Instructions Specific To Hazardous Area Installations - Siemens SITRANS L 7ML1100 Operating Instructions Manual

Ultrasonic level transducers
Table of Contents

Advertisement

B.2

Instructions specific to hazardous area installations

(Reference European ATEX Directive 2014/34/EU, Annex II, 1/0/6)
These following instructions apply to equipment covered by certificate numbers
SIRA 99ATEX5091X (XRS-5), SIRA 99ATEX5153X (XPS), SIRA 13ATEX5017X (ST-H),
CSAE 21UKEX5096X (XRS-5), CSAE 21UKEX5092X (XPS), and CSAE 21UKEX5093X (ST-H).
1. The XPS-10 and XPS-15 are certified for use as Category 2GD while the XPS-30 is certified for
use as Category 2G 1D per SIRA 99ATEX5153X and CSAE 21UKEX5092X..
2. The equipment may be used with flammable gases and vapors with the following apparatus
groups and temperature classes:
3. The XRS-5 equipment has a temperature class of T85 °C and may be used with flammable
dusts.
The XPS Transducers equipment has a degree of ingress protection of IP67 and a
temperature class of T135 °C and may be used with flammable dusts.
4. The equipment is certified for use in the following temperature range:
Transducers
Compact Operating Instructions, 09/2021, A5E43390688-AC
Apparatus group
Temperature class
B.2 Instructions specific to hazardous area installations
XRS-5
XPS Transducer
II
T1 to T6
T1 to T4
ST-H
II
II
T5
Certificates
53