Mitsubishi Electric AJ65VBTCU-68DAVN User Manual page 37

Programmable controller digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

3 SPECIFICATION
Table 3.9 Remote Register Assignment for Ver. 2 Remote Device Station
Transfer Direction
Master
Remote
Remote
Master
3 - 15
(2) Remote register assignment for ver. 2 remote device station (ver. 2
compatible slave station) setting
Table 3.9 indicates the remote register assignment for ver. 2 remote device
station (ver. 2 compatible slave station) setting.
(Ver. 2 Compatible Slave Station) Setting
Address
RWwm+0
H
RWwm+1
H
RWwm+2
H
RWwm+3
H
RWwm+4
H
RWwm+5
H
RWwm+6
H
RWwm+7
H
RWwm+8
Analog output enable/disable setting
H
RWwm+9
CH. 1 to 4 output range setting
H
RWwm+A
CH. 5 to 8 output range setting
H
RWwm+B
H
RWwm+C
H
to
RWwm+F
H
RWrn+0
H
RWrn+1
H
RWrn+2
H
RWrn+3
H
RWrn+4
H
RWrn+5
H
RWrn+6
H
RWrn+7
H
RWrn+8
H
RWrn+9
H
to
RWrn+F
H
POINT
Do not execute read or write to the remote register that is not allowed to use. When
a read or write is executed, the functions of the AJ65VBTCU-68DAVN is not
guaranteed.
Description
CH. 1 digital value setting
CH. 2 digital value setting
CH. 3 digital value setting
CH. 4 digital value setting
CH. 5 digital value setting
CH. 6 digital value setting
CH. 7 digital value setting
CH. 8 digital value setting
HOLD/CLEAR setting
Reserved
CH. 1 check code
CH. 2 check code
CH. 3 check code
CH. 4 check code
CH. 5 check code
CH. 6 check code
CH. 7 check code
CH. 8 check code
Error code
Reserved
m, n: The address set for the master station in the station number setting.
MELSEC-A
Default Value
Refer to
0
0
0
0
Section 3.6.2
0
0
0
0
0
Section 3.6.3
0
Section 3.6.4
0
0
Section 3.6.5
0
0
0
0
0
Section 3.6.5
0
0
0
0
0
Section 3.6.7
0
3 - 15