The GEMC 7-Ampere NAC Extender includes 2 models: The GEMC-NAC7L (used with the large enclosure) and GEMC-
NAC7S (used with the small enclosure).
Notification Appliance Circuits (NAC's)
A Notification Appliance Circuit is a circuit or path directly connected to a notification appliance, i.e. any audible, tactile or
visual signal--or any combination thereof--employed to indicate a fire, supervisory or trouble condition.
The Gemini C-Series control panels comply with National Fire Protection Association (NFPA) requirements for temporal
pulse sounding of fire notification appliances. Use only the specified UL Listed notification appliances. Note: For IN-
DOOR / DRY LOCATION USE ONLY.
OVERVIEW
The GEMC-NAC7S or GEMC-NAC7L (referred to as "GEMC-NACXX" throughout this manual) can be used as either:
• A UL864 9
th
edition accessory to a Gemini C-Series Combination Fire & Burglary Alarm control panel
--or--
• A UL864 9
th
edition NAC Extender for use with any listed Fire Alarm Control Panel (FACP)
The dual nature of the GEMC-NACXX requires this manual be divided into two individual sections: When the GEMC-
NACXX is used with the Gemini C-Series control panels, proceed to the next section named "GEMINI C-SERIES OP-
ERATION" directly below. When used with a listed Fire Alarm Control Panel as a stand-alone NAC Extender, stop here
and turn to page 21.
GEMINI C-SERIES OPERATION
INTRODUCTION
When used with a Gemini C-Series control panel, the
GEMC-NACXX functions as if it were two separate mod-
ules, an External Output ("Fire NAC Extender" board)
with 7 of the 8 outputs utilized (the first 4 supervised) and
a 4-Zone EZM (Expansion Zone Module) used to send
the status of a device (AC ON/OFF, BATTERY GOOD/
TBL, GROUND FAULT and TAMPER) to the C-Series
control panel.
The GEMC-NACXX is wired to the 4-wire fire bus of the
C-Series control panel, and provides:
• 4-Supervised Outputs suitable as 24V, maximum 2A
each, combined 6.5A maximum regulated Notification
Appliance Circuits. These outputs can be configured
as:
• 4 Class B or
• 1 Class A and 2 Class B or
• 2 Class A
• 3-Unsupervised Form-C Dry relay outputs activated by
a programmed event generated by the Gemini C-Series
control panel (the 8th output is not used)
• One supervised, isolated GEMC-Remote Bus interface
• One normally-closed (N/C) housing tamper input, identi-
fied by trouble on dedicated integral EZM zone
• Isolated integral ground-fault detection circuit (detects
Gemini C-Series GEMC-NAC Extender Installation Instructions
GEMC-NAC7L / GEMC-NAC7S
SUPERVISED NAC EXTENDER
INSTALLATION INSTRUCTIONS
1.25KΩ to ground or less)
• One isolated input (terminals 1-2) to synchronize
"Smart" outputs (Listed Wheelock or System Sensor
horns/strobes) with other outputs from the C-Series
motherboard or other GEMC-NACXX devices
● Power supply contains integral battery charger capable
of charging up to 4 pairs of 7AH / 7.5AH / 8AH sealed
lead acid or gel type 12V batteries. Note: All batteries
must be of the same AH rating.
● The system monitors for low battery, no battery, brown-
out and monitors battery charging circuit voltage, identi-
fied by battery trouble on dedicated integral EZM zone
• Remote bus interface and two Inputs are isolated, thus
allowing for separate ground fault detection and annun-
ciation
● Allows audible notification appliances (horns) to be si-
lenced while visual notification appliances (strobes)
continue to operate
● Input allows synchronized Wheelock/System Sensor
operation between the motherboard or other C-Series
NAC circuits, allowing for multiple NAC circuits to be
used within the same area
● Each of the 4 NAC circuits are individually supervised
for opens or shorts, and will annunciate and report
separately
● Solid State over-current protection on the four NAC's
WI1821 08/10
1

