SERVICE MANUAL Wall Mounted Type DC Inverter SUPER MATCH Model No. AS35S2SF1FA-WH WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity should be serviced or repaired only by experienced professional technicians.
Introduction 1 Introduction 1.1 Model name explanation Health White 220~240V50HZ/1ph R32 refrigerant version 1 Platform of indoor units:F(F Plstform) Supermatch second generation normal efficiency Nominal cooling capacity (12000BTU/h) Type of indoor unit: S (wall-mounted) Indoor unit Domestic air conditioner...
Specifications 2.Features Super quiet: Lower noise operation condition A-PAM DC inverter:With adoption of S-TYPE,S-PAM and PHASE control technology to works more stably at low-frequency,and is more energy-saving,mor powerful at high frequency. Long distance air supplying: The indoor units is improved by the optimized motor, fan and air duct so as to provide long distance airflow with 12m+ maximum.
Specifications TECHNICAL SPECIFICATIONS-PARTS cooling heating Air flow rate(high) m³/h Speed(Hi/Mid/Lo) 1200/1000/800 Type ML fin- 7HI-HX tube Heat exchanger c t i Removable/Washable/Mildew Proof Air filter Microcomputer Control Temperature control l l o 0010402886W Note: the data are based on the conditions shown in the table below Conversation formulae n i l Kcal/h= KW×860...
Connector Wiring diagrams 6. Printed Circuit Board Connector Wiring Diagram Connectors PCB(1) (Control PCB) For AS35S2SF1FA-WH CN9 Connector for fan motor CN6 Connector for heat exchanger thermistor and Room temperature thermistor CN5、CN5’ Connector for UP&DOWN STEP motor CN11、CN11’ Connector for RIGHT&LEFT STEP motor CN21(white line)、CN52(black line) Connector for indoor terminal N and L CN8 Connector for display board CN23 (red line) Connector for communicate between the indoor board and the outdoor board...
Page 15
Functions and Control 7.Funcitions and Control 7.1 Main functions and control specification 7.1.1 Automatic operation When the running mode is turned to automation after starting the system, the system will first determine the running mode according to the current room temperature and then will run according to the determined mode.
Functions and Control Control feature: send the dehumidifying signal to the outdoor system. When Tr>Ts+2℃, the compressor will be turned on, the indoor fan will operate at the set speed. When Tr is between the Ts and Ts+2℃, the outdoor system will operate at the high dehumidifying frequency for 10 minutes and then at the low dehumidifying mode for six minutes.
Page 17
Functions and Control 7.1.4 Heating operation mode. * temperature control range: 16---30℃ * temperature difference: ±1℃ * control feature: the temperature compensation is automatically added and the system will send the heating signals to the outdoor system. If Tr+0.5℃≤Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode. If Tr>Ts+1.5℃, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
Page 18
Functions and Control Send strength operation signal to the outdoor system. The mode change finishes the strength operation. Entering ‘mute’, you can have normal operation or signal control such as timing to finish the strength operation. When the system is at the automatic option with the strength/ mute function, if the system enters the cooling mode, the cooling strength/ mute function will be offered;...
Page 19
Functions and Control operations, the set temperature will be raised for 1 centigrade and the system will keep this status for 3 hours and then close down. 2.3 During the dormant time, except the change of the system mode or a new press on the dormant setting keys, the timing of the 8 hours dormancy will take the first timing as the start time, any presses on other keys will not affect the original timing.
Page 20
Functions and Control 7.1.12 High load protection control The outdoor system will be stopped if the coil temperature is above 63℃ for 2 minutes. The indoor fan will be controlled by the thermostat. The outdoor system can be restarted when the coil temperature is below 45℃...
Page 21
Functions and Control 7.1.16 Single indoor system operation * Enter condition: First, set the high speed airflow and 30 centigrade set temperature, then press the dormant keys for 6 times within 7 seconds, the system will feedback with 6 rings. * After the system enters the separate indoor system operation mode, the indoor system will operate according to the set mode and neglect the communication signals of the outdoor system.
Page 22
Functions and Control 7.2 Value of thermistor Room sensor and Pipe Sensor Room sensor R25℃=23KΩ±2% B25℃/50℃=4200K±1% R25℃=23KΩ+2% Temp.(℃) Resistor(KΩ) Temp.(℃) Resistor(KΩ) Temp.(℃) Resistor(KΩ) 266.905 32.215 250.866 30.671 5.87 235.895 29.21 5.65 221.911 27.828 5.44 208.838 26.521 5.24 196.609 25.283 5.04 185.163 24.111 4.86...
Service diagnosis 10. Service Diagnosis 10.1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.
Page 29
Service diagnosis 10.3 Error Codes and Description indoor display Code indication Indoor displaying panel code indication Outdoor Reference Only For 498 and fault description (LED1 Page 498A display flash Other display (Red/Green Time times) □On ★ Flash■Off) ● Indoor and Communication fault between Directly display Page.36...
