8.4: Control Features Feature Description...
  • Page 42: Ignition Sequence

    BOILER CONTROL: INTERNAL WIRING & OPERATION B. IGNITION SEQUENCE Figure 8.1 shows the ignition sequence for the P ® boiler control. Table 8.5 describes each step in the sequence in detail. The P ® boiler control provides dual sensing of the flame to maximize the reliability. The control senses the burner flame with both the flame sensor and the ignition electrode.
  • Page 43 BOILER CONTROL: INTERNAL WIRING & OPERATION Period Demand Status User Interface Display A heat demand has no influence in the Safety On/Off period. The Safety On/Off step will continue even if the demand Safety has ended. On/Off This step very quickly opens and closes the gas valve relays and determines if the control is operating correctly. The CH pump is turned off during this test.
  • Page 44: Boiler Control

    BOILER CONTROL: INTERNAL WIRING & OPERATION Low Water Cutoff: Connect the power supply wires C. BOILER CONTROL for a probe type low water cutoff to the 120 vac LWCO terminals (#19 & #20 for PF-50/80/110/140); #25 & 1. Installation Location & Vent Material: #26 for PF-200/210/300/399)in the main terminal The P ®...
  • Page 45 BOILER CONTROL: INTERNAL WIRING & OPERATION Mode 2 – Permanent Demand and Outdoor Reset: Mode 6 – Hydro-Air Units: This mode is specifically Mode 2 operates much like Mode 1 except that no designed for boiler supplying hot water to a hot water thermostat contact closure is required between coil in a forced air heating system using fixed supply terminals #1 &...
  • Page 46 BOILER CONTROL: INTERNAL WIRING & OPERATION 2. Setpoint operation: Note that, depending on the type of heat distribution When operating in CH mode 0, 3 or 6 the user can used, this value should be set higher. For example, if select a target temperature for the boiler supply.
  • Page 47 BOILER CONTROL: INTERNAL WIRING & OPERATION The default for these values are as follows: 4. Other Features: Temp = 18°F and Time = 20 minutes. Pump Post Purge: The P ® control allows the installer to set post purge times for the CH and/or This function is designed to help the boiler recover General Pumps.
  • Page 48: Domestic Hot Water (Dhw)

    BOILER CONTROL: INTERNAL WIRING & OPERATION Table 8.9: Outdoor Design Temperature (ODT) – U.S. Cities City State City State City State Mobile 29°F -2°C Springfield 2°F -17°C Albuquerque 16°F -9°C Anchorage -18°F -28°C Indianapolis 2°F -17°C New York City 15°F -9°C Juneau 1°F...
  • Page 49: Service Notification

    BOILER CONTROL: INTERNAL WIRING & OPERATION 2. DHW Priority: • Pump Mode 2 – DHW Mode 1 & 2: The General The P ® boiler control provides limited pump will operate with the DHW pump to direct domestic hot water priority with an installer selectable excess boiler heat to the DHW Tank.
  • Page 50: System Test

    BOILER CONTROL: INTERNAL WIRING & OPERATION Flame Signal/Failures: Pressing the “ ” key again will G. SYSTEM TEST display the Flame Signal/Failures Screen. The flame signal is an indication of combustion stability of the The System Test feature allows the installer or service burner.
  • Page 51: Sensor Resistance

    BOILER CONTROL: INTERNAL WIRING & OPERATION b. Dependent Boilers: The “dependent” boilers SENSOR RESISTANCE operate at the setpoint temperature that the See Figure 8.4 for typical resistance of the boiler sensors. Master boiler specifies. • Maintain all of their own safety parameters such as safety limit, vent temperature limit, and freeze protection.
  • Page 52 BOILER CONTROL: INTERNAL WIRING & OPERATION...
  • Page 53 BOILER CONTROL: INTERNAL WIRING & OPERATION...
  • Page 54 BOILER CONTROL: INTERNAL WIRING & OPERATION 4. Setting up Multiple Boiler Operation: To cascade PF-50 and PF-80 a. Setting the Boiler Address: models, display must include On/Off switch and sub-base must • Press the “Menu” and “Select” keys include dual terminal blocks. simultaneously for 5 seconds to enter the Installer Menu.
  • Page 55 BOILER CONTROL: INTERNAL WIRING & OPERATION To cascade PF-50 and PF-80 models, check that the display sub-base has the cascade link as illustrated in Figure 8.6. Figure 8.7: Interconnection of Cascade Link Wires f. After operation of the second boiler is initiated, •...
  • Page 56 BOILER CONTROL: INTERNAL WIRING & OPERATION b. Similarly, the WWSD Temperature set on the 9. Multiple Boilers – DHW Operation: master boiler will prevent any boilers from a. Since the DHW tank sensor or thermostat is operating for a CH demand when the outdoor connected only to the Master boiler, this is the temperature is above this value.
  • Page 57: Start-Up Procedure

