Kohler 15REYG Installation Manual page 43

Commercial generator sets
Hide thumbs Also See for 15REYG:
Table of Contents

Advertisement

Continued from Figure 5-6:
or
or
or
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to
the last saved settings when the master switch is moved to the OFF/RESET position.
There are 3 options when the display says SAVE:
Press:
To return to the first parameter, coarse voltage adjustment, to check
or change settings before saving. See Figure 5-6.
or
To save changes.
or
To discard changes without saving.
"Yes"or "no" flashes when the up or down arrow is pressed and then the
controller exits the configuration mode. The display returns to the
runtime hours.
Now move the master switch to OFF/RESET.
* X in the examples above denotes any number from 0 to 9. The actual values may vary from
model-to-model.
Figure 5-7 Output Voltage Adjustments, Continued
TP-6727 10/11
To enter coarse voltage stability (gain) adjustment mode.
To raise or lower the voltage stability (gain) in large
increments.
To enter fine voltage stability (gain) adjustment mode.
To raise or lower the voltage stability (gain) in smaller
increments.
To enter volts/Hz adjustment mode.
To raise or lower the volts/Hz: 00=low; 09= high
To enter SAVE mode.
Display : *
x x
2 P
x
x
2 P
x
3 P 0
S A V E
S A V E
x x
1 P
Y E S
n o
x x x x
Section 5 Controller
43