Page 30
Installations 10.3.1 Thermistor or Related Abnormality Indoor Display E1: Room temperature sensor failure E2: Heat-exchange sensor failure Outdoor display LED1 flash 10 times:Defrost temperature sensor failure LED1 flash 11 times:Suction temperature sensor failure LED1 flash 12 times:Ambient temperature sensor failure LED1 flash 13 times:Discharge temperature sensor failure Method of The temperatures detected by the thermistors are used to determine thermistor errors...
Page 31
Installations 10.3.2 EEPROM abnormal Indoor Display E4: Indoor EEPROM error Indoor display F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times Method of The Data detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed...
Page 32
Installations 10.3.3 Indoor fan motor malfunction Indoor Display Method of The rotation speed detected by the Hall IC during fan motor operation is used to determine Malfunction abnormal fan motor operation Detection Malfunction when the detected rotation feedback signal don’t received in 2 minutes Decision Conditions Supposed Causes...
Page 33
Installations Check whether Terminal on the outdoor mainboard is well inserted. it is normal Reinsert the terminals Electrify the machine again and turn it on in The motor and the Cool state with the remote controller. outdoor pcb are check whether the motor could run. well R emove fan m otor af te r s witch off the power.Measure the resistances...
Page 34
Installations Supposed ■ IPM protection dues to the compressor faulty Causes ■ IPM protection dues to faulty PCB of IPM module ■ Compressor wiring disconnected Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, else parts damage may be occurred.
Page 35
Installations Electrify the machine again and turn it on with the remote controller, If malfunctions IPM Module is damaged and are reported before or upon the compressor needs replacing. being started up, The compressor is started normally, but malfunctions are reported after it has Repair the power supply run for some time.
Page 36
Installations 10.3.8 Power Supply Over or under voltage fault Outdoor display: LED1 flash 6 times The power supply is over voltage Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit. Malfunction Detection Malfunction An voltage signal is fed from the voltage detection circuit to the microcomputer Decision...
Page 37
Installations 10.3.9 Overheat Protection For Discharge Temperature Outdoor display: LED1 flash 8 times Method of The Discharge temperature control is checked with the temperature being detected Malfunction by the Discharge pipe thermistor Detection Malfunction when the compressor discharge temperature is above 110℃ Decision Conditions Supposed...
Page 38
Installations 10.3.10 The communication fault between indoor and outdoor Indoor display outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB. Malfunction Detection Malfunction ■ The outdoor PCB broken leads to communication fault. Decision ■...
Page 39
Installations If the voltage is a constant value The indoor mainboard is of 0V DC to 5V DC.Or the voltage damaged; replace it with a between Communication line(red ) and N(white new one. line) is not close to18V DC when only indoor charged. Test the outdoor power is Check the cable supply 230VAC with a...
Page 40
Installations 10.3.11 Loss of synchronism detection Inverter side current detection is abnormal Outdoor Display LED1 flash 18 times LED1 flash 19 times Method of The position of the compressor rotor can not detected normally Malfunction Detection Malfunction when the wiring of compressor is wrong or the connection is poor; Decision or the compressor is damaged Conditions...
Page 41
Table of Contents 10.3.12 High work-intense protection Outdoor display LED1 flash 21 times Method of High work-intense control is activated in the heating mode if the temperature Malfunction being sensed by the heat exchanger thermistor exceeds the limit. Detection Malfunction Activated when the temperature being sensed by the heat exchanger Decision rises above 65℃...
Table of Contents 11. Wiring diagrams 11.1 INDOOR UNIT WIRED CONTROLLER WIFI MAG SWITCH SWITCH SW1/CN14 UP-DOWN STEPMOTOR LEFT-RIGHT STEPMOTOR CONDENSER Domestic air conditioner...
Page 43
Circuit diagrams 11.2 Circuit Diagrams Domestic air conditioner...
Page 44
Repair the product or products dealt with in this service information by anyone else could result in serious injury or death 2017 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Page 45
Removal Procedure Removal of front panel front panel Loosen the screw Domestic Air Conditioner...
Page 46
Removal Procedure Lift up the control box cover 3 Remove the control box cover Domestic Air Conditioner...
Page 47
Removal Procedure Remocal of front panel Pull the wires off the panel and then release the pivots on both sides of the unit to remove the front panel. Remove the air filters Domestic Air Conditioner...
Page 48
Removal Procedure Remove the casing four four Domestic Air Conditioner...
Page 49
Removal Procedure horizontal flap and the stepper motor flap Loosen the screws and remove the stepper motor Domestic Air Conditioner...
Page 50
Removal Procedure horizontal louver and control box Every blade go round and round,then move Loosen the screw Domestic Air Conditioner...
Page 51
Removal Procedure Loosen the hook and the service Cover Lift up the exchanger and remove it Domestic Air Conditioner...
Page 52
Removal Procedure motor cover Domestic Air Conditioner...
Page 53
Removal Procedure Domestic Air Conditioner...