APCQ Capacitor Banks
Installation, operation and maintenance instructions

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi APCQ

  • Page 1 APCQ Capacitor Banks Installation, operation and maintenance instructions...
  • Page 2: Table Of Contents

    6.10. Optional base frame (200 mm) and flanges (base frame covers) ............. 31 6.11. Optional space heater ........................32 6.12. Optional internal lamp ........................33 6.13. APCQ from 350 to 550 kvar (master + slave with one connexion point) ........... 33 STATUS SECURITY LEVEL DOCUMENT ID REV.
  • Page 3 AP CQ CAPA CITO R BA NKS 6.14. APCQ for 600 and 900 kvar (master + slaves) .................. 34 7. Easy commissioning ..........................35 8. Troubleshooting ............................38 9. Maintenance ..............................39 10. Spare parts ..............................41 11. Dimensions and weight ..........................42 11.1.
  • Page 4: Introduction

    Do not attempt to work on a powered APCQ capacitor bank. After switching off the power supply to the APCQ capacitor bank, always wait at least 5 minutes before working on the unit (i.e. time for the power capacitors to be discharged). Always verify by measurement that capacitors are dis- charged.
  • Page 5: Upon Reception

    Figure As an option, APCQ-M and APCQ-R can also be delivered in wood crates / sea worthy packing as per Figure 4. Immediately after reception, please inspect the delivery and make sure that the packing is in good conditions. Report immediately to your HITACHI ENERGY representative any damages.
  • Page 6: Identification Tag

    Figure 2: Lifting lugs 3.2. Identification tag The APCQ capacitor bank nameplate is located on the front door, at the outside. A second similar nameplate is pre- sent inside the cubicle. The nameplate information should always remain readable to ensure proper identification during the whole life of the APCQ capacitor bank.
  • Page 7: Packing & Unpacking

    AP CQ CAPA CITO R BA NKS 3.4. Packing & unpacking By default, APCQ-L, APCQ-M and APCQ-R capacitor banks are delivered in carton box (standard packing, as per Figure 3 here below). Optionally, wood crates and seaworthy can be used as per Figure 4 here below.
  • Page 8 – Remove carefully the wall of the crate – Remove the seaworthy plastic bag (if existing) – Remove fixation screws in the pallet (if existing) Similarly, any damage on the packing or material must be immediately reported to your Hitachi Energy representative. STATUS SECURITY LEVEL DOCUMENT ID REV.
  • Page 9: Products Overview And Description

    – APCQ-L: wall-mounted cubicles without reactor, – APCQ-M: free floor-standing cubicles without reactor, – APCQ-R: free floor-standing cubicles with reactors. All APCQ capacitor banks are available in master execution only, equipped by default with a RVC controller (RVT as an option). 4.2. APCQ capacitor layouts...
  • Page 10: Apcq Capacitor Banks Internal Layout

    AP CQ CAPA CITO R BA NKS 4.3. APCQ capacitor banks internal layout Number APCQ-L Description Fan (air outlet) Auxiliary transformer Auxiliary connections (current transducer) Power Factor Controller (RVC by default or RVT as an option) UA contactors Busbar point of connection (3-Phase)
  • Page 11 Main busbar (3-Phase) for bottom (by default) or top cable connections QCap Power Module Circuit breaker (optional) HRC fuses Protection plexiglasses covering copper bars STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 11/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 12: Power Factor Controllers

    AP CQ CAPA CITO R BA NKS Figure 7: APCQ-M & APCQ-R internal layout 4.4. Power Factor Controllers – RVC controller (by default if V ≤ 440V), – RVT (optional if V ≤ 440V, otherwise provided by default). Note: the Quick Start manual of the power factor controller is provided within the capacitor bank.
  • Page 13: Power Module

    AP CQ CAPA CITO R BA NKS 4.5. Power module Power modules are all-in-one pre-wired modules, which include capacitor, contactor, fuses, discharge resistors and reactor (for APCQ-R). The protection plexiglasses are present by default inside all APCQ cabinets. Capacitor Plexiglass...
  • Page 14: Thermal Cutoff Switch

    AP CQ CAPA CITO R BA NKS Important note: auxiliary power supply is included by default in the APCQ capacitor bank, there is no need to provide an external power supply. 4.6. Thermal cutoff switch Each APCQ capacitor bank cubicle includes a temperature-sensitive switch that trips the controller power supply (hence RVC/RVT controller will be off) in case of over temperature above 60°C (or 140°F) inside the enclosure.
  • Page 15 AP CQ CAPA CITO R BA NKS Figure 13: Location of thermal cutoff switch in APCQ-M and APCQ-R IP23 layout Figure 14: Location of thermal cutoff switch in IP54 layout STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public...
  • Page 16: Installation

