Get Point Configuration - 0X35 - Honeywell CM4 Operating Instructions Manual

Serial communication protocol
Hide thumbs Also See for CM4:
Table of Contents

Advertisement

Honeywell Analytics
Get Point
Configuration
0x35
This command queries an individual point for its
current configuration.
Command packet to instrument:
Command Code (0x35) - 1 byte
Point Flag - 1 byte
bits 0-1: Point Number
bits 2-7: Undefined
Response packet from instrument:
Command Code (0x35) - 1 byte
CM4 Date - 2 bytes
CM4 Time - 2 bytes
Point Status Flag - 1 byte
bit 0: Point Enable/Disable bit
bits 1-2: Point locked status
bits 3-7: Undefined
MDA Gas Abbr. - 6 bytes (not null terminated)
Gas Table number - 1 byte (0 is the first table)
Format Code - 1 byte
Alarm Level 1 - 2 bytes
Alarm Level 2 - 2 bytes
20 mA - 2 bytes
Full Scale - 2 bytes
Point ID - 20 bytes
Status - 1 byte
0x00 = Point read
0xff = Error
17
CM4 Protocol Manual
00 = Point 1
01 = Point 2
10 = Point 3
11 = Point 4
0 = Disabled
1 = Enabled
00 = Normal (No point lock-on)
01 = Lock-on for this point
10 = Lock-on for another point
11 = Undefined
Rev. 2.4 (3/05)