CONTENTS Getting Other Informations and Publications ..3 Start Up Important Installer Note ......... 19 Wall Mount General Information Crankcase Heaters ..........19 Heat Pump Wall Mount Model Nomenclature ..4 High Pressure Switch ..........19 Shipping Damage ............ 7 Three Phase Scroll Compressor Start Up ....
Getting Other Information and Publications These publications can help you install the air For more information, contact these conditioner or heat pump. You can usually find these at publishers: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE MODEL NUMBER CONTROL REVISIONS MODULES VOLTS & PHASE A - 230/208/60/1 COIL OPTIONS CAPACITY B - 230/208/60/3 X - Standard 38 - 3 Ton C - 460/60/3 1 - Phenolic Coated Evaporator 43 - 3½...
Any grille that meets with 5/8 inch louver criteria may Air Conditioning Contractors of America (ACCA). The be used. It is recommended that Bard Return Air Grille air duct should be installed in accordance with the Kit RG2 through RG5 or RFG2 through RFG5 be Standards of the National Fire Protection Association installed when no return duct is used.
FRESH AIR INTAKE CONDENSATE DRAIN – EVAPORATOR All units are built with fresh air inlet slots punched in A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are the service panel.
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. Failure to provide the 1/4 inch clearance 2. On wood frame walls, the wall construction must be between the supply duct and a combustible strong and rigid enough to carry the weight of the surface for the first 3 feet of duct can result in...
FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 – MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 1, FOR ACTUAL DIMENSIONS Manual 2100-413G Page 12 of 28...
WIRING – MAIN POWER WIRING – LOW VOLTAGE WIRING Refer to the unit rating plate for wire sizing information 230 / 208V, 1 phase and 3 phase equipment dual and maximum fuse or “HACR” type circuit breaker primary voltage transformers. All equipment leaves the size.
FIGURE 8 SHXXXDX – HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A2 ENERGY MONITOR FULL TIME DEHUMIDIFICATION Manual 2100-413G Page 15 of 28...
Page 16
FIGURE 9 SHXXXDX – HOT GAS REHEAT DURING DEHUMIDIFICATION WITH PROGRAMMABLE THERMOSTAT FULL TIME DEHUMIDIFICATION Manual 2100-413G Page 16 of 28...
FIGURE 10 10KW 1 PH — 6 & 9KW 3 PH TABLE 2 THERMOSTAT WIRE SIZE COMPRESSOR CUT OFF THERMOSTAT Outdoor thermostats are available to hold off various AND OUTDOOR THERMOSTATS banks of electric heat until needed as determined by outdoor temperature.
NOTE: For total and proper control using DDC, a LOW VOLTAGE CONNECTIONS total of 7 controlled outputs are required (6 if These units use a grounded 24 volt AC low voltage no ventilation system is installed). For proper circuit. system operation under Emergency Heat conditions where the compressor needs to be The “R”...
START UP FIGURE 11 IMPORTANT INSTALLER NOTE START UP LABEL For improved start up performance wash the indoor coil IMPORTANT with a dish washing detergent. THESE PROCEDURES MUST BE CRANKCASE HEATERS FOLLOWED AT INITIAL START UP SH491-B and -C are provided with compressor AND AT ANY TIME POWER HAS crankcase heat.
PHASE MONITOR HEATING SEQUENCE – On a call for heating, the compressor and reversing valve of the unit are energized All units with three phase compressors are equipped to provide heat pump heating. If the room temperature with a 3 phase line monitor to prevent compressor falls below the 2nd stage heating set point backup damage due to phase reversal.
There is a cycle speed up jumper on the control. This DEFROST CYCLE can be used to reduce the time between defrost cycle The defrost cycle is controlled by temperature and time operation without waiting for time to elapse. on the solid state heat pump control. See Figure 12. Use a small screwdriver or other metallic object, or When the outdoor temperature is in the lower 40°F another 1/4 inch QC, to short between the SPEEDUP...
TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL 3. Turn thermostat blower to “auto” position. Indoor TROUBLESHOOTING PROCEDURE blower should stop. NOTE: Many models have a 1-minute blower time delay on “off” command; 1. NOTE: A thorough understanding of the defrost wait for this to time-out. cycle sequence is essential.
3. Check resistance reading to chart of resistance use CHECKING TEMPERATURE SENSOR OUTSIDE sensor ambient temperature. (Tolerance of part is UNIT CIRCUIT ± 10%) 1. Disconnect temperature sensor from board and from 4. If sensor resistance reads very low, then sensor is outdoor coil.
REFRIGERANT CHARGE FAN BLADE SETTING DIMENSIONS Shown in Figure 13 are the correct fan blade setting The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with dimensions for proper air delivery across the outdoor a refrigerant charge shown on the unit serial plate.
TABLE 9 INDOOR BLOWER PERFORMANCE – CFM 230V / 460V Subtract .08 static for 2" filter NOTE: SH381 is shipped with the indoor NOTE: SH431 and SH491 are shipped with blower on medium speed for ducted the indoor blower on high speed for applications.
TABLE 10 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.