    5.1. Working conditions: dust, moisture and temperature The APCQ capacitor banks are for indoor installation only. Protect your APCQ capacitor banks against dust and mois- ture and place it in a well-ventilated area where the ambient temperature doesn’t exceed the following values: –...
  • Page 17: Apcq-M And Apcq-R Capacitor Banks

    5.4. Electrical installation 5.4.1. Dielectric test All APCQ capacitor banks are fully factory tested including a dielectric test between power terminals and earth (2500V 50Hz 10s). If additional dielectric test is required on site, the following procedure should be followed: –...
  • Page 18: Earth Connection

    AP CQ CAPA CITO R BA NKS 5.4.3. Earth connection – APCQ-L capacitor bank earth connection: one M6 stud located inside the bank plate next to the lower left corner. Figure 17: Earth connection in APCQ-L – APCQ-M and APCQ-R capacitor bank earth connections: two M8 screws located on an earthing bar (either lo- cated on top or bottom according to top or bottom cable entry).
  • Page 19: Power Cables Selection

    To disconnect the unit from the network, HITACHI ENERGY suggests preferably a circuit breaker. A 3-phase discon- necting fuse or a 3-phase switch with fuses may nevertheless be used. The circuit breaker should be chosen with a nominal current rating of minimum 1.5 times the rating of the APCQ ca- pacitor bank.
  • Page 20: Apcq-M And Apcq-R Electrical Connections - Bottom Entry

    Figure 21: APCQ-L power cables connection to busbars – Connect CT cables. Figure 22: APCQ-L CT connection 5.4.6. APCQ-M and APCQ-R electrical connections – Bottom entry The APCQ-M and APCQ-R cubicles are bottom cable entry by default. STATUS SECURITY LEVEL DOCUMENT ID REV.
  • Page 21: Auxiliary Power Supply

    Figure 24: APCQ-M and APCQ-R CT connection 5.4.7. Auxiliary power supply Each APCQ cubicle is provided with its own and built-in auxiliary power supply connection (230V 50Hz). Then there is no need to provide external auxiliary power supply. 5.4.8. Current transformer selection Current transformer (CT) has to be provided locally (not provided with APCQ capacitor bank).
  • Page 22: Current Transformer Connection

    – Primary side current rating should be sufficient to monitor the total line current (including transient phenomena such as drive/motor starts). The APCQ capacitor bank is provided with HITACHI ENERGY RVC/RVT controller with automatic adaptation to net- work phase-rotation. Maximum rms current of the...
  • Page 23: Multi Ratio Ct And Summation Transformer

    For more complex situation (i.e.: two or more power source connections) the current has to be measured in different points in order the APCQ capacitor bank receives correct measurement in any circumstances. Then, when several CT’s are requested, one or several summing transformer should to be used.
  • Page 24: Connection Of Several Banks In Parallel

    Several APCQ capacitor banks can be connected in parallel. All APCQ capacitor banks are master units (i.e. fitted with a RVC or RVT controller) for better availability. If two units or more are connected, they must be connected as per...
  • Page 25: Options

    RVT must be ordered if communication and remote control are required. Please refer to RVT manual for exhaustive information. 6.2. APCQ-M and APCQ-R electrical connections – Top entry (optional) A top entry is possible and can be ordered as an option.
  • Page 26 AP CQ CAPA CITO R BA NKS Figure 30: Optional circuit breaker connection – APCQ-M and APCQ-R, top or bottom entry Figure 31: Connection with circuit breaker – APCQ-L STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 26/47 ©...
  • Page 27: Cable Entry Cubicle

    The cable entry cubicle can be used with one or up to four APCQ cubicle(s). It can be located left or right of the APCQ cubicle and by default, it is located in the middle of the APCQ cabinets as per...
  • Page 28: Seismic Design

    – Place the seal between the cubicles, place the cubicles side by side, assemble the 8 pins and interconnect them mechanically with the 4 brackets as per Figure Figure 34: Interconnection of cubicles 6.6. Seismic design HITACHI ENERGY can provide a type tested seismic design as per: – IEC 60068-2-57: 2013 – IEEE 693:2005. STATUS SECURITY LEVEL DOCUMENT ID REV.
  • Page 29: Ip54 Design

    Air inlet and outlet are both located in the front door: air inlet in the bottom, air outlet in the top. Figure 35: IP54 design Figure 36: Location of thermal cutoff switch in IP54 layout STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 29/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 30: Wooden Crates And Seaworthy Packing

    Different size of crates are used for one, two, three and four cabinets. Below picture show an example of crates for two cabinets. Figure 37 Wooden crate with seaworthy packing for 2 APCQ-R/M cabinets Seaworthy packing dimensions and weight with APCQ cabinets Crate for one cabinet Aprox 1200x800x2400 mm (WxDxH) –...
  • Page 31: Optional Ip20 Internal Grid For Apcq-M And Apcq-R

