Overview; Structural Principle - AEG VB 40.5 User Manual

Vacuum circuit breaker
Table of Contents

Advertisement

1. Overview

1-1 General:
VB 40.5 vacuum circuit breaker (hereinafter referred to as circuit breaker) is applicable to AC 50Hz
and 35kV Power Systems, and can be used as protection and control equipment for industrial and mining
enterprises, power plants and substations, and is applicable to frequently operated occasions.
1-2 General provisions:
The circuit breaker complies with the following standards:
GB/T 1984
IEC 62271-100
IEC 60694
DL/T 403
1-3 Normal operating conditions:
Ambient temperature
Maximum temperature:
Minimum temperature:
Maximum daily average temperature:
Ambient humidity
Daily average relative humidity:
Monthly average relative humidity:
Daily average saturated vapor pressure:
Monthly average saturated vapor pressure:
Earthquake intensity:
Altitude:
Others: no inflammable and explosion hazard, no chemical corrosive gas and no violent vibration.
Note: in case of different use environment or other special requirements, it is necessary to consult with
the manufacturer.

2. Structural principle

2-1 Main structure
The circuit breaker adopts integrated and modular design, and the overall structure is simple and
reasonable. It adopts upper and lower settings, with the arc extinguishing chamber part above and the
interlocking and operating mechanism part below. Special spring operating mechanism is used, without
adjustment, and the action is stable and reliable.
The vacuum arc extinguishing chamber of the three-phase conductive circuit of the circuit breaker is
arranged in the closed solid sealing pole column, which not only improves the insulation performance of the
High-voltage alternating-current circuit-breakers
High-voltage switchgear and controlgear - Part 100: Alternating current
circuit-breakers
Common specifications for high-voltage switchgear and controlgear
standards
HV vacuum circuit-breaker for rated voltage 12kV to 40.5kV
+ 40ºC
- 25ºC
+ 35ºC
≤95%
≤90%;
≤2.2×10
≤1.8×10
No higher than Level 8
≤ 1000m, conventional products can be used below 1000m above sea
level, and high-altitude products need to be noted when ordering.
-3
Mpa
-3
Mpa
1