Venting Requirements; Typical Vent Installation - Napoleon Ascent 30 B30NTR-1 Installation And Operation Manual

Table of Contents

Advertisement

Available languages

Available languages

horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0" rise per foot or 0mm rise per meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4" rise per foot or 21mm rise per meter using fl exible venting. For safe and proper

venting requirements

operation of the appliance, follow the venting instructions exactly.
EN
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" (31.8mm) air gap
all around between the inner liner and outer liner is required for safe operation.
This appliance is certified for use with a power vent kit. Contact your local authorized dealer for more
If approved for use with a power vent kit, state: "This appliance is certifi ed for use with a
information.
power vent kit. Contact your local authorized dealer for more information."
If not, cover with a white box.
2.1

typical vent installation

8" (203mm)
minimum
10
W415-1768 / B / 08.10.18
24" (61cm)
maximum
TOP VENT
7.1D
16" (40.6cm)
minimum
40ft (12m)
Maximum
3ft (1m)
minimum
34 5/8"
(86cm)