    6.10. Optional base frame (200 mm) and flanges (base frame covers) The APCQ-M/R cabinets are delivered by default with 100 mm plots in the bottom and flanges. It is possible to order a double-plots execution (200 mm high base) as per below picture.
  • Page 32: Optional Space Heater

    This option is made of one heater and its fan, which are located bottom or center of the cabinet (as per below picture) and one thermostat, located top of the cabinet. Figure 40 Space heater STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 32/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 33: Optional Internal Lamp

    The lamp can be switched on / off manually with a switch located to the right lateral side Figure 41 Internal lamp 6.13. APCQ from 350 to 550 kvar (master + slave with one connexion point) Such optional design is made of one master + one slave cabinet, with one single point of connection in the master cabinet.
  • Page 34: Apcq For 600 And 900 Kvar (Master + Slaves)

    AP CQ CAPA CITO R BA NKS 6.14. APCQ for 600 and 900 kvar (master + slaves) We can provide Master – Slave configuration for larger rating. In such case, each cabinets (master + slave(s) are delivered separately and must be assembled on site.
  • Page 35: Easy Commissioning

    Check that the CT(’s) is (are) properly installed (closed loop) and connected. Remove the CT short circuit. Note: If your APCQ capacitor bank is equipped with an optional RVT, refer to RVT instruction manual and don’t follow the points below.
  • Page 36 Figure 47: View of programmable parameters Then, select: Feature 1 (linear / circular) and Feature 2 (generative / regenerative target cos ϕ). STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 36/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 37 Note: a negative cos ϕ indicates that the load is re-injecting reactive power on the network. The RVC continues to work normally. For RVT, please refer to RVT manual provided within the capacitor bank. STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 37/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 38: Troubleshooting

    AP CQ CAPA CITO R BA NKS 8. Troubleshooting Most of the APCQ capacitor bank operating issues may be identified with the help of error messages or icons display on the RVC/RVT controller. Refer to the troubleshooting paragraph of the RVC/RVT controller instruction manual.
  • Page 39: Maintenance

    Especially, it may help a lot for preventive maintenance and guarantee a long lifetime of the equipment. The interval between two maintenances will depend on working conditions but should not be longer than one year. STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 39/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 40 Regular maintenance procedure OK/NOK − Check ambient temperature and equipment ventilation (should be within specification). − Isolate the APCQ capacitor bank from power supplies. − Open the front door panel. − Clear air inlet and outlet. − Clean all parts from dust and dirt.
  • Page 41: Spare Parts

    10. Spare parts HITACHI ENERGY recommend to have a stock of spare parts for fast maintenance and repair. The Parts that HITACHI ENERGY recommends to have on site are (for one single APCQ cabinet): – One controller – Two fans (which have to be replaced every 4 to 5 years) –...
  • Page 42: Dimensions And Weight

    2185 Max 550 kg Cable entry cubicle 2165 410/610 Max 180 kg APCQ-L APCQ-M & APCQ-R Figure 50: APCQ IP23 dimensions STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 42/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 43: Ip54 Standard Design

    Max 30 kg APCQ-M 2165 Max 260 kg APCQ-R 2165 Max 550 kg Cable entry cubicle 2165 410/610 Max 180/200 kg STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 43/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 44 AP CQ CAPA CITO R BA NKS APCQ-L APCQ-M & APCQ-R Figure 51: APCQ IP54 dimensions STATUS SECURITY LEVEL DOCUMENT ID REV. LANG. PAGE Approved Public 9AKK107680A4136 44/47 © 2022 Hitachi Energy. All rights reserved.
  • Page 45: Technical Specifications

    Clearance lateral: not necessary - top and bottom: 200 mm − − APCQ-M and APCQ-R cubicles: free floor standing, bottom cable entry (top ca- ble entry optional) − Clearance lateral & back: 50 mm (but no clearance required between two...
  • Page 46 Flange (base frame cover) Top cable entry cubicle for APCQ-M/R Cable entry cubicle for APCQ-M/R (one entry cubicle for up to 4 APCQ cabinets) Seismic design Voltage presence lamp(s) and other indication lamps in the front door (as per cus-...
  • Page 47 We reserve all rights in this document and in the subject matter and illustrations con- E-Mail: tained therein. Any reproduction, disclosure to third parties or utilization of its contents Marketing: power.quality@hitachienergy.com – in whole or in parts – is forbidden without prior written consent of Hitachi Energy Ltd. Service: service.jumet@hitachienergy.com Visit us at hitachienergy.com/power-capacitors ©Hitachi Energy 2022.