Rinnai MSB-C3 Installation Instructions Manual page 5

Manifold electronic control system

Advertisement

For Units 2, 3, 4, and 5:
5) Run the 4-pin connector of
Communication Cable B (9.8 ft, 3 m
cable) up through the cable
access in the bottom of
Unit 1's cabinet.
6) Connect the connector of the
Communication Cable B to socket
2 on the Control Board. The
Communication Cable B ground
wire terminals should be grounded
with the MSB ground wire and
Communication Cable A ground
wire terminal.
Ground wires of
Communication Cable B
7) Run the other end of
Communication Cable B through
the cable access in the bottom of
Unit 2's cabinet.
8) Connect the 4-pin connector
from Communication Cable B to the
4-pin socket located at the top of
the water heater control board of
Unit 2. Communication Cable B
ground wire terminal should be
grounded with the PC board
ground wire.
Ground wire of
Communication Cable B
9) Attach the cable tie bracket to
the bottom of the water heater
cabinet using the existing screw.
Pull all of the excess cable up into
Unit 2's cabinet, and then secure it
tightly to the bracket using the
cable tie.
10) Repeat steps 5 to 9 for Units 3,
4, and 5, as applicable.
Note: Communication Cable B for
Unit 3 plugs into socket 3, Unit 4
plugs into socket 4, etc.
11) After making all of the
connections to the Control Board,
tighten all of the cable ties used to
secure the Communication Cables.
12) Place the front cover panels
back on each of the water heaters
using (4) screws.
13) Restore power to the water
heaters.
System Operation
• The Control Board can
electronically connect up to 25
water heaters.
• When multiple water heaters
are operating, they will attempt
to supply equal amounts of hot
water.
• On initial water flow demand,
from 1 to 3 units which can be
determined by Dip SW setting
of Master MSB board will open
their servos valves until flow
demand is determined. See
Dip SW table for open water
flow valve. Only the necessary
number of water heaters will
begin to fire to meet demand.
Water heaters not firing will
close their valves.
• As the default setting, 3 units will
open its servo valve until flow
demand is determined.
It is recommended that the dip
switch settings on MSB boards
other than the Master MSB board
be set for 1 unit ready.
• When installation is completed,
do a test run for all units.
• After the test run, check and clean
the water filter on all units.
Dip SW table for open water flow servo valve
When viewing the installed MSB board, the dip switch will be as
shown below (upside down).
3 units ready (default)
No1 OFF
No2 OFF
Dip SW
setting
NOTE: In a recirculation system, in order to increase the tempera-
ture setting, it is necessary to turn off the power supply to the
circulation pump, increase the temperature setting, and then turn
the pump back on. No additional action is necessary when
decreasing the temperature setting.
Indicator lights on the Control Board indicate the status of each
of the water heaters as follows:
LED 1 ~ 5
Water flow servo valve is open when water
Solid
heater is in standby or working.
Flashing Slowly (1.2
Water flow servo valve is closed when water
sec on / 0.5 sec off)
heater is not operating.
Flashing Quickly
An error is detected. A temperature controller
(0.5 sec on / 0.5 sec
must be connected to this unit to read the
off)
error code.
Off
No unit detected at this connection.
• The temperature setting for all
of the connected water heaters
is controlled by the
temperature controller
connected to the water heater
with the Master MSB Board.
Temperature controllers
connected to the other units
will provide maintenance
codes for their respective units.
• If water heaters do not use a
temperature controller, the
temperature setting for the
water heater with the Master
MSB board is used.
• If a water temperature over
140 degree F is desired, then
an MCC-91 controller needs to
be connected to Master
Control Board.
• For proper operation, it is not
recommended that different
models be connected together.
Combining different models may
result in lower performance.
• The order in which each water
heater operates is occasionally
rotated to ensure equal usage
among the entire system.
2 units ready
1 unit ready
No1 ON
No1 ON
No2 ON
No2 OFF
LED 6
(Working with multiple MSB boards)
LED 1 ~ 5
EXPLANATION