Piping For Space Heaters - Rheem RTGH-95XLP-2 Use And Care Manual

95% condensing tankless water heater
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS

Piping for Space Heaters

Local codes or plumbing authority requirements may vary
from the instructions or diagrams provided in this manual
and take precedence over these instructions.
Combination Potable and Space
Heating Application
DANGERS:
When this system requires water for space heating at
elevated temperatures (above 125°F [52°C]), a mixing or
tempering valve MUST BE installed in the hot water supply
line to the house in order to reduce the scald hazard
potential.
Any piping or components used in the installation of
this water heater in a combination potable and space
heating application must be suitable for use with
Typical Combination Installation
64
Air
Separator
Shut-O
Valve
Air Handler
(Pump included)
drinking water.
If this water heater is installed in an application intended
to supply domestic hot water needs and hot water
for space heating purposes, DO NOT connect the
heater to an existing heating unit or components of a
heating system that have previously been used with a
nondrinking water system.
Toxic chemicals such as those used for boiler treatment
may be present and will contaminate the drinking water
supply causing possible health risks. Never introduce
toxic chemicals, such as glycol and those used for
boiler treatment, into this system.
This water heater is NOT approved as the dedicated
space heating unit.
This water heater must be used for combination
applications with air handler only and not for indoor
heating applications.
Union
Relief
Valve
Tempering
Valve
Tempered
Water
Tankless
Water Heater
Gas Supply
Line
Drain Valve
Cold Water Supply
Shut-O Valve
Check
Valve
Cold Water
Supply
Potable Water
Expansion Tank
(2 gallons)