2.1.1. Switching circuit connection diagram, Time chart,
Parameter settings
F L
FLA
FLC
(Commercial
power)
S3
RY1(Inverter)
MC2
RY2(Commercial
power)
MC3
Title
Output signal selection of commercial
power/inverter switching
Commercial power/inverter switching
frequency
*3
Inverter side switching waiting time
Commercial power side switching waiting
*3
time
Commercial power switching frequency
holding time
*1
Input terminal selection #6 (S2)
Input terminal selection #7 (S3)
Output terminal selection #1 (OUT1)
Output terminal selection #2 (OUT2)
*1:Be careful about Items 5 and 7 in 2.2, "Precautions."
*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of
*3: and are included the operation time of the relay and the magnet contactor.
In almost all cases, it is not necessary to change these parameter settings.
Inverter protective
action signal
FLX
(Inverter)
S3
MC2
MC3
MC1
F
Function
Commercial power switching
frequency hold time
Commercial power
switching frequency
Setting frequency
0Hz
P24-OUT1(RY1)
for inverter run
output
P24-OUT2(RY2)
for commercial
power run output
Commercial power
run switching signal
S3-CC
Run signal
ON
F-CC
Stand-by signal
ON
ST-CC
Inverter run
Adjustment range
0 to 3
0 to
0.1 to 10.0 seconds
0.37 to 10.0 seconds
0.1 to 10.0 seconds
0 to 135
0 to 135
0 to 119
0 to 119
8
Frequency after speed is
detected
Inverter-side switching
*2
wait time
ON
Commercial power
switching wait time
ON
ON
Commercial power run
Setting value
Power supply frequency
Different for each model
(Emergency stop)
(Commercial power run
switching)
(Commercial power/inverter
switching output 1)
(Commercial power/inverter
switching output 2)
E 6 5 8 1 3 6 4
Speed detection time
ON
ON
Inverter run
2 or 3
0.62
2.0
20
102
46
48