Advertisement

loading

Summary of Contents for NAPCO GEMC-NAC7L

  • Page 1 Symbol: NSSC © NAPCO 2010 WI1821 08/10 The GEMC 7-Ampere NAC Extender includes 2 models: The GEMC-NAC7L (used with the large enclosure) and GEMC- NAC7S (used with the small enclosure). Notification Appliance Circuits (NAC's) A Notification Appliance Circuit is a circuit or path directly connected to a notification appliance, i.e. any audible, tactile or visual signal--or any combination thereof--employed to indicate a fire, supervisory or trouble condition.
  • Page 2 Each NAC circuit output rated @ 2A maxi- GEMC-HSKIT1416, size 14.25" x 16" x 5.25") mum. • The GEMC-NAC7L uses the large housing with room Optional Auxiliary Output Power: 2A maximum per cir- for four pairs of 12V standby batteries (model GEMC- cuit in alarm;...
  • Page 3 Coded Alarms / Cadences by Zone An initiating zone can be individually programmed, using PCD-Windows Quickloader, to activate one of thirty available coded alarms/cadences on NAC circuits. This feature is primarily used to assist in the identification of a particular area of a large facility, such as a hospital, where a certain section of the hospital will sound a particular code during an alarm to allow people to select the correct egress method or path.
  • Page 4: Installation

    Series control panel. See page 8 for more information. JUMPERS When used with a Gemini C-Series control panel, the INSTALLATION jumpers on the GEMC-NACXX circuit board are used as follows: The GEMC-NACXX must be installed in accordance with NFPA 72 and with article 760 of The National Electrical NAC OPTIONS: Only jumper 4 "Offset"...
  • Page 5 in the gang box to the 3-wire terminals located on the when in an "active" alarm condition, polarity is reversed power supply PC board. from what is shown in "normal" standby mode). These terminals are supervised outputs that provide low imped- ance output to drive devices such as strobes, bells and Maintenance The GEMC-NACXX should be tested at least once a year...
  • Page 6 the ground fault circuit; a short from this terminal to any etc), see the section "NAC SYNCHRONIZATION NAC circuit terminal should cause a ground fault, causing RULES" further in this manual. the ground fault LED to light and the keypad to display a Fire trouble ground fault with the associated zone.
  • Page 7 WIRING PROGRAMMING FOR CLASS A Notification Appliance Circuit Supervision Install a 2.2K end-of-line (EOL) resistor across the last The External Output Assignment screen provides the notification appliance on each Notification Appliance Cir- ability to select Class A operation for NAC 1 / NAC 2 cuit to be supervised.
  • Page 8 INTEGRAL EZM ADDRESS JUMPERS Quickloader Zone Assignments The integral EZM Address must be selected for a valid address for In the Quickloader, select the EZM type in the System Assign- the 4 system troubles to be sent back to the panel to be annunciated/ ment screen, click the EZM Assignments tab and select the Type reported.
  • Page 9 WIRING DIAGRAMS FOR SINGLE AND MULTIPLE NAC EXTENDERS Single NAC Extender (Unsynchronized) Single NAC Extender (Synchronized) 4-WIRE FIRE BUS NAC A (or B-D) 4-WIRE FIRE BUS (–) (–) (–) EOLR 2.2K (–) (–) INPUT INPUT (–) INPUT 1 Multiple NAC Extenders (Unsynchronized) Multiple NAC Extenders (Synchronized) 4-WIRE FIRE BUS NAC A (or B-D)
  • Page 10 set using S2 for a total of 2.5A]. NAC SYNCHRONIZATION RULES The UL 864 9 edition standard includes the requirement Rule 3: All notification appliances in the same field of that all visible notification appliances in the same field of view must use the same sync pattern.
  • Page 11 NAC A - Sync S1 0 Amps NO DEVICES NAC A - Sync S1 - 2 Amps NAC B - Sync S1 - 2 Amps GEMC- NAC B - Sync S1 - 2 Amps XXXMB GEMC- NAC C - Sync S1 - 2 Amps XXXMB NAC C - Sync S2 - 1.25 Amps NAC D - Sync S2 - 2 Amps...
  • Page 12 zones are restored, will reinitiate the cadence alarm. by zone in place of the standard temporal audible alarm. This method is requested for schools and other institu- The strobes will continue until the RESET button is pressed and all fire alarms are restored. tions that would like to identify the device or zone that initiated the alarm to determine the proper egress route Method 2 (Non-standard Cadence)
  • Page 13 OVER-CURRENT PROTECTION GEMC-XXXMB AND GEMC-NACXX GEMC-NACXX NAC Over-Current protection when con- nected to a Gemini C-Series Control Panel When the NAC is active (turned on), it will detect a cur- rent above 6A and turn off the output within 100mS. The output will remain off until either: a.
  • Page 14 GEMC-NAC7S) ; the larger enclosure diagrams are similar, except the larger enclosure (model includes an additional battery shelf and tamper GEMC-NAC7L) switches. 1. ROUTE CONTINUOUSLY POWERED 120VAC If not already installed, mount a separate electrical gang box (single or double gang) located no closer than 6 inches and...
  • Page 15 MOUNTING AND INSTALLATION (CONT'D) 3. INSTALL THE GEMC-PS24V7A POWER SUPPLY BOARD For more information, see the individual installation instructions provided with each power supply: GEMC-PS24V7A: WI1646 EXPLODED VIEW OF POWER SUPPLY BOARD. SEE TABLE BELOW FOR NUMBER DESCRIPTIONS and MUST be installed. Note: To ensure all hardware and component mounting holes are suitably aligned, loosen and re-tighten all pre- 2.
  • Page 16 MOUNTING AND INSTALLATION (CONT'D) 4. INSTALL THE POWER SUPPLY SHIELDS Power Supply Shields and Other Hardware IMPORTANT: In the steps that follow, always ensure all exposed metal surfaces are bonded to earth ground. NOTCH 1. Secure the HW1788 Right Side Plate (item 4) and the HW1789 Left Side Plate (item 5) to the enclo- sure base with the 6-32 nuts (item 2).
  • Page 17 MOUNTING AND INSTALLATION (CONT'D) 5. ROUTING THE GEMC-120VACH HARNESS FROM THE GANG BOX INTO THE CONTROL PANEL EN- CLOSURE & POWER SUPPLY BOARD At this point, both the control panel and electrical gang box are mounted, and the electrical gang box contains 3 wires that provide a continuously-powered (un-switched) 120VAC source from a maximum 15A dedicated branch circuit and a grounding conductor.
  • Page 18 MOUNTING AND INSTALLATION (CONT'D) 6. PREPARING THE GEMC-NACXX PC BOARD A small folded fishpaper must be installed over the power NACXX PC board. terminals to electrically isolate the terminals and serve as 3. Insert the two HW1829 Mounting Buttons into the two an electrical barrier to ensure against accidental contact mounting holes.
  • Page 19 MOUNTING AND INSTALLATION (CONT'D) 7. INSTALLING THE GEMC-NACXX PC BOARD Note: Some items are pre-installed at the fac- tory. To ensure all hardware and component mounting holes are suitably aligned, loosen and re-tighten all pre-installed fasteners as needed. 1. Install and secure the HW1490 Support Bar to the GEMC-NACXX PC board.
  • Page 20 MOUNTING AND INSTALLATION (CONT'D) 8. INSTALL THE BATTERY SHELVES If not already installed at the factory, install the HW1489 shelves for the batteries with the 6-32 nuts (N101). ASSEMBLED VIEW SEE TABLE BELOW FOR NUMBER DESCRIPTIONS BATTERY SHELF (HW1489) INSTALLATION SEE TABLE BELOW FOR NUMBER DESCRIPTIONS Item No.
  • Page 21: Specifications

