Chromalox NWHO(F)-27 Installation And Renewal Parts Identification

Circulation heater (for regular and fuel oil heating)

Advertisement

Quick Links

Chromalox
RENEWAL PARTS IDENTIFICATION
Type NWHO(F)-27 Series Circulation Heater
Thermostat
(When Specified)
3 - 1-3/8" K.O.
for 1" Conduit
3" Pipe
Outlet (Std.)
2 Mtg. Lugs Ea
with Three 3/4" - 10
x1-1/8" Deep
Holes on 1-3/4"
Centers
3" Pipe
Inlet (Std.)
WARNING: This heater is not intended for use in haz-
ardous atmospheres where flammable vapors, gases,
liquids or other combustible atmospheres are present
as defined in the National Electrical Code. Failure to
comply can result in explosion or fire.
Hazardous area terminal enclosures are available, consult your
local Chromalox representative for details.
The NWHO-27 series is a general-purpose oil circulation heater
intended for use indoors.
The 27 or 36 steel sheathed tubular elements are welded to a remov-
able steel flange and centered in a 10 inch diameter steel heating chamber.
WARNING: Hazard of Shock. Disconnect all power
before installing heater.
1. Vertical mounting (axis of chamber vertical as in sketch above) is
preferred. (Terminal housing at top of heater) (Figure A)
2. When mounting heater horizontally, inlet and outlet MUST be up.
In any other position, heater cannot be purged of air and elements
may be seriously damaged. (Figure B)
3. This series of circulation heaters are provided with mounting lugs
to support the heater chamber. Refer to sketch above for location
of these mounting lugs.
4. Mount heaters to permit unrestrained expansion of chamber due to
temperature. This can be accomplished by using a slotted mount-
Correct
© 2010 Chromalox, Inc.
Installation
and
(for Regular and Fuel Oil Heating)
15-15/16"
A
C
B
A
A
11"
3/4" NPT
Pipe Plug
17-1/8"
Incorrect
Figure A — Vertical Mounting
®
DIVISION
SALES
REFERENCE
DATE
Specifications — Table A
Model
Volts
NWHO-2780R15
240 or 480
NWHO-2790R15
240 or 480
NWHO-27100R15
240 or 480
NWHO-27120R15
240 or 480
NWHO-2750R15
240 or 480
NWHO-2760R15
240 or 480
NWHO-2770R15
240 or 480
Dimensions and ratings vary according to customer requirements.
Check engineering drawing for specifications.
F-Denotes heater is baffled, i.e., NWH0F
GENERAL
Depending upon the specifications, the NWHO-27 may or may not be
factory equipped with AR or other Chromalox thermostats. Such ther-
mostats function to control outlet temperatures and limits internal tem-
perature under abnormal flow conditions. These controls do not fail-safe.
Thermocouples are also available as an option.
CAUTION: Users should install adequate back-up con-
trols and safety devices with their electric heating
equipment. Where the consequences of failure may be
severe, back-up controls are essential. Although the
safety of installation is the responsibility of the user,
Chromalox will be glad to make equipment recom-
mendations.
INSTALLATION
ing assembly on either of the lugs.
5. DANGER: Hazard of Fire. Provide minimum of 6" spacing
from a chamber and related piping to nearest combustible materi-
al. Avoid operation of heater near combustible fluids or in com-
bustible vapor or gas laden atmosphere.
6. Provide adequate space at terminal end to permit withdrawal of the
heater from chamber should servicing be required.
7. If two or more heaters are needed to provide the needed heating
capacity, arrange them for series oil flow.
8. DANGER: Possible Explosion. A pressure relief valve
should be provided by customer at outlet of vessel. There should
be no other valving between vessel and valve.
SERVICE REFERENCE
4
SECTION
(Supersedes PE437)
161-303184-001
APRIL, 1999
Regular Oil Heaters
Phase
kW
W/In
2
3
80
20
77-9/16
3
90
20
81-9/16
3
100
20
87-9/16
3
120
20
97-9/16
Fuel Oil Heaters
3
50
12
77-9/16
3
60
12
87-9/16
3
70
12
97-9/16
Correct
Incorrect
Figure B — Horizontal Mounting
NWHO
PE437-1
Dimensions (In.)
A
B
C
52
48-1/2
56
52-1/2
62
58-1/2
72
68-1/2
52
48-1/2
62
58-1/2
72
68-1/2

Advertisement

loading

Summary of Contents for Chromalox NWHO(F)-27

  • Page 1 Check engineering drawing for specifications. F-Denotes heater is baffled, i.e., NWH0F GENERAL factory equipped with AR or other Chromalox thermostats. Such ther- mostats function to control outlet temperatures and limits internal tem- perature under abnormal flow conditions. These controls do not fail-safe.
  • Page 2 2. Periodically check temperature control and pressure temperature Order Renewal Parts on a Special Order Basis. Give the name of the part number, voltage, and wattage to your Chromalox Representative for identification of renewal parts.

This manual is also suitable for:

Nwho-2780r15Nwho-2790r15Nwho-27100r15Nwho-27120r15Nwho-2750r15Nwho-2760r15 ... Show all