Remember to disable the outputs, as a full functional test includes activating the ALARM outputs. A
Honeywell Analytics Test Lamp must be used for this test (Section 4.4). Point the Test Lamp directly at the
front of the Detector (on axis as much as possible, within a distance of about 1 to 25 feet). Activate the Test
Lamp by pressing and holding its pushbutton. While watching the red ALARM LED on the face of the
Detector, slowly move the Test Lamp's boresight to ensure the Detector receives its full intensity. (NOTE:
Practicing this technique may help to optimize testing of the FSX Detectors). (Sections 3.6 and 4.4).
The Detector's red ALARM LED will illuminate, usually within three (3) to ten (10) seconds. Also, the ALARM
Relay outputs will activate and the 4-20 mA analog output will change to 20 mA (±0.6 mA).
If the Detector fails to respond within ten (10) seconds, do the following:
1. Wait ten (10) to twenty (20) seconds before performing another test.
2. Check the Distance: verify that the testing distance is between one (1) and twenty-five (25) feet
from the FSX Detector(s).
3. Check Aiming Accuracy: verify that the proper testing technique (as described above) is followed.