Installation Instructions Mini Split Air Conditioning or Heat Pump Systems Air Conditioning S115A-10K10 S115A-13K10 S240A-13K11 Heat Pump S115HP-10K10 S115HP-13K10 S240HP-13K11 950-0004 Rev 7, 28 October 2005...
Unit Parts & Features Indoor Unit Air in Panel Air filter Cover panel Wiring cover Cover plate of electric box Air out Louver Cooling indicator Remote control Heating On/Off indicator indicator SWING AUTOFAN OPER AUTO SWING HUMID LIGHT SAVE TIMER ON/OFF MODE ON OFF...
Installation Dimension Diagram Distance to ceiling should be 6 inches or more see spec Right-positioned piping hole sheet Left-positioned piping hole Distance to wall should be 6 inches or more Distance to wall see spec should be 6 sheet Piping-hole sleeve inches or more Distance to floor Wrapping tape...
• Certified power supply conductors must be used. INSTALLATION KITS Installation kits are available for all NCP Mini-Split systems. These kits contain a 20’ line set appropriate for each model, connecting wires, PVC tape, drainage hose, and wall sleeve(s). Contact your local dealer for availability.
Select Installation Locations Indoor Unit: • The air intake and outlet should not be obstructed. • The wall the unit is mounted on should allow for a clear hole for the condensation drain line and the refrigeration lines. • The wall the unit is mounted on should be strong enough to bear the weight and vibration of the unit.
Page 8
Indoor Unit Installation 1. Install the Rear Panel (mounting plate) • Always mount rear panel horizontally. • Hold the rear panel on the wall where you want the unit to be located and ensure that it is level using a plumb line or level. Once leveled, mark the screw locations on the wall. •...
Indoor Unit Installation (cont.) 115 VAC Air Conditioner Wiring 115 V Heat Pump Wiring 3 way terminal board 5 way terminal board (Indoor Unit) (Indoor Unit) N(1) See Wire See Wire Table Table (para 4) (para 4) for wire for wire sizes sizes N(1)
Indoor Unit Installation (cont.) 6. Hang Indoor Unit • Bundle the refrigeration lines, drainage hose, and wiring conduit attached to the indoor unit and Wrapping tape wrap them securely for enough length to extend through the piping hole to the exterior of the Connection pipes building.
Page 11
Outdoor Unit Installation (cont.) 3. Position Outdoor Unit • Review page 5 - “Select Installation Location” for “Outdoor Unit” and for “Both Indoor and Outdoor Units”. • Make sure unit is positioned solidly and leveled on its foundation. Use leveling feet if necessary.
Testing 1. Notes: • Installation MUST be complete prior to testing. • System MUST be tested prior to operation. 2. Leakage Test • Use standard A/C practices to properly check refrigeration tubes and connections for any leaks prior to system start up. 3.
If the unit exhibits a defect in normal use and is determined to be within the warranty period, NCP will, at its option, either repair or replace the unit free of charge within a reasonable time after the unit is returned.
Page 14
Specifications S115A-10K10 S115HP10K10 SYSTEM MODEL NUMBER Air Conditioning Only Heat Pump Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Catalog Number Catalog Number Catalog Number Catalog Number S115A-10K10-O S115A-10K10-I S115AHP10K10-O S115HP-10K10-I COMPONENT MODEL NUMBER 9,500 BTU 9,500 BTU Cooling Capacity...
Page 15
Specifications S240A-13K11 SYSTEM MODEL NUMBER S240HP-13K11 Air Conditioning Only Heat Pump Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Catalog Number Catalog Number Catalog Number Catalog Number S240A-13K11-O S240A-13K11-I S240AHP13K11-O S240HP-13K11-I COMPONENT MODEL NUMBER 12,500 BTU 12,500 BTU Cooling Capacity 13,000 BTU Heating Capacity Seer Rating...
Page 16
Specifications S115A-13K10 S115HP-13K10 SYSTEM MODEL NUMBER Air Conditioning Only Heat Pump Outdoor Unit Indoor Unit Outdoor Unit Indoor Unit Catalog Number Catalog Number Catalog Number Catalog Number S115A-13K10-O S115A-13K10-I S115HP-13K10-O S115HP-13K10-I COMPONENT MODEL NUMBER 12,500 BTU 12,500 BTU Cooling Capacity 13,000 BTU Heating Capacity 10.5...