DBC.2 "increased safety" terminal blocks, are manufactured according to the prescriptions given by
IEC / EN 60079-0, IEC / EN 60079-7 Standards and are in compliance with the ATEX 94/9/CE Directive and the IEC
Ex Certification Scheme
DBC.2 terminal blocks are also designed and manufactured in compliance with IEC / EN 60947-1 and IEC / EN 60947-7-1
reference product standards.
Terminal blocks (components) must be inserted in Ex e enclosures. The terminal blocks + enclosure assembly must
be subjected to separate certification.
DBC.2 terminal blocks are suited for a temperature range between - 40 and + 80 °C
Ambient temperature range shall be between - 40 and + 40 °C
Rail assembly composition in potentially expolosive (Ex e) environments
End section
Each rail assembly is formed by two or more adjoining terminal blocks and by END BRACKETS, that are located at the ends of
the assembly, in a way to obtain a compact and single arrangement.
As the back of each terminal block performs the function of insulating wall for the adjoining terminal block, an END SECTION is
necessary to close and provide appropriate insulation to the first terminal block forming the assembly.
Rail assemblies can be subdivided into groups by interposing COLOURED PARTITIONS, in order to ease the location of
different circuits
Each terminal block can be connected to adjoining elements by means of CROSS CONNECTION of the comb type.
Adjoining terminal blocks can be visually separated by interposing a COLOURED PARTITION, having a thickness of 1,5 mm.
Adjoining jumpers between different phases should be electrically separated by interposing an END SECTION type DBC/PT.
Multiple cross connections can be performed between terminal blocks, by means of a comb-type CROSS CONNECTION the
use of which enables also to obtain parallel extending, pole skipping, staggered, and parallel skipping cross-connection
schemes
Ex e Instruction Manual N° 31
Mounting rail
TECHNICAL NOTE
Comb-type cross connection PTC "Easy bridge"
End bracket
Page Rev.
31
1
4
18/07/14
Date
Issued
Approved

Advertisement

loading

Summary of Contents for cabur DBC.2

  • Page 1 IEC / EN 60079-0, IEC / EN 60079-7 Standards and are in compliance with the ATEX 94/9/CE Directive and the IEC Ex Certification Scheme DBC.2 terminal blocks are also designed and manufactured in compliance with IEC / EN 60947-1 and IEC / EN 60947-7-1 reference product standards.
  • Page 2 Ex e I Mb Ex e = “increased safety” protection mode = gas group = EPL = group I (mines) = EPL DBC.2 two-level feed-through terminal block - Rated Ex values Minimum / Resistance Ex e Gauge Rated Rated maximum...
  • Page 3 Wire clamping collar Note(*): values taken from Table 4 of IEC 60947-1 Std. Cabur terminal block type DBC.2 allows the direct and anti-loosening connection of solid, stranded and flexible conductors, by means of wire clamping collars, captive screws and conducting body.
  • Page 4 Attestation of Conformity to ATEX 94/9/EC Directive Inserted in the following document: M19/e general instructions (leaflet inserted in every package) Terminal blocks approved in conformity to ATEX 94/9/CE Directive Terminal blocks “at increased safety” (Ex e) are manufactured according to IEC/EN 60079-0, IEC/EN 60079-7 Std.