Standard Fittings; Duct Length - LG LMV1940DW Installation Instructions Manual

Hide thumbs Also See for LMV1940DW:
Table of Contents

Advertisement

STEP 2:
PREPARE THE VENTING SYSYTEM

STANDARD FITTINGS

NOTE: If the existing duct is round, you must use a rectangular-to-round adapter, with a rectangular 3"
extension duct installed between the damper assembly and the adapter to prevent the exhaust
damper's sticking.

DUCT LENGTH

The total length of the duct system, including straight duct, elbows, transitions, wall or roof caps must not
exceed the equivalent of 140 feet.
For best performance, do not use more than three 90 degree elbows.
Below are the standard fittings and their equivalent length in feet.

To calculate the equivalent length of each ductpiece used, see the examples below.
For 3 1/4"x10" SYSTEMS
3 1/4"x10"
90û elbow
2ft.
1-3 1/4" x 10" 90û elbow
1-Wall Cap
8 feet straight duct
TOTAL LENGTH
3 1/4"x10"
3 1/4"x10" roof
to 6"=5ft.
4
5
3 1/4"x10"
wall cap
90û elbow
=40ft.
=10ft.
6ft.
wall cap
=
25 ft.
=
40 ft.
=
8 ft.
=
73 ft.
!
3 1/4"x10" 90û
cap=24ft.
elbow=25ft.
6
7
45û elbow
=5ft.
.ECKHA '
Examples
For 6" ROUND SYSTEMS
90û elbows
transition
1-transition
2-90û elbows
1-Wall Cap
8 feet straight
TOTAL LENGTH
— 9 —
3 1/4"x10"
flat elbow
=10ft.
6ft.
2ft.
wall cap
=
5 ft.
=
20 ft.
=
40 ft.
=
8 ft.
=
73 ft.