    START-UP PROCEDURE 9. START-UP PROCEDURE 3. Refer to Section 8, Boiler Control, to set up the A. GENERAL control for the desired operation. 1. Confirm that all water, gas and electricity are turned off. 4. Use the ignition sequence, Figure 8.1 to follow the light off and shutdown sequences and to assist in 2.
  • Page 58 START-UP PROCEDURE b. Polypropylene vent systems from Centrotherm or • Verify that the fan speed indicated is within Duravent should include a sample port fitting 100 rpm of the Low Power fan speed listed in connected to the exhaust outlet port of the boiler. Table 12.3.
  • Page 59: Lighting & Operating Procedures

    START-UP PROCEDURE E. LIGHTING & OPERATING PROCEDURES FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. If you cannot reach your gas supplier, A.
  • Page 60: Troubleshooting

    TROUBLESHOOTING 10. TROUBLESHOOTING A. HARDWARE ERROR- NO COMM MAIN WARNING BOARD Do not use this appliance if any part has been under If the display shows “NO COMM MAIN BOARD”, water. Improper or dangerous operation may result. Contact your PB Heat representative or PB Heat Contact a qualified service technician immediately to Technical Support.
  • Page 61 TROUBLESHOOTING Table 10.1: Control Board Blocking Error Codes (automatic reset): “E” Internal Error Display Error Description Corrective Action CODE SUPPLY SENSOR Supply sensor not connected. Check harness and sensor. NOT CONNECTED RETURN SENSOR Return sensor not connected. Check harness and sensor. NOT CONNECTED If DHW Mode is not intended to be set to Mode 1, DHW Store with Sensor, then change it to the...
  • Page 62 TROUBLESHOOTING Table 10.2: Control Board Locking Error Codes (manual reset): “A” Internal Error Display Error Description Corrective Action CODE 1. Watch the igniter through the observation window. 2. If no spark is present, check the spark electrode for the proper 3/16"...
  • Page 63 TROUBLESHOOTING Table 10.2 (cont’d): Control Board Locking Error Codes (manual reset): “A” Internal Error Display Error Description Corrective Action CODE INTERNAL ERROR GAS Gas Valve Relay See Note** VALVE RELAY Problems. INTERNAL ERROR Safety Relay Problems. See Note** SAFETY RELAY INTERNAL SOFTWARE Internal Software Error.
  • Page 64: Warning Errors

    TROUBLESHOOTING 3. Flue Sensor Error: E. WARNING ERRORS a. If the control senses that the flue temperature does The P ® boiler control will display a blinking screen not rise to above 50°F after ignition, and either the under several conditions. Several of these conditions provide supply water temperature rises above 120°F or the the error information directly on the screen.
  • Page 65 TROUBLESHOOTING Table 10.3: Control Board Warning Error Codes “W” Error Error Display Corrective Action CODE Description 1) Check to see if the Outdoor Sensor is connected. 2) Check wiring connectons to outdoor sensor. Outdoor Sensor 3) Remove wires from terminals #3 and #4 on #W00 Open the boiler and check the resistance between...
  • Page 66: Delayed Ignition (Hard Light-Off)

    TROUBLESHOOTING E. DELAYED IGNITION (HARD LIGHT-OFF) There are several factors that may cause a delayed ignition in the PureFire boiler due to a pressure pulse at light-off. Table 10.4: Hard Light-Off Conditions: Condition Description Corrective Action Condition If the gas inlet pressure at the inlet port on the gas valve is Be sure that the incoming gas pressure does not drop below 3.5"...
  • Page 67: Maintenance

    MAINTENANCE 11. MAINTENANCE WARNING Product Safety Information Refractory Ceramic Fiber Product This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF fibers, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F, they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans.
  • Page 68: General (With Boiler In Use)

    MAINTENANCE 3. Test low-water cut-off (if used) as described by the A. GENERAL (WITH BOILER IN USE) manufacturer. General boiler observation can be performed by the owner. If any potential problems are found, a qualified 4. Test limit as described in Section 9, Part D, installer or service technician/agency must be notified.
  • Page 69: Inspection And Cleaning Of Combustion Chamber Coils

    MAINTENANCE 2. Before re-starting the P ® boiler follow the 3. Use the nylon or brass brush (do not use steel) and steps below: scrub coils to remove any buildup, then vacuum the debris from the coils. a. Reconnect the thermostat wires. 4.
  • Page 70: Boiler Dimensions & Ratings

    BOILER DIMENSIONS & RATINGS 12. BOILER DIMENSIONS & RATINGS Figure 12.1: Dimensional Drawing – PF-50, PF-80, PF-110 & PF-140 Table 12.1: Boiler Dimensions ® PUREFIRE ® SERIES PEERLESS DIMENSIONS (INCHES) Boiler “A” “B” “C” “D” “E” “F” “G” “H” “J”...
  • Page 71 BOILER DIMENSIONS & RATINGS Figure 12.2: Dimensional Drawing – PF-200, PF-210, PF-300 & PF-399 Table 12.2: Boiler Ratings ® PUREFIRE ® SERIES PEERLESS BOILER RATINGS ® ® Series Peerless Input Heating Boiler Net Rating AFUE (MBH) Capacity Model (MBH) (MBH) Min.
  • Page 72 BOILER DIMENSIONS & RATINGS Table 12.4: P ® Main Control Specifications ® PUREFIRE ® SERIES PEERLESS MAIN CONTROL SPECIFICATIONS Power Supply 120 VAC Nominal (102-132 VAC); 60 Hertz (40-70 Hz) Phase Neutral Fuse (5650) 3.15 Amp, 250 VAC Blower Voltage...
  • Page 73: Repair Parts

