Vandal resistant emergency light

Advertisement

T-bar installation (see figure 5)
1. Bend the 4 tabs on the mounting frame 90 degrees outward to hang onto
the t-bar.
2. Hook the mounting frame onto the t-bar and use 4 self-drilling screws (not
provided) to secure the mounting frame to the t-bar.
3. Feed AC circuit wires to junction box on the unit and leave 6 inches of wire.
4. Make the proper connections according to model configuration:
For self-powered see figure 3.
For AC, AC/DC see figure 4.
5. Insert unit into the mounting frame and ensure all 4 clips are engaged.
Maintenance:
Equipment must be tested regularly in accordance with local codes.
AUTO-TEST OPTION
(Self-powered units only)
Self-Diagnostics / Self-Testing
1. When AC power is supplied to fixture, the unit will automatically initiate a
self-test and self-diagnostic test as follows:
a. Verifies battery disconnection, charger board failure, lamps failure and
transformer failure at every 4 seconds.
b. 3 minute self-testing every month after installation.
c. 120 minute self-testing every year after installation.
d. Factory per-sets all functions. Does not need field adjustment.
2. Dual color LED lamp indicator shows the following status:
a. Green color: ON/ Ready
Blinking: Testing
b. Red color (Service Alert)
c. Service Alert LED Code (Red color LED lamp indicator)
o
One blink ON/pause (4 seconds)
oo
Two blinks ON/pause (4 seconds)
ooo
Three blinks ON/pause (4 seconds)
oooo
Four blinks ON/pause (4 seconds)
ooooo
Five blinks ON/pause (4 seconds)
Note:
After solving emergency equipment fault, press test button for 2 seconds
without releasing. LED lamp will show green and unit will resume charging.
3. For manual test, press test button as follows:
Press test button once (within 2 seconds)
Press test button twice (within 2 seconds)
Press test button 3 times (within 2 seconds)
Press test button 4 times (within 2 seconds)
This unit comes with a (3) three year limited warranty.
Refer to (www.emergi-lite.com/warranty) for full warranty.
Tel: (888) 552-6467
© 2020 ABB. All rights reserved.
Battery is not con-
nected
Battery is shorted or
battery voltage drops
below acceptable
level.
Charger board circuit
fault.
Transformer fault.
Emergency lamp fault.
30 second test
3 minute test
30 minute test
90 minute test
Fax: (800) 316-4515
EGNL Series Vandal Resistant Emergency Light
Wiring diagram for AC / DC models
With wall switch
Connect the black wire to 120/347Vac, white wire to the neutral.
Connect the red wire to one contact of the wall switch and connect the
other contact to the black wire as shown below.
CAP YELLOW AND PURPLE WIRE SEPARATELY IF NOT USED.
Yellow +
PCBA
DC input
Purple - 12-24Vdc
LED 2
LED 1
Wall switch
Red
Without wall switch
Connect the black and red wires to hot lead, white wire to the neutral as
shown below.
CAP YELLOW AND PURPLE WIRE SEPARATELY IF NOT USED.
DC input
PCBA
LED 2
LED 1
Red
Figure 4
T-bar
4 Self-drilling screws
J-box cover
(not provided)
J-box
Figure 5
Standard light output
180°
Narrow light output
120°
Figure 6
White (Neutral)
Black (120 to 347VAC)
Yellow +
Purple - 12-24Vdc
White (Neutral)
Black (120 to 347VAC)
T-bar
Unit
Directional light output
60°
60°
06/20 750.2103 Rev. A