Member Objects; Type: Gateway; Type: Batch Objects; Type: Indoor Unit - Fujitsu BACnet UTY-VBGX Instruction Manual

Gateway for vrf system
Table of Contents

Advertisement

BACnet
®
Gateway for VRF System

Member objects

5.2.1 Type: Gateway

Object-name
UTY-VBGX
Gateway_ES_Status
Gateway_Error_Status
Gateway_ES_Setting
Gateway_ErrorCode_Status

5.2.2 Type: Batch objects

Batch_SetTemp_Setting
Batch_Operation_Setting
Batch_OperationMode_Setting
Batch_FanSpeed_Setting
Batch_RC_Prohibition_Setting

5.2.3 Type: Indoor Unit

IU_rr_uu_SetTemp_Status
IU_rr_uu_SpaceTemp_Status
IU_rr_uu_AutoTempLoLim_Status
IU_rr_uu_AutoTempHiLim_Status
IU_rr_uu_CoolTempLoLim_Status
IU_rr_uu_CoolTempHiLim_Status
IU_rr_uu_HeatTempLoLim_Status
IU_rr_uu_HeatTempHiLim_Status
IU_rr_uu_SetTemp_Setting
IU_rr_uu_AutoTempLoLim_Setting
IU_rr_uu_AutoTempHiLim_Setting
IU_rr_uu_CoolTempLoLim_Setting
IU_rr_uu_CoolTempHiLim_Setting
IU_rr_uu_HeatTempLoLim_Setting
IU_rr_uu_HeatTempHiLim_Setting
IU_rr_uu_Exists_Status
IU_rr_uu_Operation_Status
IU_rr_uu_ThermostatOFF_Status
IU_rr_uu_FilterSign_Status
IU_rr_uu_Emergency_Status
IU_rr_uu_Error_Status
IU_rr_uu_TempLimValid_Status
IU_rr_uu_Operation_Setting
IU_rr_uu_ThermostatOFF_Setting
IU_rr_uu_Reset_Filter_Setting
IU_rr_uu_TempLimValid_Setting
IU_rr_uu_OperationMode_Status
IU_rr_uu_FanSpeed_Status
Description
BACnet Gateway for VRF System
-
-
-
-
Object-name
Object-name
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Object-type
Device
Object-type
Object-instance
AO
BO
MO
MO
MO
Object-type
Object-instance
AI
AI
AI
AI
AI
AI
AI
AI
AO
AO
AO
AO
AO
AO
AO
BI
BI
BI
BI
BI
BI
BI
BO
BO
BO
BO
MI
MI
Object-instance
BI
BI
BO
MI
0
1
0
1
2
10rruu
11rruu
12rruu
13rruu
14rruu
15rruu
16rruu
17rruu
10rruu
11rruu
12rruu
13rruu
14rruu
15rruu
16rruu
10rruu
11rruu
12rruu
13rruu
14rruu
15rruu
16rruu
10rruu
11rruu
12rruu
13rruu
10rruu
11rruu
19/103
144
0
1
0
0

Advertisement