Intermatic PanelGuard PG100 Series Installation Instructions And Operation Manual
Intermatic PanelGuard PG100 Series Installation Instructions And Operation Manual

Intermatic PanelGuard PG100 Series Installation Instructions And Operation Manual

Electrical panel extension hardwired surge protection devices

Advertisement

Quick Links

PanelGuard
Electrical Panel Extension Hardwired Surge
INTRODUCTION
The PG60-80-100 Series is designed to be installed in very close prox-
imity to the power bus of an electric distribution panel or electric panel-
board. It can be used with most panels or panelboards in distribution
today. The PG60-80-100 Series offers peak surge amperage protection
levels of 60 kA to 100 kA per mode. It is designed to be easily mounted
above or below the panelboard. Provisions have been made with a
reversible cover plate to keep the instructions and indicators in a user
friendly position. Standard features include all mode protection, multi-
mode LED indicators that show full protection, diminished protection and
lost protection for all phases. A form C relay for remote alarm indication,
audible trouble alarm with test and silence switch are also standard
equipment.
The system is comprised of three sections; outer housing, cover plate
and inner module. Each section is engineered to make the installer/ser-
vice technician's task as easy as possible. A description of each section
and the function follows.
Outer Housing - Metal housing measuring 20" wide x 16" high x 6"
deep. The outer housing contains the inner housing. connection lugs for
each phase, neutral and ground, connections for the form C alarm relay
and the audible alarm test and silence switch.
A 5/8" flange on the forward side of the housing has ten (10) threaded
holes that are used to attached the cover plate. Four (4) mounting holes
are located in the back surface of the housing for mounting. It is sug-
gested that all four (4) fasteners be used to secure the outer housing.
Cover Plate - Metal plate measuring 19 13/16" wide x 15 13/16" high.
The cover plate contains ten (10) holes located around the edges that
matched the threaded holes in the outer housing and are used to secure
the cover plate to the outer housing. The cover plate is reversible and
has an identification label on both front and reverse sides. The labels
are mirror images of each other and selection of which side to use
depends upon the placement of the outer housing. (This process will be
explained in the installation section that follows.)
Inner Module - Metal box measuring 13 3/16" wide x 9 3/4" high x 4
15/16" deep including the mounting rails that are part of the module.
The inner module is fastened to the outer housing with four (4) bolts
through the mounting rails. Module identification and wiring diagram
labels are attached to the inner module. The inner module contains all
of the surge suppression, noise filtering, fusing, monitoring and reporting
components. Copper bus bars and terminal lugs extend from the inner
module.
NEC Section 285 requires that a SPD have a fault current rating equal
to or greater than the point of installation (switchboard or panelboard).
The PG60-80-100 Series is suitable for use on a circuit capable of deliv-
ering not more than 200,000 amperes (120/208-3Y, 120/240-2S,
120/240-3HLD, 277/480-3Y models). 480-3D models are rated at
25,000 amperes. Should you require a 480-3D model with a higher fault
current rating consider Intermatic PG2500/PG3000/PG3500 Series
which are rated at 200 kAIC.
INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL
100 SERIES - V.10-03
®
PG60 - PG80 - PG100 Series
INSTALLATION INSTRUCTIONS
and
OPERATIONS MANUAL
Model # PG100 - 208 - 3Y
P
S
R
EAK
URGE
ATING
PG60
60 kA per Mode
PG80
80 kA per Mode
PG100
100 kA per Mode
S
V
UPPLY
OLTAGE AND
240-2S
120/240 Single Phase
208-3Y
120/208 Three Phase Wye
240-3HLD 120/240 Three Phase H. L. Delta
480-3Y
277/480 Three Phase Wye
480-3D
480 Three Phase Delta
20.0"
ALARM
PROTECTION MODES
Red ALARM light ON or
Green lights ON indicate
Alarm
L1
L2
L3
Neutral
power present and protec-
Audible Alarm ON indicates
loss of protection. Refer to
tion circuits for each mode
the operation manual for
are operating propely.
One or more Green lights
troubleshooting help.
OFF indicates loss of power
Ground
or protection. Refer to the
L1
L2
L3
operation manual for
troubleshooting help.
CAUTION; HIGH VOLTAGE INSIDE
SEVICE BY QUALIFIED PERSON NEL ONLY
C
ONFIGURATION
6.0"
OPERATION
16.0"
PG60-80-

Advertisement

loading

Summary of Contents for Intermatic PanelGuard PG100 Series

  • Page 1 100 SERIES - V.10-03 INSTALLATION INSTRUCTIONS ® PG60 - PG80 - PG100 Series PG60 PG80 PG100 OPERATIONS MANUAL Model # PG100 - 208 - 3Y URGE ATING 60 kA per Mode 80 kA per Mode 100 kA per Mode UPPLY OLTAGE AND...
  • Page 2: Before Installation

    Surge Protection Device, contact your supplier. If you have questions about the proper use of this unit for your application, contact Intermatic at the numbers listed under TECHNICAL ASSISTANCE on page 5 of this publication. Wire Pass-through area...
  • Page 3 INSTALLATION (above panelboard) PG60-240-2S PG80-240-2S Turn OFF and LOCK the electric power supply to the panel- PG100-240-2S board. SELECT the location where the Surge Protection Device (SPD) will be mounted, above or below the electric panel. Position the SPD adjacent to the electric panel with the bus bars pointed toward the panel.
  • Page 4: Alarm Relay Connections

    Use the following table as a guideline for the PG60, PG80 and PG100 Surge Protection Devices. All models have integral overcurrent fusing and the use of a dedicated circuit breaker is optional. Lugs accept wire sizes from 10 AWG to 2 AWG. Keep all leads as short and straight as possi- ble, avoiding sharp 90 degree bends.
  • Page 5 NOTE: In this application, the label with the LED indi- cators will be at the bottom of the cover plate. TECHNICAL ASSISTANCE For application or technical assistance contact Intermatic at 1-800-391-4555 or on the web at www.intermatic.com. INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL TYPICAL INSTALLATIONS...
  • Page 6 (2) What Is Not Covered By This Warranty Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the Product; (b) damage caused by use of the Product for purposes other than those for which it was designed; (c) damage caused by disaster such as fire, flood and wind;...

This manual is also suitable for:

Panelguard pg60 seriesPanelguard pg80 series