12.2 Outdoor Unit

12.2.1
Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the [piping length for additional gas], additional refrigerant should be added as shown in
the table.
Table A
Horse
Piping size
Model
Power
(HP)
Gas Liquid
9.52
Z25****
1.0HP
mm
) 6.35
Z35****
1.5HP
"
(3/8
mm
12.7
Z50****
2.0HP
"
(1/4
)
mm
Z60****
2.25HP
"
(1/2
)
(*) Systems with total refrigerant charge, m
Example: For Z25****
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m × 10 g/m =
25 g.
A
= (m
/ (2.5 × (LFL)
min
c
A
= Required minimum room area, in m
min
m
= Refrigerant charge in appliance, in kg
c
LFL
= Lower flammability limit (0.307 kg/m
h
= Installation height of the appliance : (2.2m for mini cassette & ducted)
0
SF
= Safety factor with a value of 0.75
** The required minimum room area, A
A
= m
/ (SF × LFL × h
min
c
The higher value shall be taken when determining the room area.
Min.
Max.
Std.
Max
Length
Elevation
Piping
Piping
Length
Length
A
B
(m)
(m)
(m)
(m)
15
3
20
15
3
20
5
20
3
30
20
3
30
, lower than 1.84kg are not subjected to any room area requirements.
c
(5/4)
2
× h
))
0
2
3
)
(0.6m for floor console)
, shall also be governed by the safety factor margin formula below :
min
)
0
It is advisable to avoid more
than 2 blockage directions.
For better ventilation &
multiple-outdoor installation,
please consult authorized
dealer/specialist.
This illustration is for explanation purposes only.
Piping
Max.
Additional
Length for
Refrigerant
Refrigerant
add. gas
Charge
(g/m)
(m)
(kg)
10
7.5
1.05
10
7.5
1.10
15
7.5
1.44
15
7.5
1.51
** not less than safety factor margin
Power supply cable ( )
Connection cable ( )
1/4" Liquid side piping ( )
Gas side piping ( )
Additional drain hose ( )
Installation parts you
should purchase ( )
57
Indoor A
for
Indoor A
for
min
min
mini cassette
ducted
2
2
(m
)
(m
)
Not applicable (*) Not applicable (*) Not applicable (*)
Not applicable (*) Not applicable (*) Not applicable (*)
Not applicable (*) Not applicable (*) Not applicable (*)
Not applicable (*) Not applicable (*)
Indoor A
for
min
floor console
2
(m
)
–––