    REPAIR PARTS 13. REPAIR PARTS Repair parts are available from your local PB Heat, LLC distributor or from Parts To Your Door at 1 (610) 916-5380 (www.partstoyourdoor.com). Note: Remember to include the boiler model number and serial number when ordering parts. Figure 13.1: General Repair Parts –...
  • Page 74 REPAIR PARTS Table 13.1: General Repair Parts Quantity Stock Description Required Code Front Door Panel with Ball Studs 54168 Control Lens 54167 Display Module, 852RC, PF 50-399 54702 Display Bracket Gasket 54153 Bracket for Display Module PF2007-1 Hex Nut, #6-32 with Lockwasher, (Local Hardware Supply) 51553 Screw, #6-32 x 1/2"...
  • Page 75 REPAIR PARTS Figure 13.2: Heat Exchanger/Burner Assembly Repair Parts – PF-50, PF-80, PF-110 & PF-140...
  • Page 76 REPAIR PARTS Table 13.2: Heat Exchanger/Burner Assembly Repair Parts – PF-50, PF-80, PF-110 & PF-140 Quantity Stock Description Required Code Kit Igniter & Cable w / Gasket & Hardware 54246 Igniter Only 54224 Igniter Cable 54298 Igniter Gasket 54123 Flame Sensor w / Gasket & Hardware 54247 Flame Sensor only 54295...
  • Page 77 REPAIR PARTS Figure 13.3: General Repair Parts – PF-200, PF-210, PF-300 & PF-399...
  • Page 78 REPAIR PARTS Table 13.3: General Repair Parts – PF-200, PF-210, PF-300 & PF-399 Quantity Stock Description Required Code Panel, Jacket Front Door, with Ball Studs 54256 Lens for Jacket Front Door 54167 Display Module 852RC (PF-50/399) 54702 Gasket for Display Bracket 54513 Bracket for Display Module PF2007-1...
  • Page 79 REPAIR PARTS Figure 13.4: Heat Exchanger/Burner Assembly Repair Parts – PF-200, PF-210, PF-300 & PF-399...
  • Page 80 REPAIR PARTS Table 13.4: Heat Exchanger/Burner Assembly Repair Parts – PF-200, PF-210, PF-300 & PF-399 Quantity Stock Description Required Code Kit Igniter & Cable w/ Hardware, PF50/80/110/140 54246 Igniter Only 54224 Igniter Cable 54298 Igniter Gasket 54123 Flame Sensor, with Gasket, Rauschert 54247 Flame Sensor Only 54295...
  • Page 81 REPAIR PARTS Figure 13.3: Concentric Horizontal Vent Termination Figure 13.4: Concentric Vertical Vent Termination Figure 13.5: Polypropylene Adapter Table 13.5: Optional Exhaust Vent Termination Kits Application Description PF-50 thru PF-300 & Stock Code PF-210 PF-399 – 3" Concentric Sidewall Termination Kit (PolyPro 3PPS-HK) •...
  • Page 82: Appendix A. Status Screens

    APPENDIX A. STATUS SCREENS APPENDIX A. STATUS SCREENS...
  • Page 83 APPENDIX A. STATUS SCREENS...
  • Page 84 APPENDIX A. STATUS SCREENS...
  • Page 85 APPENDIX A. STATUS SCREENS...
  • Page 86: Appendix B. User Menu

    APPENDIX B. USER MENU APPENDIX B. USER MENU...
  • Page 87: Appendix C. Installer Menu

    APPENDIX C. INSTALLER MENU APPENDIX C. INSTALLER MENU...
  • Page 88 APPENDIX C. INSTALLER MENU...
  • Page 89 APPENDIX C. INSTALLER MENU...
  • Page 90 APPENDIX C. INSTALLER MENU...
  • Page 91 APPENDIX C. INSTALLER MENU...
  • Page 92: Appendix D. Combustion Test Record

    APPENDIX D. COMBUSTION TEST RECORD APPENDIX D. COMBUSTION TEST RECORD Peerless ® ® Combustion Test Record Contact: Company Name: Address: Phone Number: Fax Number: Email Address: Jobsite Data Job Name: Jobsite Address: Boiler Data Boiler Model: Boiler Serial No.: Manufacture Date:...
  • Page 93 ® ® REV 2 Boilers PF-50 PF-80 PF-110 PF-140 PF-200 PF-210 PF-300 PF-399 I n s t a l l a t i o n , O p e r a t i o n & M a i n t e n a n c e M a n u a l TO T H E I N S TA L L E R : This manual is the property of the owner and must...

Table of Contents