Quick Links

Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
Indoor Air Quality – VOC
(Volatile Organic Compounds)
The Air Quality Controller – VOC is specifically
designed to control a fan with a Vari-Green
The controller senses the level of Volatile Organic
Compounds (VOCs) in the space and automatically
adjusts the ventilation rate to the space by
increasing or decreasing the speed of the supply or
exhaust fan based on the level of VOCs.
Applications for this controller include bathrooms,
conference rooms, cafeterias, or any other space
where air quality is of concern. Ventilating based
on the VOC concentration assures that the space
will not be over or under ventilated while using the
Vari-Green motor technology to operate quietly and
efficiently.
The VOC controller has adjustments for air quality
setpoint, and minimum and maximum fan speed.
The fan speed and VOC level are available as
analog outputs to be read by a building automation
system or a secondary device.
General Safety Information
Only qualified personnel should install this product.
Personnel should have a clear understanding of
these instructions and should be aware of general
safety precautions. Improper installation can result
in electric shock, possible injury due to coming in
contact with moving parts, as well as other potential
hazards. Other considerations may be required
if high winds or seismic activity are present. If
more information is needed, contact a licensed
professional engineer before moving forward.
motor.
®
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Precaution should be taken in explosive
atmospheres.
PN 475407
Vari-Green
Indoor Air Quality–VOC
DANGER
CAUTION
CAUTION
Control
®
1

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck Vari-Green Air Quality VOC

  • Page 1 PN 475407 Vari-Green Control ® Indoor Air Quality–VOC Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information.
  • Page 2: Electrical Safety Information

    Inspection and Maintenance a claim with carrier. Any physical damage to the During Storage unit after acceptance is not the responsibility of Greenheck Fan Corporation. While in storage, inspect product once per month. Keep a record of inspection and maintenance Unpacking performed.
  • Page 3: Drywall Mounting

    The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and sensor failure. To prevent these conditions, Greenheck recommends sealing the conduit leading to the junction box, filling the junction box with...
  • Page 4 Wiring Minor Display All wiring for the Greenheck Air Quality Controller is 0.34 inch 3-digit Class II low-voltage control wiring. See the Wiring Alpha-Numeric Diagram on Page 7 for the wiring overview. Main Display 0.76 inch 4-digit Numeric Dot for Cutout Mode...
  • Page 5: Parameter Descriptions

    Programming (J19 = PRG) Parameter Description Default Setting The unit ships with factory default parameter Display setpoints. Parameter setpoints may be edited in the field by an HVAC technician. During parameter Air Quality Setpoint editing, the output voltage is set to zero. General Programming Factory Defaults...
  • Page 6 Fan Cutout, Parameter P3 Output State, Parameter P6 Factory Default = 0 Factory Default = 1 0 – Fan Cutout Disabled 0 – Manual Control 1 – Fan Cutout Enabled 1 – Normal Operation The Fan Cutout is designed to shut off the exhaust The Output State allows manual control of the Fan fan when the VOC level falls below the Air Quality Speed for system setup and commissioning tests.
  • Page 7: Wiring Diagram

    Wiring Diagram Troubleshooting Potential Solution Problem Fan always at minimum speed  Place an opened permanent or white board marker underneath the controller. The fan should increase speed within a few minutes. Fan always at high speed Check that the air quality measurement is decreasing. If there is a large ...
  • Page 8: Warranty

    Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year.