Installation; Selection Of The Best Location - LG MULTI V ARNU073B3G4 Installation Manual

Hide thumbs Also See for MULTI V ARNU073B3G4:
Table of Contents

Advertisement

Installation

Installation

Selection of the best location

Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or service
under the product.
Chassis
A
B3
600(23-5/8)
B4
600(23-5/8)
B(Min)
A(Min)
Service Space
8
8
Indoor Unit
Indoor Unit
[Unit: mm(inch)]
B
900(35-7/16)
1100(43-5/16)
Ceiling
A
B
Top view
[Unit: mm(inch)]
Inspection hole
(600(23-5/8) x 600(23-5/8))
Control box
600
(23-5/8)
[Unit: mm(inch)]
• Refer to Suction grille and Suction canvas installation
manual for detail installation of Built-in duct type
Built-in Duct type
Airflow
600
(23-5/8)

Advertisement

Table of Contents
loading