Operation And Service; Troubleshooting - TCRS AH150TON Operating And Service Manual

150 ton ahu

Advertisement

 Turn on Main Disconnect
 Turn BLOWER switch to the ON position. Green BLOWER ON light indicates system is powered.
 Turn BLOWER SPEED to desired speed. Blower minimum speed is 30% when blower is on.
 Filter and mist eliminator must be kept clean to ensure proper operation.
Caution must be taken when troubleshooting the electrical circuit and should only be performed by a trained service
technician.
INDICATION
Nothing
operates
Blower Fault
For operation and service concerns please call:

Operation and Service

POSSIBLE CAUSE
Main power
Control power
Breaker tripped
Motor failure

Troubleshooting

CORRECTIVE ACTION
Check voltage
Check transformer and fusing
Find cause, reset breaker
Verify 480V 3ph is present
Verify 0-10VDC control voltage is present
replace blower motor if not responding
440-658-2020