Lennox ELITE Series Installation Instructions Manual page 27

Table of Contents

Advertisement

FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
C
* WALL
SUPPORT
C
See venting table
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
Downloaded from
ManualsNet.com
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
SIZE TERMINATION
PER TABLE 6
D
B
STRAIGHT
APPPLICATION
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
D
E
B
A
EXTENDED
APPLICATION
5
for maximum venting lengths with this
2" (51mm)
3" (76mm)
Vent Pipe
12" (508MM)
12" (508MM)
6" (152MM)
8" (203MM)
12" (305MM)
20" (508MM)
6" (152MM)
FIGURE 30
search engine
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
See venting table
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
Vent Pipe
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
6" (152MM)
intake and exhaust
C−Minimum from
end of exhaust to
8" (203MM)
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
6" (152MM)
pipe (intake/exhaust)
Page 27
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
REDUCER MAY BE
1/2" (13mm) ARMAFLEX
TO TERMINATION
D
B
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
A
C
5
for maximum venting lengths with this
2" (51mm)
Vent Pipe
12" (508MM)
6" (152MM)
6" (152MM)
12" (305MM)
6" (152MM)
FIGURE 31
INSULATION IN UN-
CONDITIONED SPACE
SIZE TERMINATION
PER TABLE 6
STRAIGHT
APPPLICATION
D
B
EXTENDED
APPLICATION
3" (76mm)
Vent Pipe
12" (508MM)
6" (152MM)
6" (152MM)
20" (508MM)
6" (152MM)