PORTABLE FORCED AIR HEATERS
SERVICE
PROCEDURES
Continued
AIR OUTPUT, AIR INTAKE,
AND LINT FILTERS
1. Remove upper shell (see page 8).
2. Remove filter end cover screws using
5/16" nut-driver.
3. Remove filter end cover.
4. Replace air output and lint filters.
5. Wash or replace air intake filter (see
Preventative Maintenance Schedule,
page 6).
6. Replace filter end cover.
7. Replace fan guard and upper shell.
IMPORTANT: Do not oil filters
PUMP PRESSURE
ADJUSTMENT
1. Remove pressure gauge plug from filter
end cover.
2. Install accessory pressure gauge (part
number HA1180).
3.
Start heater (see Operation, page 5).
Allow motor to reach full speed.
4. Adjust pressure. Turn relief valve to
right to increase pressure. Turn relief
valve to left to decrease pressure. See
specifications below for correct pres-
sure for each model.
5. Remove pressure gauge. Replace pres-
sure gauge plug in filter end cover.
R
Lint Filter
Figure 13 - Air Output, Air Intake, and Lint Filters, B35CEH and B70CEH Models
Lint Filter
Figure 14 - Air Output, Air Intake, and Lint Filters, B100CEH and B150CEH Models
Pressure
Gauge
Plug
Plastic Cap
Figure 15 - Pressure Gauge Plug Removal
(B35CEH and B70CEH Models Shown)
10
Air Intake Filter
Filter End
Cover
Air Output
Filter
Air Intake Filter
Filter End
Cover
Air Output
Filter
Relief
Model
Valve
B35CEH
B70CEH
B100CEH
B150CEH
Pressure
Gauge
Figure 16 - Adjusting Pump Pressure
Fan Guard
Fan Guard
Pump
Pressure
(Bar/PSI)
0.200/2.9
0.338/4.9
0.338/4.9
0.380/5.5
105398