BUILDING VENTILATION DESIGN GUIDE
Method 5: Decoupled Dedicated Outdoor Air System (DDOAS)
Provide a separate, dedicated outdoor-air system designed to filter, condition, and dehumidify ventilation air and deliver it directly to the
conditioned space through a separate register or grille. This approach requires a separate independent ventilation duct system not
associated with the Duct-Free Split system.
LG recommends using the DDOAS method in all installations.
Advantages
• May be used with the full lineup of Duct-Free Split system indoor
units.
• The outdoor air unit may supply "neutral" air to the occupant space
even when the Duct-Free Split system indoor unit fan changes
speed or cycles on and off. DDOAS controls do not have to be
interlocked with the Duct-Free Split system.
• In lieu of installing localized smaller outside air treatment
equipment throughout the building, this method centralizes the
ventilation air source making service and filter changes easier and
less disruptive for the building occupants.
• Third-party demand control ventilation controls are more readily
accommodated.
Figure 32: Decoupled Dedicated Outdoor Air System (DDOAS).
Outdoor
Air Unit
54 | FOUR-WAY CASSETTE
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Disadvantages
• Ceiling space is required to accommodate ductwork between the
outdoor air unit and ceiling diffusers.
Methodology illustrations are for examples only and do not depict actual
indoor units for the specific outdoor unit pairing. These are generic illus-
trations to show ventilation design only.
Ceiling Diffuser
Indoor Unit