    FIRE ALARM CONTROL PANEL (FACP) OPERATION ● Each of the 4 NAC circuits are individually supervised INTRODUCTION for opens or shorts, and will annunciate and report When additional notification appliances are required, the separately GEMC-NACXX supervised 7 ampere voltage-regulated ● Each of the 4 NAC circuits can be disabled/enabled NAC (Notification Appliance Circuit) Extender and relay separately at the GEMC-FK1 Fire keypad.
  • Page 22 (model GEMC-HSKIT1416, size 14.25" x 16" x 5.25") NAC's 3 and 4 from NAC's 1 and 2 by .5 seconds to al- • The GEMC-NAC7L uses the large housing with room low instantaneous current for the synchronized devices. for four pairs of 12V standby batteries (model GEMC- However, note that when shunted, the strobes and HSKIT1425, size 14.25"...
  • Page 23 INSTALLATION Fuse Battery fuse is a UL Listed fuse rated 250VAC / 12.5A. If The GEMC-NACXX must be installed in accordance this fuse is blown, a battery trouble will be enunciated with NFPA 72 and with article 760 of The National Elec- (refer to LED Diagnostic Table).
  • Page 24 AC Fail relay output (Fig. 2) to the common trouble in- 19. (+) REM (FIRE BUS) put. 20. (–) PWR (FIRE BUS) 21. GREEN (FIRE BUS) 22. YELLOW (FIRE BUS) Isolated 4-wire bus terminals wired from the Gemini C- OVER-CURRENT PROTECTION Series control panel terminals 18-22 GEMC-XXXMB AND GEMC-NACXX 23.
  • Page 25 "NAC OPTION" JUMPER OPTIONS The "NAC OPTION" jumpers described in the table below are only used when the "NAC ADDR" jumper is set to 0 ("zero" no shunt connectors across any of the jumpers). When the "NAC ADDR" jumper is set to 0 ("zero"), the AUX relays are dedi- cated to the following tasks: •...
  • Page 26 WIRING DIAGRAMS FOR SINGLE AND MULTIPLE NAC EXTENDERS S i n g l e N AC E x t e n d e r OUTPUT OUTPUT "X" "X" "X" "X" AC TBL BATT TBL (–) (–) INPUT INPUT POLARITY SHOWN IN ALARM (+) (–) (+) (–) (ACTIVE) CONDITION >...
  • Page 27 SYSTEM SENSOR COMPATIBLE DEVICES Listed below are System Sensor models that provide audible and visible (AV) notification and conform to required synchronization protocols: WALL MOUNT WALL SPEAKER STROBES 2 Wire Horn/Strobe Std Candela Red SPSR Wall, Red, Selectable Candela, Speaker/Strobe P2RH 2 Wire Horn/Strobe Hi Candela Red SPSR-P...
  • Page 28 SYSTEM SENSOR COMPATIBLE DEVICES (CONT'D) SPANISH PAD PRINT "FUEGO" NO PAD PRINT "PLAIN" P2R-P 2 Wire Horn/Strobe Wall Std Candela Red - PLAIN SR-SP Strobe Std Candela Red - Fuego P2RK-P 3 Wire Horn/Strobe Wall Std Candela Red - PLAIN Outdoor SRH-SP Strobe Hi Candela Red - Fuego P2W-P...
  • Page 29 COOPER-WHEELOCK COMPATIBLE APPLIANCES The following tables list the appliances produced by Cooper Wheelock that are compatible with the Wheelock synchronization protocol: COMPATIBLE WHEELOCK APPLIANCES COMPATIBLE WHEELOCK SYNCHRONIZING HORNS WITH SYNCHRONIZING STROBES AH-12 AH-24 AMT-241575W AMT4-241575W AH-12WP AH-24WP AMT-2475W AMT4-2475W HS-24 MIZ-24S AMT-241575W-NYC AMT4-241575W-NYC...
  • Page 30 NOTES Gemini C-Series GEMC-NAC Extender Installation Instructions...
  • Page 31 NOTES Gemini C-Series GEMC-NAC Extender Installation Instructions...
  • Page 32: Napco Limited Warranty

    NAPCO. After repair or replacement, NAPCO NAPCO is not an insurer of either the property or safety of the user's assumes the cost of returning products under warranty. NAPCO shall...

This manual is also suitable for:

Gemc-nac7s