Kohler 15RES Manual page 16

Residential generator sets
Table of Contents

Advertisement

Code Fault
AF
Auxiliary fault
input shutdown
HE
High engine
temperature
shutdown
LCL
Low coolant
level
LOC
Loss of coolant
LOP
Low oil
pressure
shutdown
OC
Overcrank
shutdown
OF
Overfrequency
shutdown
OS
Overspeed
shutdown
OU
Overvoltage
shutdown
UF
Underfrequency
shutdown
UU
Undervoltage
shutdown
SCF0 Software
Communication
Fault 0
Figure 2-4 ADC 2100 Fault Shutdown Codes
16
Section 2 Operation
Description
Input from a customer-supplied switch that closes
when the fault is active. The generator set shuts
down 0.3 seconds after the fault is detected and will
not start when the fault is active (input is grounded).
This protection becomes active 3 seconds after
crank disconnect.
Shutdown occurs if the engine coolant temperature
exceeds the maximum temperature for more than
5 seconds. This protective becomes active after the
engine reaches the crank disconnect speed.
Not used.
Not used.
Shutdown occurs if a low oil pressure condition
exists for more than 5 seconds. This protective
becomes active 30 seconds after the engine has
reached crank disconnect speed (30 second inhibit).
Shutdown occurs after 3 unsuccessful starting
attempts. The crank cycle is set for three starting
attempts of 15 seconds cranking and 15 seconds
rest.
The generator set also shuts down if no engine
rotation is sensed during cranking. Shuts down
1 second after the fault is detected.
Shutdown occurs when the governed frequency
exceeds 110% of the system's frequency setpoint
for more than 5 seconds. This protective becomes
active 10 seconds after engine start (10 second
inhibit).
Shutdown occurs if the engine speed exceeds 115%
of the normal running speed for more than
0.3 seconds.
Shutdown occurs if the voltage exceeds 120% of the
system nominal voltage for more than 2 seconds.
Shutdown occurs when the governed frequency falls
below 90% of the nominal system frequency for
more than 5 seconds or below 59 Hz for more than
60 seconds. This protective becomes active
10 seconds after engine start. (10 second inhibit).
Shutdown occurs if the voltage falls below 80% of
the nominal system voltage for more than
10 seconds.
Indicates a software or communication problem
within the
.
ADC 2100
Check
Check the cause of the auxiliary fault.
Check for blocked air inlets and exhaust
outlets.
Check for leaks in the lubrication system.
Check the oil level and add oil if the level is
low.
Check the fuel supply, spark plug, and
battery.
Check for loose connections.
Contact an authorized Kohler distributor/
dealer for service if problem continues.
Contact an authorized Kohler
distributor/dealer for service if problem
continues.
Contact an authorized Kohler
distributor/dealer for service if problem
continues.
Contact an authorized Kohler distributor/
dealer for service if problem continues.
Reduce the load and restart the generator
set.
Contact an authorized Kohler
distributor/dealer for service if problem
continues.
Reduce the load and restart the generator
set.
Contact an authorized Kohler distributor/
dealer for service if problem continues.
Replace the controller.