Specification - Mitsubishi Electric PKFY-P15VBM-ER3 Technical & Service Manual

Hide thumbs Also See for PKFY-P15VBM-ER3:
Table of Contents

Advertisement

4

SPECIFICATION

4-1. SPECIFICATIONS
Service ref.
Power source
Cooling capacity
(Nominal)
Power input
Current input
Heating capacity
(Nominal )
Power input
Current input
External finish
External dimension H x W x D
Net weight
Heat exchanger
Fan
Type x Quantity
External
static press.
Motor type
Motor output
Driving mechanism
Airflow rate
(Low-Mid2-Mid1-High)
Noise level (Low-Mid2-Mid1-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Diameter of
Liquid
(R410A)
(R410A)
Gas
refrigerant pipe
Field drain pipe size
Standard
Document
Accessory
attachment
Remark
Optional parts
External LEV Box
Installation
*1 Nominal cooling conditions
Indoor :
27°CDB/19°CWB (81°FDB/66°FWB)
Outdoor :
35°CDB (95°FDB)
Pipe length :
7.5 m (24-9/16 ft)
Level difference :
0 m (0 ft)
Notes:
1. Nominal conditions *1, *3 are subject to JIS B8615-1.
2. Due to continuing improvement, above specification may be subject to change without notice.
OCH418E
PKFY-P15VBM-E
PKFY-P15VBM-ER2
PKFY-P15VBM-ER3
PKFY-P15VBM-ER4
PKFY-P15VBM-ER5
1.7
kW
*1
kcal/h
1,450
*1
5,800
BTU/h
*1
kcal/h
1,500
*2
kW
0.04
0.20
A
kW
1.9
*3
*3
kcal/h
1,600
BTU/h
6,500
*3
kW
0.04
0.20
A
mm
295 × 815 × 225
inch
11-5/8" × 32-1/8" × 8-7/8"
kg (lb)
10 (23)
Line flow fan × 1
Pa
0
mmH
O
0
2
kW
0.017
m
/min
4.9 - 5.0 - 5.2 - 5.3
3
L/s
82 - 83 - 87 - 88
cfm
173 - 177 - 184 - 187
dB <A>
29 - 31 - 32 - 33
mm (inch)
ø6.35 (ø1/4")
ø12.7 (ø1/2")
mm (inch)
mm (inch)
I.D. 16 (5/8")
PAC-SG95LE-E
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
*2 Nominal cooling conditions
27°CDB/19.5°CWB (81°FDB/67°FWB)
35°CDB (95°FDB)
5 m (16-3/8 ft)
0 m (0 ft)
PKFY-P20VBM-E
PKFY-P20VBM-ER1
PKFY-P20VBM-ER2
PKFY-P20VBM-ER3
PKFY-P20VBM-ER4
PKFY-P20VBM-ER5
1-phase 220-240V 50Hz, 1-phase 220V 60Hz
2.2
1,900
7,500
2,000
0.04
0.20
2.5
2,200
8,500
0.04
0.20
Plastic, MUNSELL (1.0Y 9.2/0.2)
295 × 815 × 225
11-5/8" × 32-1/8" × 8-7/8"
10 (23)
Cross fin (Aluminum fin and copper tube)
Line flow fan × 1
0
0
1-phase induction motor
0.017
Direct-driven by motor
4.9 - 5.2 - 5.6 - 5.9
82 - 87 - 93 - 98
173 - 184 - 198 - 208
29 - 31 - 34 - 36
Polyethylene sheet
PP honeycomb
Fuse
LEV
R410A CITY MULTI
Flare
ø6.35 (ø1/4")
Flare
ø12.7 (ø1/2")
I.D. 16 (5/8")
Installation Manual, Instruction Book
PAC-SG95LE-E
*3 Nominal heating conditions
20°CDB (68°FDB)
7°CDB/6°CWB (45°FDB/43°FWB)
7.5 m (24-9/16 ft)
0 m (0 ft)
12
PKFY-P25VBM-E
PKFY-P25VBM-ER1
PKFY-P25VBM-ER2
PKFY-P25VBM-ER3
PKFY-P25VBM-ER4
PKFY-P25VBM-ER5
2.8
2,400
9,600
2,500
0.04
0.20
3.2
2,800
10,900
0.04
0.20
295 × 815 × 225
11-5/8" × 32-1/8" × 8-7/8"
10 (23)
Line flow fan × 1
0
0
0.017
4.9 - 5.2 - 5.6 - 5.9
82 - 87 - 93 - 98
173 - 184 - 198 - 208
29 - 31 - 34 - 36
Flare
ø6.35 (ø1/4")
Flare
ø12.7 (ø1/2")
I.D. 16 (5/8")
PAC-SG95LE-E
Unit converter
kcal/h = kW × 860
Btu/h = kW × 3,412
cfm
= m
lb
= kg/0.4536
Note: Above specification data
is subject to rounding
variation.
Flare
Flare
3
/min × 35.31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents